background image

HRX-OM-K021 

 

 

 
HRW Series 

5

 

4. 

Press the [ENT] key. 

The name of the current mode flashes. 

 

 

 

Figure 2-8   Mode Selection screen 

 

5. 

Use the arrow keys ([

][

]) to switch 

to “DNET REMOTE”. 

 

 

 

Figure 2-9   Mode Selection screen (“DNET REMOTE”) 

[Tips] 

To cancel a selection, press the [SEL] key, not [ENT] key. With the press of 
the [SEL] key, the cancellation takes effect and screen is switched to the 
“Menu screen 1”. 

 
 

6. 

Press the [ENT] key. 

The selection takes effect. 

 

 

 

Figure 2-10   Mode Selection screen (“DNET REMOTE”) 

 

7. 

Press the [SEL] key to display the “Menu screen 1”

 

 

 

 

I  8   0 18

 <REMOTE/LOCAL> 

MODE:DENT REMOTE

CUSTOM DIO   OFF

<REMOTE/LOCAL>

MODE: LOCAL

CUSTOM DIO   OFF

I  8   0 18

 <REMOTE/LOCAL> 

MODE:DENT REMOTE

CUSTOM DIO   OFF

Содержание HRW D Series

Страница 1: ...viceNet communication This manual should be used in addition to another operation manual HRX OM K003 HRW002 H HRW008 H HRW015 H HRW030 H HRW002 H1 HRW008 H1 HRW015 H1 HRW030 H1 HRW002 H2 HRW008 H2 HRW015 H2 HRW030 H2 HRW002 HS HRW008 HS HRW015 HS HRW030 HS HRW002 H1S HRW008 H1S HRW015 H1S HRW030 H1S HRW002 H2S HRW008 H2S HRW015 H2S HRW030 H2S Save This Manual Carefully for Use at Any Time 2007 SMC...

Страница 2: ...of another operation manual HRX OM K003 Chapter 5 System Operation Addition of operating procedure to use DeviceNetTM communication z The contents of this manual and related documents supplied with this system shall be neither regarded as a provision of the contract nor utilized to correct or modify the existing agreements commitments and relations z For the details of DeviceNetTM communication pl...

Страница 3: ...OM K021 HRW Series Table of Contents 1 Summary of HRW D 1 1 1 DEVICENET COMMUNICATION 1 2 Operation Screen 2 2 1 OPERATION SCREEN 3 2 1 1 Menu screen 1 3 2 1 2 Mode Selection screen 3 2 2 SYSTEM OPERATION 4 ...

Страница 4: ......

Страница 5: ...iceNet communication And the value of TEMP PV FLOW PV PRESS PV DI PV 1 and running alarm conditions are also outputted The function of DeviceNet can be used when DNET REMOTE mode is selected on communication mode setting 1 Applicable when circulating fluid automatic recovery function option is selected 2 Value of DI PV is displayed when only DI control kit option is selected For details of DeviceN...

Страница 6: ...tion of operating procedure to use the DeviceNet communication Selection of communication mode is conducted on Mode Selection screen shown in figure 2 1 Operating procedure for the others please refer to the operation manual HRX OM K002 Figure 2 1 Flow Chart of Operation Screen ...

Страница 7: ... only from the operation display panel DIO REMOTE 1 System start stop is allowed only through contact signal TEMP SP value setting is available only from the operation display panel SER REMOTE 1 System start stop and TEMP SP value setting are available only through serial RS 485 communication 1 MODE DNET REMOTE System start stop and TEMP SP value setting are available only through DeviceNet commun...

Страница 8: ...y the Menu screen 1 Figure 2 5 Menu screen 1 2 With the use of the arrow keys move the cursor to 2 REMOTE LOCAL in Menu screen 1 Figure 2 6 Menu screen 1 3 Press the ENT key The Mode Selection screen is displayed Figure 2 7 Mode Selection screen MENU 1 SETTING 2 REMOTE LOCAL 3 INITIAL SET REMOTE LOCAL MODE LOCAL CUSTOM DIO OFF MENU 1 SETTING 2 REMOTE LOCAL 3 INITIAL SET ...

Страница 9: ...ction press the SEL key not ENT key With the press of the SEL key the cancellation takes effect and screen is switched to the Menu screen 1 6 Press the ENT key The selection takes effect Figure 2 10 Mode Selection screen DNET REMOTE 7 Press the SEL key to display the Menu screen 1 I 8 0 18 REMOTE LOCAL MODE DENT REMOTE CUSTOM DIO OFF REMOTE LOCAL MODE LOCAL CUSTOM DIO OFF I 8 0 18 REMOTE LOCAL MOD...

Отзывы: