Conversion Kit
5
1)
Check that the main gas supply line to the range is shut off and that the
power supply cord is disconnected.
2)
Remove access cap “A” by using a screwdriver or a coin, turning the access cap counterclockwise.
The gas pressure regulator has two settings which are indicated on two sides of the cap. Turn the cap
and reinstall it in the regulator with "LP" visible from the outside of the regulator.
Incoming line pressure upstream
from the regulator must be 1” (2.5
cm) W.C.P. higher than the manifold
pressure in order to check the
regulator. Incoming line pressure to
the regulator should be as follows for
operation and checking the regulator
setting: - NATURAL GAS:
Set pressure to 4” W.C.P. Incoming
line pressure of 3
1
/
2
” - 10
1
/
2
” W.C.P
maximum; - LP GAS: Set pressure
to 11” W.C.P. Incoming line pressure
8”- 13” W.C.P. maximum.
The range must be isolated from the gas supply piping system by turning off the respective manual shut-
off valve during any pressure testing of the gas supply piping system at test pressures equal to or
greater than 1/2 psig (3.5 kPa).
Replacing the rangetop's burners nozzles
(This operation does not require primary air regulation.)
3)
1 Remove the grates and all the burner caps and
heads;
2 Unscrew the burner nozzles with a 7 mm socket
wrench;
3 Replace the nozzles according to the type of gas to
be used and the description in paragraph 3.2
“Burner and nozzle characteristics table”.
Put the burners back in their correct position.