EX600-TFM07GB
6. Wiring (continued)
Turn-lock mechanism
of the connector
Turn the connector clockwise. It stops when turned 1/4 turn.Turn it
further. When the connector is turned 1/2 turn from the original posi-
tion, the projected portion is set at the diagonal position to the mark
and the turn is completed. Check that the connector is securely
locked.
If the connector is turned excessively, it will become difficult to
remove.
<Basic Operation>
Turning ON the power
(1) When the SI Unit and the Handheld
Terminal are connected with the cable,
the power is supplied to the Handheld
Terminal.
(2) The POWER LED (green) turns ON
and the start up screen is displayed on
the LCD display.
(3) After about 2 seconds, the Main Menu
screen is displayed.
Turning off the Power
During Main Menu screen, remove the
cable connected to the SI Unit.
SI Interface
Ver.X.X.
After
2 seconds
Main Menu
1.I/O monitor
2.Diagnosis Data
3.Sys. Configuration
4.Parameter Setting
5.Terminal Setting
Notes
- Be sure to put seal caps on any unused connectors of the EX600 SI
Unit. Appropriate use of seal caps enables the unit to achieve IP67
protection.
- The cable can be removed only when the Handheld Terminal dis-
plays the Main Menu screen. Do not remove the cable while at any
other screen, or this may cause equipment malfunction.
<Power Saving>
When the power supply is ON, and the
button is pressed for
2 seconds or more the Handheld Terminal will enter power
saving mode.
The LCD display will turn OFF. Pressing the
button again will
recover from the power saving mode.
7. Setting
7. Setting (continued)
<Main Menu>
The Handheld Terminal has five
modes for the various functions.
Each mode is composed of layers
with more detailed contents
enabling setting and checking of
each item.
Mode Selection Screen
Main Menu
1.I/O monitor
2.Diagnosis Data
3.Sys. Configuration
4.Parameter Setting
5.Terminal Setting
No.
1
2
3
4
5
Mode
I/O Monitor mode
Diagnosis Data
mode
System
Configuration
mode
Parameter Setting
mode
Terminal Setting
mode
Description
This mode displays the I/O status of the unit and
carries out forced I/O.
This mode displays the I/O status of the unit, the
detailed error contents and error log.
This mode is used to configure the following
system operations:
(1) Input the tag name of each unit.
(2) Update the memorized information of manifold
configuration.
(3) Change the hold/clear function to SW setting of
the SI unit or setting by the Handheld Terminal.
(4) Clear the ON/OFF counter of each I/O Unit.
(5) Reset the parameter of each unit to the factory
default value.
(6) Clear all error logs.
This mode is used to set each parameter type.
This mode is used to set the following:
(1) Set the contrast of the LCD display screen.
--> 9 levels
(2) Set the brightness of the LCD display screen.
--> 5 levels
(3) Set the click sound level for button operation.
--> 5 levels
(4) Set the time before entering power saving
mode when there is no operation.
--> None, 1 min, 3 min, 7 min, 10 min
(5) Cancel the operation settings of the Handheld
Terminal and return to the initial setting values.
(6) Change the password.
8.Trouble Shooting
Indication
Power LED
is OFF
LCD display
is not active
"Warning
System
access is not
completed" is
displayed on
the LCD
screen
is
displayed on
the LCD
screen.
?
ERROR LED
is ON
Problem
EX600 Power
supply voltage
level for control /
input is not within
specification.
The cable for the
handheld terminal
is defective.
Handheld terminal
is in power save
mode.
LCD is damaged.
The handheld
terminal cable is
defective.
A connection
between the units
is defective.
Manifold
configuration
memory error has
occurred.
Connection
between the units
is defective.
EX600 diagnostic
error has
occurred.
Investigation method
- Check if "PWR" LED
on the SI Unit is
green.
- Confirm that the
regulated power
supply voltage is
supplied to the
endplate.
- Confirm the
Handheld terminal
cable is connected
correctly.
- Confirm the integrity
of the connection of
the Handheld
terminal cable.
Press ESC button.
Confirm that the LCD
is active.
If LCD does not
become active after
initial checks above,
LCD is damaged.
- Confirm that the
Handheld terminal
cable is connected
correctly.
- Confirm there is no
loose connection in
the Handheld
terminal cable.
Confirm if SI Unit
"ST(M)" LED is green.
Confirm if configuration
memory is in active
state and manifold
configuration is
correct.
Confirm the SI Unit
"ST(M)" LED is green.
Confirm error content
through diagnostic
data mode.
Counter-measure
Supply voltage of
24V
10% to the
power supply for
control / input.
Refer to the
manual of the
corresponding
unit.
- Reconnect the
cable correctly.
- Ensure the cable
connections are
secure.
Same as left.
Stop operation
and contact SMC
sales office.
- Reconnect the
cable correctly.
- Ensure the cable
connections are
secure.
If LED is flashing
red and green,
there is a
connection fault
between the units.
Re-make and
then confirm the
connection
between the units.
Please refer to
respective unit's
operation manual
to clear the error.
If the LED is
flashing red and
green, there is a
connection fault
between the units.
Re-make and
then confirm the
connection
between the units.
Refer to error
code list and
respective unit's
operation manual
for counter
measure to the
error.
9. Contact
AUSTRIA
(43) 2262 62280
NETHERLANDS
(31) 20 531 8888
BELGIUM
(32) 3 355 1464
NORWAY
(47) 67 12 90 20
CZECH REP.
(420) 541 424 611
POLAND
(48) 22 211 9600
DENMARK
(45) 7025 2900
PORTUGAL
(351) 21 471 1880
FINLAND
(358) 207 513513
SLOVAKIA
(421) 2 444 56725
FRANCE
(33) 1 6476 1000
SLOVENIA
(386) 73 885 412
GERMANY
(49) 6103 4020
SPAIN
(34) 945 184 100
GREECE
(30) 210 271 7265
SWEDEN
(46) 8 603 1200
HUNGARY
(36) 23 511 390
SWITZERLAND
(41) 52 396 3131
IRELAND
(353) 1 403 9000
UNITED KINGDOM
(44) 1908 563888
ITALY
(39) 02 92711
URL http://www.smcworld.com (Global) http://www.smceu.com (Europe)
Specifications are subject to change without prior notice from the manufacturer.