Smith Cast Iron Boilers GB250 SERIES Скачать руководство пользователя страница 19

19

This boiler has been designed to provide years of
trouble free perfor mance in nor mal installations.
Examination by the homeowner at the beginning of each
heating season, and in mid-heating season, should
assure continued good performance. In addition, the
boiler should be examined by a qualified ser vice
professional at least once every year.

NOTE: Do not draw water from heating system for
cleaning. Minerals in the water can build up on the
heat transfer surfaces and cause overheating and
subsequent failure of the cast iron sections.

NOTE: Do not obstruct the flow of combustion and
ventilation air.

NOTE: If boiler is equipped with a low water cutoff,
follow manufacturer's maintenance instructions.

BEFORE EACH HEATING SEASON

1. Remove and inspect draft hood and vent piping
(connecting draft hood to chimney or vent) for
obstructions, soot accumulation, rust or corrosion. Clean
and replace as necessary. Check tightness of joints;
seal all joints where necessary.

2. Check boiler flue passageways in the boiler sections
for any blockage or soot accumulation. Remove draft
hood, jacket top and flue collector. Using a flashlight,
examine all flue passageways.  

a. If passageways are free of soot and obstructions,
replace flue collector and seal with furnace cement.

b. If passageways need cleaning, remove burners as
described in paragraph 3 below. Insert long-handle
bristle flue brush down between section tubes and
upward through sections from combustion chamber in
both diagonal directions to remove carbon from
finned surfaces. Vacuum debr is. Replace flue
collector and seal with furnace cement. 

c. Reinstall jacket top panel and draft hood.

3. Check and clean burner assembly. Remove burner
access panel. Lift burners up and to rear until burners
are disengaged from orifices. Brush top of burners with
soft bristle brush and blow out with air or vacuum.

4. Check gas manifold for proper position and
reassemble burners to the manifold. Line up holes in
burners with the orifices, and slide assembly back into
position. BE SURE TO REINSTALL BURNERS WITH
BURNER PORTS ON THE TOP SURFACE (UPRIGHT).

5. When a low water cut-off has been utilized, follow the
manufacturer’s maintenance instr uctions. As a
minimum, test the operation of electronic controls at
least once a year. Remove, clean and inspect the probe.
If the LWCO fails to operate proper ly it must be
replaced. Float type controls should be flushed once a
month during the heating season.

6. Follow "System Start-Up & Adjustments" procedures
in Section 3 of this manual.

Steam Boiler Cleaning Instructions

The following procedures must be followed on initial
start-up and if the presence of sediment, sludge or
impurities hamper proper boiler operations.

1. With gate valves closed on supply and return lines,
start burner and allow boiler to become pressurized so
that the pressuretrol may be adjusted and set for limit
cut-off desired (normally about 3 psi). Turn off burner
and allow pressure to drop to 0 psi., then proceed with
the following cleaning procedure.

2. Remove the pressure relief valve.

3. Add caustic soda (lewis lye) through this opening at
the rate of one pound per thousand square feet of
radiation capacity. Scout, Squirk or similar steam boiler
cleaners may be used instead of lye. Tr isodium
phosphate (1/4#) is also an excellent cleaner.

4. Provide pipe connection (full size) from pressure relief
valve opening to a convenient drain to serve as a vent.

5. Fill the boiler with a manual fill valve until water starts
to trickle from this pipe.

6. Fireboiler at sufficient rate to generate and maintain
steam. Entrained water and impurities will then discharge
(with steam) from open vent. Add water as necessary so
that the low water cutoff does not shut off burner.

SECTION 4: MAINTENANCE

DANGER:To avoid fire and explosion hazards: Do
not store anything against the boiler or allow dirt or
debris to accumulate in the area immediately
surrounding the boiler.  Keep boiler area clear and
free from combustible materials, gasoline and other
flammable vapors and liquids. Lint, paper or rags
must not be allowed to accumulate near the burners.
Do not place clothing on boiler to dry.

TO TURN OFF APPLIANCE

1.  Set the thermostat to lowest setting.
2.  Turn off all electric power to the appliance if service is to be performed.
3.  Turn gas control knob counterclockwise to "OFF".  Do not force.

Содержание GB250 SERIES

Страница 1: ...pment of Boiler 4 SECTION 2 BOILER INSTALLATION Step 1 Locating Setting Boiler 5 Step 2 Installing Steam Piping 6 Step 3 Installing Hydronic Components 7 Step 4 Venting Boiler 7 Step 5 Installing Testing Gas Piping 10 Step 6 Wiring Boiler 11 SECTION 3 START UP OPERATION Sequence Of Operation 16 Prior To Start Up 16 Start Up Adjustments 16 SECTION 4 MAINTENANCE Before Each Heating Season 19 How To ...

Страница 2: ... local codes 2 DANGER Indicates an imminently hazardous situation which if not avoided will result in death serious injury or substantial property damage WARNING Indicates a potentially hazardous situation which if not avoided could result in death serious injury or substantial property damage CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor injury or pr...

Страница 3: ...utlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to previous conditions of use 7 Any improper operation of the common venting sys tem should be corrected so the installation conforms with National Fuel Gas Code ANSI Z223 1 latest edition When resizing any portion of the common venting system the common venting system should be resized to approac...

Страница 4: ...rubber seals Water treatment chemicals and system cleaning chemicals must be compatible with this and all other construction materials SHIPMENT OF BOILER Each boiler is shipped in a single carton Draft hood is shipped in a separate carton on larger models Optional Vent Damper When ordered the vent damper is shipped in an individual carton packaged with the boiler Mounting of the damper is required...

Страница 5: ...s are proper as shown Local requirements may specify greater clearances must be adhered to Boiler shall be install ed such that the gas ignition system com ponents are protected from water dripping spraying rain etc during appliance oper ation and service WARNING Never install boiler on combustible flooring without combustible flooring pan or on carpeting as heat damage and or fire may result FIGU...

Страница 6: ...ing connections are shown in Figure 2 3 All external piping must be supported by hangers not by the boiler or its accessories Supply outlet must run full size from boiler to a header at least 24 above top of boiler Condensate return piping should be connected to boiler through a Hartford Loop Install gate valves in supply and return Proper steam piping practices must be followed at all times Maint...

Страница 7: ... and GB250 6 boilers Applicable boiler is equipped with a factory mounted spill switch harness mounting bracket assembly spill switch is provided in plastic bag See Figure 2 5 Install mounting bracket on outside surface of draft hood shroud with screws provided HARNESS MUST BE ON OUTSIDE OF SHROUD Install spill switch in hole in shroud on outside surface with screws provided Plug wiring leads from...

Страница 8: ...t force it closed as it may damage the gear train and void the warranty The blade should move freely and without obstruction Secure the vent damper housing to the drafthood outlet with sheet metal screws or pop rivets Refer to Figure 2 8 for fastener locations Install flue pipe over top of vent damper and secure to damper housing with sheet metal screws or pop rivets Attach vent damper cable to ca...

Страница 9: ...t draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from cigarette cigar or pipe 6 After it has been determined that each appliance remaining connected to common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to previous conditions of use...

Страница 10: ...0 990 1 600 2 800 5 800 90 10 22 40 84 160 320 490 930 1 500 2 600 5 400 100 9 21 38 79 150 305 460 870 1 400 2 500 5 100 125 8 18 34 72 130 275 410 780 1 250 2 200 4 500 150 8 17 31 64 120 250 380 710 1 130 2 000 4 100 175 7 15 28 59 110 225 350 650 1 050 1 850 3 800 200 6 14 26 55 100 210 320 610 980 1 700 3 500 1 4 3 8 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 326 493 622 824 1 049 1 380 1 610 2 067 2 ...

Страница 11: ... right of the primary pressuretrol when facing the front of the boiler Connect wiring assemblies provided on boiler from the low water cut off or transformer to the primary pressure control and from the gas valve to the secondary pressure control as shown in Fig 2 12 Do not readjust the secondary pressuretrol its purpose is to interrupt thermocouple power to the gas valve in case the primary press...

Страница 12: ...NOTE Boiler transformer must not be used to power external accessories i e zone valves relays etc Otherwise transformer will be overloaded and burn out 12 FIGURE 2 13 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS WITH STANDING PILOT MCDONNELL MILLER 67 LOW WATER CUT OFF EXCEPT GB250 8 GB250 9 N G FIGURE 2 14 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT MCDONNELL MILLE...

Страница 13: ...ILERS EQUIPPED WITH INTERMITTENT PILOT VENT DAMPER MCDONNELL MILLER 67 LOW WATER CUT OFF FIGURE 2 14 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER MCDONNELL MILLER 67 LOW WATER CUT OFF EXCEPT FOR GB250 8 GB250 9 N G ...

Страница 14: ...SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER MCDONNELL MILLER 67 LOW WATER CUT OFF FOR GB250 8 GB250 9 N G FIGURE 2 16 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH INTERMITTENT PILOT VENT DAMPER 400 SERIES LWCO ...

Страница 15: ...ATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER 400 SERIES LWCO EXCEPT FOR GB 250 8 9 FIGURE 2 18 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER 400 SERIES LWCO GB250 8 9 ONLY ...

Страница 16: ...er sits SYSTEM START UP ADJUSTMENTS Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the boiler underwent tests specified in ANSI Z21 13 1 Check combination gas valve on boiler and make sure it is in the OFF position 2 For vent damper equipped models with the thermostat set to call for heat observe that vent damper positio...

Страница 17: ...essures If rated input cannot be obtained with adjustment gas supply pressure or orifice size may be cause Consult local utility and Smith 8 Gas burner orifices supplied with boiler have been carefully designed to provide correct gas input rate for most gas conditions typically found in the U S and Canada Occasionally however local gas characteristics may not allow unit to be properly adjusted for...

Страница 18: ...nclosing the pilot 7 Find pilot Follow metal tube from gas control The pilot is between the central burner tubes behind the base door 8 Turn knob on gas control counterclockwise to Pilot 9 Push down and hold the red button Immediately light the pilot with a match Continue to hold the red button down for about one 1 minute after the pilot is lit Release button and it will pop back up Pilot should r...

Страница 19: ...ON THE TOP SURFACE UPRIGHT 5 When a low water cut off has been utilized follow the manufacturer s maintenance instructions As a minimum test the operation of electronic controls at least once a year Remove clean and inspect the probe If the LWCO fails to operate properly it must be replaced Float type controls should be flushed once a month during the heating season 6 Follow System Start Up Adjust...

Страница 20: ...can also be checked by using a pin gauge 4 All orifices are screwed into the manifold and may be removed by using a 5 8 wrench or socket 5 Reverse procedures above to install orifices and burners BE SURE TO REINSTALL BURNERS WITH BURNER PORTS ON TOP SURFACE UPRIGHT HEATING SYSTEM PROBLEMS CAUSES No Heat 1 Blown fuse or circuit breaker 2 Switch turned off 3 Pilot outage 4 IID system malfunction 5 F...

Страница 21: ...ld 63276 1 1 Manifold 59123 1 Manifold 63278 1 Manifold 59125 1 Manifold 59126 1 11 Burner Orifice No 31 N G 59141 6 Burner Orifice No 32 N G 59142 5 9 10 Burner Orifice No 33 N G 59143 8 Burner Orifice No 34 N G 59144 5 Burner Orifice No 52 L P 59150 5 5 6 8 9 10 MODEL GB250 SERIES REPLACEMENT PARTS LIST ORDERING INFORMATION When ordering replacement parts provide the model and serial number show...

Страница 22: ...Hood 8 For Spill Switch 59217 1 Draft Hood 8 59218 1 Draft Hood 9 59219 1 1 31 Junction Box 4 x 4 60178 1 1 1 1 1 1 Silicone Sealant 11 oz 40440 3 8 Fiberglass Rope 5 Ft Block to Base Seal 60024 32 Vent Damper 7 w Harness Ass y 69496 1 1 Vent Damper 8 w Harness Ass y 69497 1 1 Vent Damper 9 w Harness Ass y 69498 1 1 Cable Bracket 59270 1 1 1 1 1 1 33 Manual Reset Spill Switch 59273 1 1 1 34 Manual...

Страница 23: ...51B 1103 72360 1 1 Pilot Ass y L P Q3451B 1103 72361 1 N A N A Pilot Ass y L P Q3451B 1103 70008 1 10 Gas Valve N G VR8304P 4332 59136 1 1 1 1 1 1 Gas Valve L P VR8304P 3340 59137 1 1 1 Gas Valve L P VR8304P 4330 59138 1 1 1 Ignition Control S8600M 1013 51177 1 1 1 1 1 1 Ignition Cable 36 Lg 59308 1 1 1 1 1 1 30 Transformer 120 24 1006 43VA 50172 1 1 1 1 1 1 23 REF GB250 GB250 GB250 GB250 GB250 GB...

Страница 24: ...24 29 33 17 15 14 13 18 19 25 27 10 6 7 4 3 11 31 30 5 2 28 32 1 JACKET ASSEMBLY 34 16 26 9 23 24 22 ...

Страница 25: ...ce venting system pipes or chimney escaping into the living space Flames coming out around the appliance Yellow colored flames in the appliance Stale or smelly air The presence of soot or carbon in or around the appliance Very high unexplained humidity inside the building If any of the symptoms CO poisoning occur or if any of the signs of carbon monoxide are present vacate the premises immediately...

Страница 26: ...26 ...

Страница 27: ...27 ...

Страница 28: ...WESTCAST INC 260 NORTH ELM STREET WESTFIELD MA 01085 TEL 413 562 9631 FAX 413 562 3799 www smithboiler com ...

Отзывы: