Installation
16
U.S. Installation only / 3-wire branch
circuit
Refer to figure, where local codes allow the
connection of the ground wire from the
oven to the power supply cable neutral
wire (white wire):
• The ground wire must be connected first;
• If local codes permit, connect the green
or yellow-green ground wire from the
range and the white wire from the range
to the power supply neutral wire (white
wire).
• Connect the red and black leads from
the range to the matching color wires in
the junction box using UL/CSA listed
wire connectors.
U.S. and Canada installation / 4-wire
branch circuit
• Separate the green or yellow-green
wires from the white wires that extend out
of the end of the appliance cable.
• The ground wire must be connected first.
• Connect the green or yellow-green
ground wire from the appliance to the
ground wire in the junction box (green
colored wire) using UL/CSA listed wire
connectors. Do not connect the
grounding wire to the neutral wire in the
junction box.
• Connect the red and black leads from
the appliance to the matching color
wires in the junction box using UL/CSA
listed wire connectors.
• Connect the white wire from the
appliance to the neutral white wire in the
junction box using a UL/CSA listed wire
connector.
A
cable from power supply
bw
black wires
B
junction box
gw
white-green or yellow-green wires
C
cable from range
rw
red wires
D
UL/CSA listed conduit connector
ww
white wires