5.1
Daily inspection
5-1
Chapter 5 Checks, Maintenance and
Adjustment
5.1 Daily inspection
Before daily operation, check the following points. When any abnormality is found, stop operation
immediately and refer to the Chapter 6 Troubleshooting.
There should be no leakage of compressed air.
The green LED is ON during operation.
Confirm that condensate comes out of the drain tube.
The evaporation thermometer is in the green area when the product is operated with compressed air.
The indicated value of the evaporation thermometer is about 5 to 10
°C lower than ambient temperature in
a state where the product is stopped and compressed air is not applied.
There should be no abnormality with noise or vibration from the product.
There should be no smell or smoke from the product.
- Only people who have sufficient knowledge and experience about the product and its
accessories are allowed to perform maintenance.
- Before maintenance, read and understand the important cautionary notifications in this
operation manual.
WARNING
DANGER
- Cut off the power supply for upstream when removing the panel.
- Before replacing or cleaning parts, be sure to bleed compressed air remain inside of the
product until the gauge indicates “0”.
Do not remove the auto drain case assembly with any air pressure remaining internally. If
there is residual pressure in the product, there would be great danger of an unexpected
accident, such as shooting out of parts when they are being unscrewed.
- Power supply parts become hot and will be applied with high voltage during operation. Heat
may cause burns, or electric shock can result due to high voltage. Even if the switch with
lamp is turned off and operation is stopped, electricity will be applied to the primary line.
During the work for charging line, turn OFF the electrical leakage breaker of the user's
equipment.
- Even if the device operation stops, there is a danger of burns due to residual heat. Do NOT
start working on the parts inside the product until the temperature has decreased to 50oC
or less. It may take 10 to 15 minutes.
- There is the possibility of contacting the condensate during the auto drain maintenance
work. Follow enduser procedures ensure safety of operator.
(example. Put on protective glass, apron, and gloves).
- Use an aqueous solution of neutral detergent for cleaning of the auto drain and do not use
solvents.
- When removing the panels and and auto drain case assembly, wear protective gloves to
prevent injuries from sharp edges.
Содержание IDF190D Series
Страница 12: ...IDX OM X011 Chapter 2 Name and Function of Parts 2 1 Name and Function of Parts IDF190D 240D Series 2 2...
Страница 20: ...IDX OM X011 Chapter 3 Transportation and installation 3 3 Cautions about Reinstallation IDF190D 240D Series 3 8...
Страница 36: ...IDX OM X011 Chapter 7 Documents 7 5 Air and refrigerant circuits and functions IDF190D 240D Series 7 6...
Страница 38: ...IDX OM X011 Chapter 8 Option C 8 2 Precautions for installation and handling IDF190D 240D Series 8 2...
Страница 42: ...IDX OM X011 Chapter 9 Option M 9 4 Electrical circuit diagram IDF190D 240D Series 9 4...