Caution on Installation
HEC002-A/HEC006-A
3-2
3.2 Installation
If the air inlet of Thermo-con and the outlet opening is not enough, the cooling capacity decreases
due to the rise of the ambient temperature, decrease of the radiating air flow. Install Thermo-con
following condition. Moreover, when the exhaust duct is necessary, prepare it by customer.
3.3 Mounting
The product should be mounted as follows.
1) Use the foot attached to the product for mounting.
2) Then tighten M4 screws (bolts) or equivalent into 4 holes sized to 5mm on the parts marked with
arrow for mounting.
Fig. 3-1 Installation environment
Air IN
Air OUT
Air IN
Air OUT
Fig. 3-2 Installation environment (when the back side
has been blocked)
HEC002:100mm or more
HEC006:500mm or more
HEC002:200mm or more
HEC006:500mm or more