Figure 56: For analysers NOT fitted with CF4 option this is what is displayed.
Pressing “System Purge Now” will perform a complete vacuum purge of the analyser
including all pipework, sample hose and gas storage bag. This is normally only required if
the analyser has just been calibrated and the user needs to purge the system of calibration
gas, or contaminated gas has been allowed to enter the machine. Once purged the analyser
is ready to take gas samples again.
Pressing “Pump back now” manually operates a pump back cycle. This option is also
available from the main display window. Once pressed the analyser will prompt you to
connect the sample line to the gas compartment and begin pumping back. Depending on
the pressure in the gas compartment and the volume of gas in the bag the pump back cycle
can take up to five minutes to complete.
“SF6 / CF4 mix in use” enables or disables the CF
4
measurement mode. This function
requires a system reboot and is described in detail in section 6.9 above.
“Display Balance Gas” changes the main display so that the missing balance is shown as
either nitrogen or air. This function requires a system reboot and is described in detail in
sections 6.7 & 6.8 above.
The option to set a line purge before every test should be set to “no” unless instructed
otherwise by SMC.
8.3
Gas Cylinder Testing
The “Gas Cylinder Testing” option is used when you want to use the analyser with a gas
bottle of SF
6
rather than a switch gear or circuit breaker. With this option set to “Yes” the