Gardner Denver Driver Manual
Page 13 of 13
Appendix C. Reference
Appendix C.1. Data Storage Format
Offset
Description
Units
DA_Service_Data
0
Advisories
see ES/RS2000 Controller spec
1-20
10x (Shutdown code / Hourmeter reading) pairs see ES/RS2000 Controller spec
21
Current total runtime hourmeter reading
Hours
22
Current loaded runtime hourmeter reading
Hours
23-28
6x Current temp hourmeters [H1]
– [H6]
Hours
29-34
6x Stored temp hourmeters [OH1]
– [OH6]
Hours
35
Last maintenance A
Hours
36
Last maintenance B
Hours
37
Oilage
Unknown, see ES/RS2000 controller spec
Operating Mode Data
0
Operating mode indication
see ES/RS2000 Controller spec
1
Sequence number
1
see ES/RS2000 Controller spec
2
Unit operating state
2
see ES/RS2000 Controller spec
Operating Data
0
System pressure
divide by 16 for pressure in psig
1
Filter pressure
divide by 16 for pressure in psig
2
Discharge temperature
divide by 16 for temperature in degrees F
3
Reservoir temperature
divide by 16 for temperature in degrees F
4
Motor current
3
amps
1
ES V2.0X Controllers do not respond with this field.
2
ES V2.0X Controllers do not respond with this field.
3
RS2000 V4.0X Controllers set this field to zero.