Piping

Caution

1. Regarding the circulating fluid piping, consider 

carefully the suitability for temperature and 

circulating fluid.

If the operating performance is not sufficient, the pipings may burst 

during operation. Also, the use of corrosive materials such as alu-

minum or iron for fluid contact parts, such as piping, may not only 

lead to clogging or leakage in the circulating fluid circuit but also 

refrigerant leakage and other unexpected problems. Provide 

protection against corrosion when you use the product.

2. Select the piping port size which can exceed the rated flow.

For the rated flow, refer to the pump capacity table.

3. When tightening at the drain port of this product, 

use a pipe wrench to clamp the connection ports.

4.  Supply water pressure to the automatic fluid fill port 

of this product should be 0.2 to 0.5 MPa.

This product has a built-in ball (float) tap. If you attach it to the 

faucet of a sink, etc. it will automatically supply water to the 

rated fluid level of the tank (halfway between HIGH and LOW.)

If the water supply pressure is too high, the pipes may burst 

during use. Proceed with caution.

5.  Ensure that piping is connected to the overflow port 

so that the circulating fluid can be exhausted to the 

drainage pit when the fluid level in the tank increases.

6. For the circulating fluid piping connection, install a 

drain pan and wastewater collection pit just in case 

the circulating fluid may leak.

7. This product series are constant-temperature fluid 

circulating machines with built-in tanks.

Do not install equipment on your system side such as pumps 

that forcibly return the circulating fluid to the unit. Also, if you 

attach an external tank that is open to the air, it may become 

impossible to circulate the circulating fluid. Proceed with caution.

Be sure to read this before handling the products. For safety instructions and tempera-
ture control equipment precautions, refer to the “Handling Precautions for SMC Prod-
ucts” and the “Operation Manual” on the SMC website: https://www.smcworld.com

HRS200 

Series

Specific Product Precautions 3

Mounting/Installation

Warning

Do not place heavy objects on top of this product, or step on it.

The external panel can be deformed and danger can result.

Caution

1. Install on a rigid floor which can withstand this 

product’s weight.

2. Secure with bolts, anchor bolts, etc.
3. Refer to the Operation Manual for this product, and 

secure an installation space that is necessary for 

the maintenance and ventilation.

1.  The air-cooled type product exhausts heat using the fan that is 

mounted to the product. If the product is operated with insuffi-

cient ventilation, ambient temperature may exceed 45

°

C, and 

this will affect the performance and life of the product. To pre-

vent this ensure that suitable ventilation is available (see below).

2.  For installation indoors, ventilation ports and a ventilation fan 

should be equipped as needed.

2000 mm or more

800 mm or more

800 mm or more

800 mm or more

400 mm

or more

Ventilation

Required installation space 

for ventilation and 

maintenance

3.  If it is impossible to exhaust heat from the installation area in-

doors, or when the installation area is conditioned, provide a 

duct for heat exhaustion to the air outlet port of this product for 

ventilation. Do not mount the inlet of the duct (flange) directly to 

the air vent of the product, and keep a space larger than the di-

ameter of the duct. Additionally, consider the resistance of the 

duct when making the air vent port for the duct.

<Heat radiation amount/Required ventilation rate>

Heat 

radiation 

amount

[kW]

Required ventilation rate [m

3

/min]

Differential temp. of 3

°

between inside and outside 

of installation area

Differential temp. of 6

°

between inside and outside 

of installation area

Approx. 37

615

310

4. When using the product at a low ambient tempera-

ture (10

°

C or less), refer to “Operation at low ambi-

ent temperature or low circulating fluid tempera-

ture” (page 14).

15

Содержание HRS200 Series

Страница 1: ...ort 1 This is a manual fluid fill port that is different from the automatic fluid fill port Fluid can be supplied manually into the tank without removing the side panel Fluid can be supplied manually...

Страница 2: ...ay panel Eye bolt M12 4 places 715 556 851 1114 428 421 278 110 108 Overflow port Rc1 Automatic fluid fill port Rc1 2 Fluid level indicator Signal cable entry Hole 40 Grommet with membrane Power cable...

Страница 3: ...Thermo chiller automatic fluid fill port 3 User s equipment To wastewater collection pit Fluid supply Circulating fluid return port Overflow port Tank drain port 4 5 2 2 2 2 1 1 6 Ensure that the ove...

Страница 4: ...p when this function is operated o lamp Equipped with a power failure auto restart function which restarts the product automatically after stopped due to a power failure Lights up when this function i...

Страница 5: ...optional accessories depending on the accessory the allowable current of 24 VDC devices will be reduced Refer to the operation manual of the optional accessories for details Item Specifications Conne...

Страница 6: ...830 401 118 1538 HRS200 A 46 SW The circulating fluid temperature and pressure are displayed in SI units MPa C only If this option is not selected a product with a unit selection function will be prov...

Страница 7: ...ed by user it is necessary to lift the thermo chiller by a forklift or sling work Carefully read the procedure manual included with this kit before performing the installation Part no Applicable model...

Страница 8: ...ectric conductivity target 5 0 to 45 0 S cm Set range of electric conductivity hysteresis 2 0 to 10 0 S cm Operating temperature range Circulating fluid temperature 5 to 60 C Power consumption 400 mA...

Страница 9: ...now Protection Hood Stainless steel snow protection hood for air cooled chiller According to the mounting direction of the snow protection hood the ventilation from the fan can be selected from four d...

Страница 10: ...ment Element Parts List No Description Material Qty Note q Body PC PP 1 w Element 1 PP 1 e Extension piece Stainless steel 2 Conversion from NPT to Rc r Handle 1 When H is selected t Sealant tape PTFE...

Страница 11: ...rm code 2 Operable items Operation start stop Circulating fluid temperature setting Alarm sound stop Key lock Key operation sound ON OFF Digital display brightness adjustment Alarm sound ON OFF HRS CV...

Страница 12: ...0 C Circulating fluid return temperature T2 297 K 24 C Circulating fluid temperature difference iT 4 K T2 T1 Conversion factor minutes to seconds SI units 60 s min 1 Refer to the next page for the typ...

Страница 13: ...1 kg L or using current unit system weight volume ratio 1 kgf L Specific heat C 4 19 x 103 J kg K or using current unit system 1 x 103 cal kgf C 2 Values for density and specific heat change slightly...

Страница 14: ...ulating fluid spec ified in Operation at low am bient temperature or low cir culating fluid temperature 5 In locations where condensation may occur 6 In locations which receive direct sunlight or radi...

Страница 15: ...glycol aqueous solution 15 wt 5 to 10 Ethylene glycol aqueous solution 15 wt Be sure to read this before handling the products For safety instructions and tempera ture control equipment precautions re...

Страница 16: ...nd tempera ture control equipment precautions refer to the Handling Precautions for SMC Prod ucts and the Operation Manual on the SMC website https www smcworld com HRS200 Series Specific Product Prec...

Страница 17: ...mS cm 100 1 to 300 1 v v Chloride ion Cl mg L 50 or less v Sulfuric acid ion SO4 2 mg L 50 or less v Acid consumption amount at pH4 8 mg L 50 or less v Total hardness mg L 70 or less v Calcium hardnes...

Страница 18: ...rformed or will stop Power supply voltage is not within the rated voltage range of 10 In case the water level inside the tank is reduced abnormally Circulating fluid temperature is too high Compared t...

Страница 19: ...Safety Instructions Be sure to read the Handling Precautions for SMC Products M E03 3 and Operation Manual before use...