Countermeasures 

(1) 

Connect wires correctly. 

(2) 

Replace the part. 

(3) 

Replace the part or connect wires correctly. 

(4) 

Replace the valve (the pilot valve) with a new one. 

(5) 

Adjust the pressure so that pilot pressure is within the specified range during operation. 

(6) 

  If incorrect oil has been used for lubrication, remove the oil with air blow, and replace the valve with a new one. 

If a lubricant is used in the system after the replacement of the valve, use turbine oil Class 1 (with no 

additive) ISO VG32. 

  If there is a large amount of condensate or condensate cannot be removed completely, mount an auto 

drain or install a dryer and replace the valve. 

(7) 

Check the voltage, and replace the pilot valve. 

(8) 

Protect the valve especially the coil to prevent it from being exposed to water. 

(9) 

If air leakage is caused by foreign matter, remove foreign matter in the piping by air blow and replace the 

valve. 

(10) 

Repair or replace the actuators. 

(11) 

Stop the air and additionally tighten the bolt.Check whether there is vibration or impact which has caused the 

loosening of the bolt. Install damping rubber so that the product is not affected by the vibration and impact. 

(12) 

Reduce the amount of lubrication to the amount at which the oil does not splash from the exhaust port (P

 

   

port). 

(13) 

Adjust the voltage so that the voltage at the time of operation stays within the specification range. 

(14) 

Ensure proper supply pressure and pilot pressure. 

(15) 

Stop the air consumption. Check where the air is leaking from, and stop the air leakage. 

(16) 

Install a tank on the supply side to stabilize the supply pressure. 

(17) 

Install a tank on the pilot pressure supply side to stabilize the pilot pressure. 

 
 

If the countermeasures above are not effective, there may be a problem with the valve. In that case, stop using the valve 

immediately. 

 

If any of the examples below are applicable, there may be an internal problem in the valve. In that case, stop using the 

valve immediately. 

 

  The voltage used was not the rated voltage. 

  The oil supplied was not the specified type.     

  Lubrication was stopped during operation. Or, lubrication was interrupted temporarily. 

  The product was directly exposed to water.   

  Strong impact was applied. 

  Foreign matter such as condensate or dust has entered the product. 

  Other than the cases mentioned above, any usage which falls under the precautions in this Operation Manual. 

  

If the product malfunctions, please return the valve as it is. 

 

 

 

- 11 - 

No.VEX

∗∗∗∗

-OMA0019-C

 

Содержание VEX5 Series

Страница 1: ...Doc no VEX OMA0019 C PRODUCT NAME Economy Valve MODEL Series Product Number VEX5 Series ...

Страница 2: ...fety Instructions 2 3 Design Selection 4 Mounting 5 Piping 5 Wiring 5 Lubrication 5 Air Supply 5 6 Operating environment 6 Maintenance 6 Specific Product Precautions 7 to 9 Troubleshooting 10 11 1 No VEX OMA0019 C ...

Страница 3: ...when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or attempt to remove product and mach...

Страница 4: ...oduct 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from this 1 year warranty A vacuum pad is a consumable part so it is warranted for a year after it is delivered Also even within the warranty period the wear of a product due to the use of the vacuum pad or failure d...

Страница 5: ... energizing time per day is expected to be longer than the total de energizing time per day use a valve which has DC type power saving type or long loading time type Depending on the operating conditions it may be possible to use valves which are not mentioned above Please contact us When the valve is mounted onto a control panel take measures against radiation in order to keep the valve temperatu...

Страница 6: ...ype light surge voltage suppressor check the polarity when connecting If a mistake is made regarding the polarity damage may occur to the diode in the valve the switching element in the control device power supply equipment etc 2 Applied voltage When electric power is connected to a solenoid valve be careful to apply the proper voltage Improper voltage may cause malfunction or coil damage 3 Check ...

Страница 7: ...f it is used in an environment where there is possible contact with oil weld spatter etc exercise preventive measures 7 When the valve is mounted in a control panel or it s energized for a long period of time make sure the ambient temperature is within the specifications of the valve Maintenance 1 Maintenance should be performed according to the procedure indicated in the Operation Manual this cop...

Страница 8: ... 3 and then set the terminal block 3 to the housing 2 Push it down until you hear the click sound 2 Putting rubber seal 6 plain washer 5 in this order into the cable introducing slit on the housing 2 then further tighten the cable gland 4 securely 3 Insert the gasket 8 between the bottom part of terminal block 3 and a plug attached to equipment and then screw 1 in from the top of the housing 2 to ...

Страница 9: ...after called REG and pilot valve hereinafter called SOL remote control the economy valve Action ON OFF SOL Cylinder Xa Xb Xc Yb Ya Mode Upward High speed a Low speed b Downward High speed c Low speed d Stop e a The air in the upper cylinder chamber is exhausted from the port 1 P of VEX A YE A and the air in the tank flows in through the port 1 P of VEX A XE A b Air flows into the lower cylinder ch...

Страница 10: ...re which overcomes compressed pressure Pu ΔP in the lower chamber to the tank chamber at the lower end of the stroke P2 Pu ΔP 4 In order to release air from the device for maintenance close the inlet valve for the main system Sm to release the air in the tank with exhaust valve E then discharge air in the cylinder upper chamber from VEXA YE A Then discharge air from the pilot This prevents lurchin...

Страница 11: ...reakage of lead wire Incorrect contact at the contact and connection 15 5 Foreign matter is caught in the poppet 9 6 Coil burnout Voltage is too high Or incorrect coil 7 Directly exposed to water 8 Increase of the pilot pressure Foreign matter is caught in the armature Air leaks from the pilot exhaust The supply pressure fluctuates The pilot pressure fluctuates Air is consumed by the equipment on ...

Страница 12: ...fected by the vibration and impact 12 Reduce the amount of lubrication to the amount at which the oil does not splash from the exhaust port P port 13 Adjust the voltage so that the voltage at the time of operation stays within the specification range 14 Ensure proper supply pressure and pilot pressure 15 Stop the air consumption Check where the air is leaking from and stop the air leakage 16 Insta...

Страница 13: ...nuary 1987 4 14 1 Sotokanda Chiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2018 SMC Corporation All Rights Reserved No VEX OMA0019 C ...

Отзывы: