ClimateWorx ProtoNode Start-up Guide
Page 40 of 46
Regulating Valve Start Positon
%
AV 55
o o o o
Used in systems with PID control on
condenser water valve
M-AoCoolingFirst
AV 55 AO 55 nvi/nvoM_AOCl1st_XXX SNVT_count_f
40055
Head Pressure Setpoint
psig
AV 56
o o o o
HighPressureSetValue
AV 56 AO 56 nvi/nvoHiPrStVal_XXX
SNVT_count_f
40056
Head Pressure Control Deadband
psi
AV 57
o o o o
HighPressureDeadBand AV 57 AO 57 nvi/nvoHiPrDdBnd_XXX SNVT_count_f
40057
Water Reg Valve Minimum Position
%
AV 58
o o o o
E-AO01ValueMin
AV 58 AO 58 nvi/nvoE_AO1VlMn_XXX SNVT_count_f
40058
Temperature Control
0,1
AV 59 o o o o o 0: Average, 1: Maximum
Reserve58
AV 59 AO 59 nvi/nvoReserve58_XXX SNVT_count_f
40059
Return Temperature High Limit
10 x C
AV 61 x x x x x
Temp1HiLimit1
AV 61 AO 61 nvi/nvoTp1HiLim1_XXX SNVT_count_f
40061
Temperature Low Limit
10 x C
AV 62 x x x x x
Temp1LowLimit1
AV 62 AO 62 nvi/nvoTp1LoLim1_XXX SNVT_count_f
40062
Temperature High Limit
10 x F
AV 63 x x x x x
Temp1HiLimit2
AV 63 AO 63 nvi/nvoTp1HiLim2_XXX SNVT_count_f
40063
Temperature Low Limit
10 x F
AV 64 x x x x x
Temp1LowLimit2
AV 64 AO 64 nvi/nvoTp1LoLim2_XXX SNVT_count_f
40064
Compressor Restart Delay
Seconds
AV 65
x x x x
RestartDelay
AV 65 AO 65 nvi/nvoRestrtDel_XXX
SNVT_count_f
40065
Humidification High Limit
%RH
AV 66 o o o o o
HumidHiLimit1
AV 66 AO 66 nvi/nvoHumHiLim1_XXX SNVT_count_f
40066
Humidification Low Limit
%RH
AV 67 o o o o o
HumidLoLimit
AV 67 AO 67 nvi/nvoHumLoLim_XXX SNVT_count_f
40067
Temperature 2 High Limit
10 x C
AV 68 x x x x x
Temp2HiLimit1
AV 68 AO 68 nvi/nvoTp2HiLim1_XXX SNVT_count_f
40068
Temperature 2 Low Limit
10 x C
AV 69 x x x x x
Temp2LoLimit1
AV 69 AO 69 nvi/nvoTp2LoLim1_XXX SNVT_count_f
40069
Temperature 2 High Limit
10 x F
AV 70 x x x x x
Temp2HiLimit2
AV 70 AO 70 nvi/nvoTp2HiLim2_XXX SNVT_count_f
40070
Temperature 2 Low Limit
10 x F
AV 71 x x x x x
Temp2LoLimit2
AV 71 AO 71 nvi/nvoTp2LoLim2_XXX SNVT_count_f
40071
Humidity High Limit 2 (supply)
%RH
AV 73 o o o o o
Humid2HiLimit
AV 73 AO 73 nvi/nvoHum2HiLim_XXX SNVT_count_f
40073
Humidity Low Limit 2 (supply)
%RH
AV 74 o o o o o
Humid2LoLimit
AV 74 AO 74 nvi/nvoHum2LoLim_XXX SNVT_count_f
40074
Voltage High Limit
%
AV 75 x x x x x
VoltHiLimit
AV 75 AO 75 nvi/nvoVoltHiLim_XXX
SNVT_count_f
40075
Voltage Low Limit
%
AV 76 x x x x x
VoltLoLimit
AV 76 AO 76 nvi/nvoVoltLoLim_XXX
SNVT_count_f
40076
Heater Minimum On
AV 80 o o o o o
HeaterMinOn
AV 80 AO 80 nvi/nvoHtrMinOn_XXX
SNVT_count_f
40080
Cooling Minimum On
AV 81 x o o o o
CoolMinOn
AV 81 AO 81 nvi/nvoCoolMinOn_XXX SNVT_count_f
40081
EC Fan Speed
%
AV 82 o o o o o
Main-AO01
AV 82 AO 82 nvi/nvoMain_AO01_XXX SNVT_count_f
40082
Heating Output
%
AV 83 o o o o o
Main-AO02
AV 83 AO 83 nvi/nvoMain_AO02_XXX SNVT_count_f
40083
Cooling Demand (Valve Position)
%
AV 84 x
x x
Main-AO03
AV 84 AO 84 nvi/nvoMain_AO03_XXX SNVT_count_f
40084
Water Reg Valve 1 Position
%
AV 85
o o o
EX-AO01
AV 85 AO 85 nvi/nvoEx_AO01_XXX
SNVT_count_f
40085
Free Cooling Valve 1 Position
%
AV 86
x
EX-AO02
AV 86 AO 86 nvi/nvoEx_AO02_XXX
SNVT_count_f
40086
Water Reg Valve 2 Position
%
AV 87
d d d
EX-AO03
AV 87 AO 87 nvi/nvoEx_AO03_XXX
SNVT_count_f
40087
Free Cooling Valve 2 Position
%
AV 88
x
EX-AO04
AV 88 AO 88 nvi/nvoEx_AO04_XXX
SNVT_count_f
40088
Humidifier Output Signal
%
AV 89 o o o o o
Main-AO04
AV 89 AO 89 nvi/nvoMain_AO04_XXX SNVT_count_f
40089
Sensor Mode
0,1,2
AV 91 x x x x x 0:Local,1:Remote,2:Disable
SensorMode
AV 91 AO 91 nvi/nvoSensorMod_XXX SNVT_count_f
40091
Control Mode
0, 1
AV 109 x x x x x 0:Auto,1:Manual
ControlMode
AV 109 AO 109 nvi/nvoCtrlMode_XXX
SNVT_count_f
40109
Voltage Reference (Calibration)
AV 110 x x x x x
VoltageRefrence
AV 110 AO 110 nvi/nvoVoltRef_XXX
SNVT_count_f
40110
Return Temperature Offset
10 x C
AV 111 x x x x x Used to adjust sensor readings
ReturnTempratureOffset AV 111 AO 111 nvi/nvoRetTmpOff_XXX SNVT_count_f
40111
Return Humidity Offset
%RH
AV 112 x x x x x
ReturnHumidtyOffset
AV 112 AO 112 nvi/nvoRetHumOff_XXX SNVT_count_f
40112
Supply Temperature Offset
10 x C
AV 113 o o o o o
SupplyTempratureOffset AV 113 AO 113 nvi/nvoSupTmpOff_XXX SNVT_count_f
40113
Supply Humidity Offset
%RH
AV 114 o o o o o
SupplyHumidtyOffset
AV 114 AO 114 nvi/nvoSupHumOff_XXX SNVT_count_f
40114
Return Temperature Offset
10 x F
AV 115 x x x x x
ReturnTempratureOffset2 AV 115 AO 115 nvi/nvoRetTpOff2_XXX
SNVT_count_f
40115
Supply Temperature Offset
10 x F
AV 116 o o o o o
SupplyTempratureOffset2 AV 116 AO 116 nvi/nvoSupTpOff2_XXX SNVT_count_f
40116
Binary Output (Read Only)
Fan Fault
BI 1
x x x x x
Fan Fault
BI 1 DI 1 nvoFanFault_XXX
SNVT_switch
10001
Low Airflow Alarm
BI 2
x x x x x
Low Airflow
BI 2 DI 2 nvoLoAirFlow_XXX
SNVT_switch
10002
Humidifier Alarm
BI 3
o o o o o
Humidifier Fault
BI 3 DI 3 nvoHumFault_XXX
SNVT_switch
10003
Heater High Limit Alarm (Overheat)
BI 4
o o o o o
Heater Overheat
BI 4 DI 4 nvoHtrOvrht_XXX
SNVT_switch
10004
Dirty Filter Alarm
BI 5
x x x x x
Filter dirty
BI 5 DI 5 nvoFltrDirty_XXX
SNVT_switch
10005
Fire Alarm/ Emergency Power Off
BI 6
x x x x x
Fire Alarm/Emergency
Power Off
BI 6 DI 6 nvoFireAlarm_XXX
SNVT_switch
10006
Liquid Detection Alarm
BI 7
o o o o o
Liquid Detection
BI 7 DI 7 nvoLiqDet_XXX
SNVT_switch
10007
Condensate Overflow/ Condensate Pump
Alarm
BI 8
o o o o o
Condensate
overflow/pump alarm
BI 8 DI 8 nvoCndOvrFlo_XXX
SNVT_switch
10008
Power Phase Loss Alarm
BI 9
o o o o o
Power Phase Lose
BI 9 DI 9 nvoPwrPhsLos_XXX
SNVT_switch
10009
Compressor 1 High Pressure Alarm
BI 10
x x x x
Comp.1 H pressure
BI 10 DI 10 nvoComp1HPrs_XXX
SNVT_switch
10010
Compressor 1 Low Pressure Alarm
BI 11
x x x x
Comp.1 L pressure
BI 11 DI 11 nvoComp1LPrs_XXX
SNVT_switch
10011