SMC Networks THERMO-CON HEC001 Series Скачать руководство пользователя страница 23

Troubleshooting

 

 

HEC

 

 

5-1

 

5

  Troubleshooting 

The table below shows the solutions for the problems. 

 

Problem 

Cause 

Solution 

Communication cannot be 
made. 

A wrong connecting cable is used. 

Connect the host and the thermo-
con with the following cables: 

A cross cable for RS-232C 

A straight cable for RS-485 

The settings of the host and 
thermo-con are not consistent with 
each others. 

Make the following settings of the 
host and the thermo-con 
consistent:   

Unit Number, Baud Rate, Parity Bit, 
Data Length, Stop Bit 

The program is incorrect. 

Ensure that the program is made 

properly according to this operation 
manual. (Control code, command 
code, checksum, etc.) 

The communication method is 
incorrect. 

Use the communication method 
suitable for the specification of the 
thermo-con (RS-485, RS-232C).   

It is influenced by the noise from 

outside. 

Use a shield wire for the cable, and 
ground the shield to the field 
ground. 

It is influenced by the reflected 
wave. 

Install a terminating resistance. 

Temperature cannot be set. 

Four digits are not input for the 
setting temperature. 

Input four digits for the setting 

temperature. As 0.1 deg.C is the 
minimum indication unit, input 0 
(=30H) in the hundredths place.   

Value out of the setting range is 

input. 

Set it within the temperature setting 
range (between 10.0 and 60.0 
deg.C). 

Communication cannot be 
continued. 

It exceeds the writable capacity of 
EEPROM (approx. 1 million times).   

Ask SMC for repair. 

The connecting cable comes off or 

broken. 

Check the connecting cable. 

The thermo-con does not give 
a correct answer. 

The host sends more than one 
communication data successively. 

When sending communication 
data, wait until an answer from the 
thermo-con is received to send the 
next data. 

 

Содержание THERMO-CON HEC001 Series

Страница 1: ...06 series Keep available whenever necessary A_HEC OM J017 Rev May 2010 2006 SMC CORPORATION All Rights Reserved This manual is copyrighted and all rights are reserved by SMC Corporation and may not in...

Страница 2: ......

Страница 3: ...eface Contents Chap 1 Chap 2 Chap 3 Chap 4 Chap 5 Chap 6 1 0 1 1 Record of Changes Version Contents Date 1 0 First edition June 2006 1 1 The series name is added to the cover The product photography o...

Страница 4: ...y instructions well Instructions in the categories Danger Warning and Caution are important for safety and must be duly followed Please contact the following for any question and unclear points regard...

Страница 5: ...f Communication format 4 1 4 1 Temperature setting without writing EEPROM 4 1 4 2 Reading setting temperature 4 1 4 3 Reading internal sensor 4 2 4 4 Reading external sensor 4 3 4 5 Reading alarm stat...

Страница 6: ......

Страница 7: ...he host computer and the farthest Thermo con 3 Turn on the power switch of Thermo con 4 Select communication types for all Thermo cons See the operation manual of the details 5 That s all for preparat...

Страница 8: ......

Страница 9: ...haracter code Parity Start bit Data length Stop bit Block check RS 485 or RS 232C Half duplex Asynchronous Changeable 600 1200 2400 4800 9600 19200 bps ASCII Select Nil even number odd number bit Sele...

Страница 10: ......

Страница 11: ...ad 32H Read internal sensor 33H Read external sensor 34H Read alarm status 35H Read temperature average data It is same as reading external sensor in this model 36H Set offset without writing EEPROM a...

Страница 12: ...annot return the messages properly when the communication data is received successively Selection of Unit Specification There are two cases in communication format which are specifying unit No and not...

Страница 13: ...with communication data out of set range isn t memorised If communication format is correct ACK returns When writing in EEPROM is specified changed data is memorized in EEPROM each time Since writing...

Страница 14: ......

Страница 15: ...m unit the number in the hundredths place 10 2 should always be 0 30H When the value at every 0 01deg C is input it is rounded off Host STX 31H Setting data ETX Check sum CR 101 100 10 1 10 2 Thermo c...

Страница 16: ...the value in the hundredths place can be read Host ENQ 32H Check sum CR Thermo con STX 32H Internal sensor ETX Check sum CR 101 100 10 1 10 2 Host ACK CR Possible to omit Note 2DH is entered in 101 di...

Страница 17: ...ost ACK CR Possible to omit Note 2DH is entered in 101 digit is attached to temperature data Specifying unit Host SOH UT ENQ 33H Check sum CR Thermo con SOH UT STX 33H External sensor ETX Check sum CR...

Страница 18: ...larm ERR15 D2 23 22 21 20 Upper temperature limit alarm WRN Lower temperature limit alarm WRN Thermostat alarm ERR14 DC power supply failure alarm ERR11 D3 23 22 21 20 External sensor failure alarm ER...

Страница 19: ...of every 0 01 deg C Host STX 36H Offset ETX Check sum CR Symbol 100 10 1 10 2 Thermo con ACK CR Note As for symbols minus is indicated by 2DH and plus is indicated by 0 30H Specifying unit Host SOH UT...

Страница 20: ...EPROM The host computer sets temperature of each Thermo con In this command temperature setting data is written in EEPROM The setting range is from 10 0 to 60 0 deg C As 0 1 deg C is the minimum unit...

Страница 21: ...an be set at every minimum unit of 0 01 deg C Host STX 38H Offset ETX Check sum CR Symbol 100 10 1 10 2 Thermo con ACK CR Note As for symbols minus is indicated by 2DH and plus is indicated by 0 30H S...

Страница 22: ......

Страница 23: ...the thermo con RS 485 RS 232C It is influenced by the noise from outside Use a shield wire for the cable and ground the shield to the field ground It is influenced by the reflected wave Install a term...

Страница 24: ......

Страница 25: ...0D 06 0D Set at 25 0 deg C 38 Offset setting with writing EEPROM No 02 38 30 31 35 30 03 3F3E 0D 06 0D Set at 1 50 deg C Examples of commands and answers from the thermo con unit specified Command co...

Отзывы: