![SMC Networks Electro Industries ProtoCessor Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/smc-networks/electro-industries-protocessor/electro-industries-protocessor_startup-manual_1299868031.webp)
Electro Industries ProtoCessor Start-up Guide
Page 31 of 32
Appendix D
Reference
Appendix D.1 Specifications
ProtoCessor FPC-ED4
Electrical Connections
One 2-pin Phoenix connector with one FTT-10 LonWorks port
One Ethernet 10/100 BaseT port
Approvals
CE certified; UL 916 approved; WEEE compliant; EN 60950-1,
EN 50491-3 and CSA C22-2 standards; FCC Class A Part 15;
DNP 3.0 conformance tested; RoHS compliant; CSA 205 approved
LonMark Certified
Power Requirements
5VDC
Physical Dimensions
8.5 x 3.0 x 2.0 cm (3.3 x 1.2 x .08 in.)
Weight
0.03 kg (0.07 lbs)
Operating
Temperature
-40°C to 75°C (-40°F to167°F)
Surge Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity
5 - 90% RH (non-condensing)
(Specifications subject to change without notice)
Figure 19: Specifications
Appendix D.1.1 Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating ProtoCessor.
•
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating
temperature range.
•
The interconnecting power connector and power cable shall:
o
Comply with local electrical code
o
Be suited to the expected operating temperature range
o
Meet the current and voltage rating for ProtoCessor
•
Furthermore, the interconnecting power cable shall:
o
Be of length not exceeding 3.05m (118.3”)
o
Be constructed of materials rated VW-1, FT-1 or better
•
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should
be installed in a Restricted Access Area requiring a key or a special tool to gain access.
•
This device must not be connected to a LAN segment with outdoor wiring.