3. Operation/ Shutdown
3
-
7
Supplement: How to set self tuning
Explanation
●
We recommended PID control or fuzzy
control for this device.
When setting of
PID value is necessary, please use auto
tuning.
●
Please use when high control is
unnecessary, and the condition of the
controlled object changes frequently.
●
Function to control PID parameters
automatically to fit the controlled object and
set temperature (SV value) conditions.
●
During self tuning operation, the decimal
point on the right flashes.
●
Conditions for performing self tuning
(1) Temperature startup when the power
supply is turned on
(2) Temperature startup when SV changed
(Only performed when deemed necessary)
(3) When control becomes unstable and is
judged to be continuous.
* Do not change the SV value while executing self tuning.
* Once the PID value has been decided, if the SV is not changed, the next time the power is switched on, self
tuning will not be performed.
Initial set values (default values)
Display
Parameter
display symbol
Parameter
Set value
IDH*4-***
IDH*6-***
SV
Set temperature
25
℃
CTrL
Control system
Fuzzy control
LoC
Key lock
“O”: No key lock
AT
Auto-tuning
“O”: Pause
P
Proportional band
-
I
Integral time
-
d
Derivative time
-
Sequence
Explanation
Display
∧
∧
∧
∧
or
∨
∨
∨
∨
SEL
(for 3 sec)
∧
∧
∧
∧
or
∨
∨
∨
∨
SEL
∧
∧
∧
∧
or
∨
∨
∨
∨
SEL
(for 2 sec)
Shutdown
Restart
operation
Set SV value. (e.g. 25°C)
Display
second
block
parameter
Display parameter CTrL.
Select parameter CTrL
Select SELF
* SV flashes during setting
Fix settings & return to
normal screen.
Turn off the power supply
to this unit and wait 3 min.
When
this
device
is
operated again, self tuning
begins.
SV
SV
SV
SV
SEL
SEL
SEL
SEL
∨
∨
∨
∨
∧
∧
∧
∧
Flashes
during self
tuning
PV
SV
PV
SV
PV
SV
PV