Address setting procedure via the AS-i line
The following is the procedure for address setting of the master unit via the AS-i line with
EX250-SAS3/-SAS7 (8 inputs / 8 outputs, and address connector – 2 pcs.).
For setting the unit which occupies two slaves (EX250-SAS3/-SAS7), plug the cable jack into the address
which is not to be set (ADDR2 when ADDR1 is set) to disconnect the address from the AS-i line.
<Address setting of ADDR1>
∗
1
1. Plug the cable jack into the connector for setting ADDR2. (to disconnect ADDR2 from the line)
2. Connect the AS-i line to the SI unit communication connector to apply the AS-i power supply.
3. Set the ADDR1 address from the master unit.
4. Turn off the AS-i power supply.
∗
2
<Address setting of ADDR2>
∗
1
5. Pull out the cable jack which is plugged into the connector for setting ADDR2, and plug it into ADDR1. (to
disconnect ADDR1 from the line)
6. Apply the AS-i power supply.
7. Set the address of ADDR2 from the master unit.
8. Turn off the AS-i power supply.
∗
1
9. Pull out the cable jack from the connector for setting ADDR1.
Address setting completed. After setting, wire any other AS-i units.
∗
1: Procedure above is an example for setting the address in order of ADDR1 -> ADDR2. It is not a problem to set the address in order
of ADDR2->ADDR1.
∗
2: Turn off the AS-i power supply when connecting/disconnecting the cable jack.
∗
3: SMC does not provide the cable jack.