-35-
PS##-OMM0003-A
•
Auto-preset
When auto-preset is selected in function selection mode, the set pressure can be calculated and
memorized from measured value. The set value is automatically optimized by repeated pressure changes
to the Pressure switch.
1, Selection of auto-preset OUT1
Press the
button in measurement mode to display "AP1".
(If OUT1 does not need to be set, press the
and buttons
simultaneously for 1 second or longer after "AP1" is displayed to
move to "AP2".)
2, Preparation of device
Prepare the device for which the pressure of OUT1 is set.
3, Setting of auto-preset value of OUT1
Press the
button to display "A1L".
After measurement starts, operate the device and change the pressure.
When the pressure change is detected, "A1H" will appear automatically,
and so continue to operate the device repeatedly.
(If the
and buttons are pressed simultaneously for 1 second or longer
during “A1L” displaying, measurement is stopped and “AP2” will appear.)
4, Selection of auto-preset OUT2
Press the
button to set "P_1" and "H_1" ("n_1" and "H_1" for reverse mode) and display "AP2".
(If OUT2 does not need to be set, press the
and buttons simultaneously for 1 second or longer
after "AP2" is displayed to move to measurement mode.)
5, Preparation and setting of OUT2 device
Prepare the device for which the pressure of OUT2 is set, and perform the setting of OUT2 in the
same manner as that for OUT1.
After "A2L" is displayed and measurements starts, when the pressure change is detected, "A2H"
will appear automatically.
(If the
and buttons are pressed simultaneously for 1 second or longer during "A2L" displaying,
measurement is stopped and measurement mode returns.)
6, Completion of setting
Press the
button to set "P_2" and "H_2" ("n_2" and "H_2" for reverse mode) and complete
auto-preset mode. After that, measurement mode returns.
The set values for OUT1 are displayed in auto-preset mode as follows.
•
Normal output
•
Reverse output
P_1 = A - (A - B)/4
n_1 = B + (A - B)/4
A = Max. pressure
H_1 = (A - B)/2
H_1 = (A – B )/2
B = Min. pressure
The display of set values of OUT2 is changed at the number after "_", i.e. "P_2", "n_2" and "H_2".
Содержание ISE80(H)
Страница 1: ...No PS OMM0003 A PRODUCT NAME Digital Pressure Switch MODEL Series Product Number ZSE80 F ISE80 H...
Страница 17: ...16 PS OMM0003 A Mounting with panel mount adapter Rear piping Bottom piping...
Страница 55: ...54 PS OMM0003 A Dimensions Z ISE80 02 Z ISE80 02L...
Страница 56: ...55 PS OMM0003 A Z ISE80 N02 Z ISE80 N02L...
Страница 57: ...56 PS OMM0003 A Z ISE80 F02 Z ISE80 C01...
Страница 58: ...57 PS OMM0003 A Z ISE80 C01L Z ISE80 A2...
Страница 59: ...58 PS OMM0003 A Z ISE80 A2L Z ISE80 B2...
Страница 60: ...59 PS OMM0003 A Z ISE80 B2L...