- 18 -
echo or lost the sensor
)
5.Relay1 Set Point
(Relay
1~6
Set point Setting is
same here)
According to the corresponding
relay parameter PV value is greater
than or less than this value, the relay
1-6 action, on or off,determined by
the corresponding parameters of the
relay.
(
When set to Fail Alarm the value
is invalid, the unit depending on the
level
unit,
the
integer
digits
depending on weir type
)
Damping Setup:
Increase the damping value can stable the level/distance value result, but can
make the instrument response slowly, and vice versa.
Damping Setup
Ranging from 0.1~100m/min
default:
50m/min
Current Fixed
Under special circumstances, the instrument has a larger error between
actual output current and display current, the instrument need to do current
fixing. (The factory has been set to optimal values , do not need to modify)