WARNING:

If you do not follow these instructions exactly, a fire or explosion may result with property damage, personal injury, or loss of life.

A.

BEFORE OPERATING smell all around the appliance

area for gas.  Be sure to smell next to the floor because some
gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electrical switch; do not use any 
phone in your building.

Follow the gas supplier's instructions.

If you cannot reach your gas supplier, call the fire 
department.

B.

Use only your hand to push in or turn the gas control

knob. Never use tools. If the knob will not push in or turn by
hand, don't try to repair it; call a qualified service technician.
Force or attempted repair may result in a fire or explosion.

C.  Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.

LIGHTING CONTINUOUS PILOT INSTRUCTIONS

Standing Pilot Honeywell VR8300 and White Rodgers 36C04 - Natural or Propane Gas

This appliance has a pilot which must be lit by hand.  When lighting the pilot, follow these instructions exactly.

1.

STOP!  Read the safety information on this page.

2.

Set the thermostat to lowest setting.

3.

Turn off all electric power to the appliance.

4.

Turn gas control knob clockwise to "OFF".

(For WR-36C04) Push in gas control slightly and tur n
clockwise to "OFF" unless knob is pushed in slightly.  Do not
force.
5.

Wait five (5) minutes to clear out any gas.  Then smell for

gas, including near the floor.  If you then smell gas, STOP!
Follow "A" in the safety information above.  If you don't smell
gas, go to the next step.
6.

Remove the base door covering the top of the burners

and enclosing the pilot.
7.

Find pilot - Follow metal tube from gas control.  The pilot

is between the central burner tubes behind the base door.
8.

Turn knob on gas control counterclockwise to "Pilot".

9.

Push down and hold the red button.  Immediately light the

pilot with a match.
Continue to hold the red button down for about one (1) minute
after the pilot is lit.
Release button and it will pop back up.  Pilot should remain lit.
If it goes out, repeat steps 4 through 9.

If button does not pop up when released, stop

immediately and call your service technician or gas supplier.

If the pilot will not stay lit after several tries, turn the gas

control knob to "OFF" and call your service technician or gas
supplier.
10. Replace the base door.
11. Turn gas control knob counterclockwise to "ON".
12. Turn on all electric power to the appliance.
13. Set thermostat to desired setting.

INLET

GAS CONTROL KNOB 
SHOWN IN "OFF" POSITION

GAS 

ON

OFF

RESET BUTTON

PILOT

INLET

GAS CONTROL KNOB 
SHOWN IN "ON" POSITION

GAS 

OFF

ON

Honeywell VR8300

WR-36C04

OPERATING INSTRUCTIONS

Intermittent Ignition White Rodgers 36C74/Honeywell VR8304

Honeywell VR8304

1. STOP!  Read the safety information on this page.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device 

which automatically lights the pilot.  Do not try to light the 
pilot by hand.

5. Turn gas control knob clockwise to "OFF".
6. Wait five (5) minutes to clear out any gas.  Then 

smell for gas, including near the floor.  If you then smell 
gas, STOP!  Follow "A" in the safety information on page 
18.  If you don't smell gas, go to next step.

7. Turn gas control knob counterclockwise to "ON".
8. Turn on all electric power to the appliance.
9. Set the thermostat to the desired setting.

10. If the appliance will not operate, follow the instructions "To

Turn Off Appliance" and call your service technician or 
gas  supplier.

WR-36C74 

INLET

GAS CONTROL KNOB 
SHOWN IN "ON" POSITION

GAS 

OFF

ON

INLET

GAS CONTROL KNOB 
SHOWN IN "OFF" POSITION

GAS 

ON

OFF

Содержание GB250 SERIES

Страница 1: ...pment of Boiler 4 SECTION 2 BOILER INSTALLATION Step 1 Locating Setting Boiler 5 Step 2 Installing Steam Piping 6 Step 3 Installing Hydronic Components 7 Step 4 Venting Boiler 7 Step 5 Installing Testing Gas Piping 10 Step 6 Wiring Boiler 11 SECTION 3 START UP OPERATION Sequence Of Operation 16 Prior To Start Up 16 Start Up Adjustments 16 SECTION 4 MAINTENANCE Before Each Heating Season 19 How To ...

Страница 2: ... local codes 2 DANGER Indicates an imminently hazardous situation which if not avoided will result in death serious injury or substantial property damage WARNING Indicates a potentially hazardous situation which if not avoided could result in death serious injury or substantial property damage CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor injury or pr...

Страница 3: ...utlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to previous conditions of use 7 Any improper operation of the common venting sys tem should be corrected so the installation conforms with National Fuel Gas Code ANSI Z223 1 latest edition When resizing any portion of the common venting system the common venting system should be resized to approac...

Страница 4: ...rubber seals Water treatment chemicals and system cleaning chemicals must be compatible with this and all other construction materials SHIPMENT OF BOILER Each boiler is shipped in a single carton Draft hood is shipped in a separate carton on larger models Optional Vent Damper When ordered the vent damper is shipped in an individual carton packaged with the boiler Mounting of the damper is required...

Страница 5: ...s are proper as shown Local requirements may specify greater clearances must be adhered to Boiler shall be install ed such that the gas ignition system com ponents are protected from water dripping spraying rain etc during appliance oper ation and service WARNING Never install boiler on combustible flooring without combustible flooring pan or on carpeting as heat damage and or fire may result FIGU...

Страница 6: ...ing connections are shown in Figure 2 3 All external piping must be supported by hangers not by the boiler or its accessories Supply outlet must run full size from boiler to a header at least 24 above top of boiler Condensate return piping should be connected to boiler through a Hartford Loop Install gate valves in supply and return Proper steam piping practices must be followed at all times Maint...

Страница 7: ... and GB250 6 boilers Applicable boiler is equipped with a factory mounted spill switch harness mounting bracket assembly spill switch is provided in plastic bag See Figure 2 5 Install mounting bracket on outside surface of draft hood shroud with screws provided HARNESS MUST BE ON OUTSIDE OF SHROUD Install spill switch in hole in shroud on outside surface with screws provided Plug wiring leads from...

Страница 8: ...t force it closed as it may damage the gear train and void the warranty The blade should move freely and without obstruction Secure the vent damper housing to the drafthood outlet with sheet metal screws or pop rivets Refer to Figure 2 8 for fastener locations Install flue pipe over top of vent damper and secure to damper housing with sheet metal screws or pop rivets Attach vent damper cable to ca...

Страница 9: ...t draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from cigarette cigar or pipe 6 After it has been determined that each appliance remaining connected to common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to previous conditions of use...

Страница 10: ...0 990 1 600 2 800 5 800 90 10 22 40 84 160 320 490 930 1 500 2 600 5 400 100 9 21 38 79 150 305 460 870 1 400 2 500 5 100 125 8 18 34 72 130 275 410 780 1 250 2 200 4 500 150 8 17 31 64 120 250 380 710 1 130 2 000 4 100 175 7 15 28 59 110 225 350 650 1 050 1 850 3 800 200 6 14 26 55 100 210 320 610 980 1 700 3 500 1 4 3 8 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 326 493 622 824 1 049 1 380 1 610 2 067 2 ...

Страница 11: ... right of the primary pressuretrol when facing the front of the boiler Connect wiring assemblies provided on boiler from the low water cut off or transformer to the primary pressure control and from the gas valve to the secondary pressure control as shown in Fig 2 12 Do not readjust the secondary pressuretrol its purpose is to interrupt thermocouple power to the gas valve in case the primary press...

Страница 12: ...NOTE Boiler transformer must not be used to power external accessories i e zone valves relays etc Otherwise transformer will be overloaded and burn out 12 FIGURE 2 13 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS WITH STANDING PILOT MCDONNELL MILLER 67 LOW WATER CUT OFF EXCEPT GB250 8 GB250 9 N G FIGURE 2 14 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT MCDONNELL MILLE...

Страница 13: ...ILERS EQUIPPED WITH INTERMITTENT PILOT VENT DAMPER MCDONNELL MILLER 67 LOW WATER CUT OFF FIGURE 2 14 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER MCDONNELL MILLER 67 LOW WATER CUT OFF EXCEPT FOR GB250 8 GB250 9 N G ...

Страница 14: ...SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER MCDONNELL MILLER 67 LOW WATER CUT OFF FOR GB250 8 GB250 9 N G FIGURE 2 16 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH INTERMITTENT PILOT VENT DAMPER 400 SERIES LWCO ...

Страница 15: ...ATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER 400 SERIES LWCO EXCEPT FOR GB 250 8 9 FIGURE 2 18 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS EQUIPPED WITH STANDING PILOT VENT DAMPER 400 SERIES LWCO GB250 8 9 ONLY ...

Страница 16: ...er sits SYSTEM START UP ADJUSTMENTS Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the boiler underwent tests specified in ANSI Z21 13 1 Check combination gas valve on boiler and make sure it is in the OFF position 2 For vent damper equipped models with the thermostat set to call for heat observe that vent damper positio...

Страница 17: ...essures If rated input cannot be obtained with adjustment gas supply pressure or orifice size may be cause Consult local utility and Smith 8 Gas burner orifices supplied with boiler have been carefully designed to provide correct gas input rate for most gas conditions typically found in the U S and Canada Occasionally however local gas characteristics may not allow unit to be properly adjusted for...

Страница 18: ...nclosing the pilot 7 Find pilot Follow metal tube from gas control The pilot is between the central burner tubes behind the base door 8 Turn knob on gas control counterclockwise to Pilot 9 Push down and hold the red button Immediately light the pilot with a match Continue to hold the red button down for about one 1 minute after the pilot is lit Release button and it will pop back up Pilot should r...

Страница 19: ...ON THE TOP SURFACE UPRIGHT 5 When a low water cut off has been utilized follow the manufacturer s maintenance instructions As a minimum test the operation of electronic controls at least once a year Remove clean and inspect the probe If the LWCO fails to operate properly it must be replaced Float type controls should be flushed once a month during the heating season 6 Follow System Start Up Adjust...

Страница 20: ...can also be checked by using a pin gauge 4 All orifices are screwed into the manifold and may be removed by using a 5 8 wrench or socket 5 Reverse procedures above to install orifices and burners BE SURE TO REINSTALL BURNERS WITH BURNER PORTS ON TOP SURFACE UPRIGHT HEATING SYSTEM PROBLEMS CAUSES No Heat 1 Blown fuse or circuit breaker 2 Switch turned off 3 Pilot outage 4 IID system malfunction 5 F...

Страница 21: ...ld 63276 1 1 Manifold 59123 1 Manifold 63278 1 Manifold 59125 1 Manifold 59126 1 11 Burner Orifice No 31 N G 59141 6 Burner Orifice No 32 N G 59142 5 9 10 Burner Orifice No 33 N G 59143 8 Burner Orifice No 34 N G 59144 5 Burner Orifice No 52 L P 59150 5 5 6 8 9 10 MODEL GB250 SERIES REPLACEMENT PARTS LIST ORDERING INFORMATION When ordering replacement parts provide the model and serial number show...

Страница 22: ...Hood 8 For Spill Switch 59217 1 Draft Hood 8 59218 1 Draft Hood 9 59219 1 1 31 Junction Box 4 x 4 60178 1 1 1 1 1 1 Silicone Sealant 11 oz 40440 3 8 Fiberglass Rope 5 Ft Block to Base Seal 60024 32 Vent Damper 7 w Harness Ass y 69496 1 1 Vent Damper 8 w Harness Ass y 69497 1 1 Vent Damper 9 w Harness Ass y 69498 1 1 Cable Bracket 59270 1 1 1 1 1 1 33 Manual Reset Spill Switch 59273 1 1 1 34 Manual...

Страница 23: ...51B 1103 72360 1 1 Pilot Ass y L P Q3451B 1103 72361 1 N A N A Pilot Ass y L P Q3451B 1103 70008 1 10 Gas Valve N G VR8304P 4332 59136 1 1 1 1 1 1 Gas Valve L P VR8304P 3340 59137 1 1 1 Gas Valve L P VR8304P 4330 59138 1 1 1 Ignition Control S8600M 1013 51177 1 1 1 1 1 1 Ignition Cable 36 Lg 59308 1 1 1 1 1 1 30 Transformer 120 24 1006 43VA 50172 1 1 1 1 1 1 23 REF GB250 GB250 GB250 GB250 GB250 GB...

Страница 24: ...24 29 33 17 15 14 13 18 19 25 27 10 6 7 4 3 11 31 30 5 2 28 32 1 JACKET ASSEMBLY 34 16 26 9 23 24 22 ...

Страница 25: ...ce venting system pipes or chimney escaping into the living space Flames coming out around the appliance Yellow colored flames in the appliance Stale or smelly air The presence of soot or carbon in or around the appliance Very high unexplained humidity inside the building If any of the symptoms CO poisoning occur or if any of the signs of carbon monoxide are present vacate the premises immediately...

Страница 26: ...26 ...

Страница 27: ...27 ...

Страница 28: ...WESTCAST INC 260 NORTH ELM STREET WESTFIELD MA 01085 TEL 413 562 9631 FAX 413 562 3799 www smithboiler com ...

Отзывы: