Document Revision: 2.A
T18054
FieldServer
BACnet Router FS-ROUTER-BACX
Start-up Guide
BAS Router (BACnet Multi-Network Router)
APPLICABILITY & EFFECTIVITY
The instructions are effective for the above as of July 2018.
Страница 1: ...ent Revision 2 A T18054 FieldServer BACnet Router FS ROUTER BACX Start up Guide BAS Router BACnet Multi Network Router APPLICABILITY EFFECTIVITY The instructions are effective for the above as of July...
Страница 2: ...pport needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email s...
Страница 3: ...3 10 100 Ethernet Connection Port 14 5 Operation 14 5 1 Power Up the Device 14 6 Connecting to the BACnet Router 15 6 1 Using the FieldServer Toolbox 15 6 2 Using a Web Browser Directly 16 7 Configur...
Страница 4: ...n Resistor Jumper 10 Figure 6 Power Jumper Switch 11 Figure 7 Bias Resistor DIP Switches EOL 12 Figure 8 Port 1 RS 485 Connection 13 Figure 9 Port 2 RS 485 Connection 13 Figure 10 Ethernet Connection...
Страница 5: ...MC Cloud NOTE For SMC Cloud information refer to the SMC Cloud Start up Guide online at the Sierra Monitor website NOTE The latest versions of instruction manuals driver manuals configuration manuals...
Страница 6: ...part FS 8915 35 QS WARNING Install only as instructed failure to follow the installation guidelines or using screws without the DIN rail mounting bracket could result in permanent damage to the produc...
Страница 7: ...BACnet Router Start up Guide Page 7 of 27 3 2 Dimensions 3 2 1 Dimension Drawing FS ROUTER BAC1 R2 Port Figure 2 FS ROUTER BAC1...
Страница 8: ...BACnet Router Start up Guide Page 8 of 27 3 2 1 Dimension Drawing FS ROUTER BAC R1 Port R2 Port Figure 3 FS ROUTER BAC...
Страница 9: ...sistors typically pull one line high and the other low far away from the decision point of the logic In the RS 485 carrier the bias resistor is 510 ohms which is in line with the BACnet spec It should...
Страница 10: ...ation Resistor Termination resistors are also used to reduce noise These pull the two lines of an idle bus together However they would override the effect of any bias resistors if connected Terminatio...
Страница 11: ...ther power supply requirements Position A The Carrier makes use of a full wave rectifying bridge Can be used for 12 24VAC input or 9 30VDC input At 9VDC this becomes marginal Position B The Carrier ma...
Страница 12: ...etting is OFF switch position right side o To enable biasing turn the bias switch ON switch position left side NOTE Biasing only needs to be enabled on one device The BACnet Router has 510 ohm resisto...
Страница 13: ...he 3 pin connector as shown The following Baud Rates are supported on the R1 Port 9600 19200 38400 57600 76800 115200 4 2 RS 485 Connection R2 Port Connect to the 3 pins on the left hand side of the 6...
Страница 14: ...poses via an Ethernet cable between the PC and the BACnet Router or connect the BACnet Router and the PC to the switch using a straight CAT5 cable 5 OPERATION 5 1 Power Up the Device Apply power to th...
Страница 15: ...Internet using Toolbox add the Internet exposed IP Address of the Router by clicking on the button or alternatively enter the Internet exposed IP Address in a web browser directly 6 1 Using the Field...
Страница 16: ...fferent IP Networks assign a Static IP Address to the PC on the 192 168 2 X network NOTE The FieldPoP tab see Figure 12 allows users to connect to the SMC Cloud Sierra Monitor s device cloud solution...
Страница 17: ...tings The IP settings for the router are also used by both BACnet IP connections The IP settings can be changed in the Network Settings section as shown 7 1 3 Multiple Connections Network Number set u...
Страница 18: ...For example type into a Google browser my IP Address to see the local PC s Public IP Address 7 1 6 BACnet MS TP and BACnet Ethernet Max Info Frames the number of transactions the Router may initiate w...
Страница 19: ...up Guide Page 19 of 27 7 2 Diagnostics By clicking on the Diagnostics tab all the connection communication details can be viewed to ensure the BACnet Router is working correctly Figure 13 BACnet Rout...
Страница 20: ...with a lower instance number will ignore the Who Is request High Device Instance sets a high limit for the Device Instance Devices with a higher instance number will ignore the Who Is request Network...
Страница 21: ...etwork Number Enter a value between 1 and 65534 that is unique across the entire BACnet network IP Port The IP Port number to be used for this BACnet IP connection Common values 47808 47809 Device Ins...
Страница 22: ...ll necessary documentation is shipped with the FieldServer on the USB flash drive these documents are constantly being updated Newer versions may be available on the Sierra Monitor website Ensure that...
Страница 23: ...of 27 o Ensure Full Diagnostic is selected this is the default NOTE If desired the default capture period can be changed o Click on Start Diagnostic o When the capture period is finished the Diagnost...
Страница 24: ...of 27 Step 2 Send Log o Once the diagnostic test is complete a zip file will be saved on the PC o Click Open to launch explorer and have it point directly at the correct folder o Email the diagnostic...
Страница 25: ...the Diagnostic Capture is complete email it to technical support The Diagnostic Capture will accelerate diagnosis of the problem Open the FieldServer FS GUI page Click on Diagnostics in the Navigation...
Страница 26: ...ons This device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE This equipment has been tested and f...
Страница 27: ...n or on which original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from batter...