SMC Networks ClimateWorx FieldServer ProtoNode FPC-N34 Скачать руководство пользователя страница 36

 

ClimateWorx ProtoNode Start-up Guide

 

Page 36 of 46

 

 Update Firmware 

Appendix A.6.

To load a new version of the firmware, follow these instructions: 

1.  Extract and save the new file onto the local PC. 

2.  Open a web browser and type the IP Address of the FieldServer in the address bar. 

o

 

Default IP Address is 192.168.1.24 

o

 

Use the FS Toolbox utility if the IP Address is unknown (

Appendix A.1

) 

3. 

Click on the “Diagnostics & Debugging” button. 

4.  In the Navigation Tree on the left hand side, do the following: 

a. 

Click on “Setup” 

b.  Click on 

“File Transfer” 

c. 

Click on the “Firmware” tab 

5. 

In the Firmware tab, click on “Choose Files” and select the firmware file extracted in step 1. 

6. 

Click on the orange “Submit” button. 

7. 

When the download is complete, click on the “System Restart” button. 

 

 BACnet: Setting Network_Number for more than one ProtoNode on Subnet 

Appendix A.7.

For both BACnet MS/TP and BACnet/IP, if more than one ProtoNode is connected to the same subnet, 
they must be assigned unique Network_Number values. 

On the main Web Configuration screen, 

update the Network Number with the “network_nr” field and click 

submit. The default value is 50.  

 

 

Figure 30: Web Configurator 

– Setting Network Number for BACnet 

Содержание ClimateWorx FieldServer ProtoNode FPC-N34

Страница 1: ...Guide For Interfacing ClimateWorx Products M52 Controller To Building Automation Systems BACnet MS TP BACnet IP BACnet Ethernet Modbus TCP IP Metasys N2 and LonWorks APPLICABILITY EFFECTIVITY Explain...

Страница 2: ...the ProtoNode product Sierra Monitor Corporation does not provide direct support If ClimateWorx needs to escalate the concern they will contact Sierra Monitor Corporation for assistance Support Conta...

Страница 3: ...t to the Field Protocol cabling Section 4 3 or connect ProtoNode FPC N35 s 2 pin LonWorks port to the Field Protocol cabling Section 4 4 8 Connect Power to ProtoNode 6 pin connector Section 4 5 9 Use...

Страница 4: ...ower Up ProtoNode 18 5 Use ProtoNode Web Configurator to Setup the Gateway 19 5 1 Connect the PC to ProtoNode via the Ethernet Port 19 5 2 Connecting to ProtoNode Web Configurator 20 5 3 Selecting Pro...

Страница 5: ...Termination Switch on the ProtoNode N34 left and 16 Figure 13 Connection from ProtoNode to RS 485 Field Network 17 Figure 14 RS 485 BMS Network EOL Switch 17 Figure 15 LonWorks Terminal 17 Figure 16...

Страница 6: ...net btl for more information about the BACnet Testing Laboratory Click here for BACnet PIC Statement LonMark International is the recognized authority for certification education and promotion of int...

Страница 7: ...lled device connected to the ProtoNode and automatically configures them for BACnet MS TP BACnet IP BACnet Ethernet Metasys 2 N2 by JCI Modbus TCP IP or LonWorks 3 It is not necessary to download any...

Страница 8: ...1088 ProtoNode FPC N35 FPC N35 1089 Figure 1 ProtoNode Part Numbers FPC N34 units have the following 3 ports RS 485 Ethernet RS 485 FPC N35 units have the following 3 ports LonWorks Ethernet RS 485 3...

Страница 9: ...TU Baud Rate 9600 Parity None Data Bits 8 Stop Bits 1 Figure 4 COM Settings 3 3 2 Set Modbus Node ID for each Device attached to the ProtoNode Set Modbus Node ID for each of the devices attached to Pr...

Страница 10: ...do not use the S bank DIP switches S0 S3 to select a Field Protocol o On ProtoNode FPC N35 units these switches are disabled the Field Protocol is always LonWorks ProtoNode FPC N34 S Bank DIP Switches...

Страница 11: ...NOTE Never set a BACnet MS TP MAC Address of the ProtoNode to a value from 128 to 255 Addresses from 128 to 255 are Slave Addresses and can not be discovered by BMS Front Ends that support Auto Discov...

Страница 12: ...Cnet MS TP The baud rate on ProtoNode for Metasys N2 is set for 9600 B bank DIP switches B0 B3 are disabled for Metasys N2 on ProtoNode FPC N34 B bank DIP switches B0 B3 are disabled on ProtoNode FPC...

Страница 13: ...mateWorx ProtoNode Start up Guide Page 13 of 46 4 INTERFACING PROTONODE TO DEVICES 4 1 ProtoNode FPC N34 and FPC N35 Showing Connection Ports Figure 9 ProtoNode FPC N34 upper and ProtoNode FPC N35 low...

Страница 14: ...ACnet and FPC N35 LonWorks Pins 1 through 3 are for RS 485 devices o Use standard grounding principles for RS 485 GND Pins 4 through 6 are for power Do not connect power until Section 4 4 Device Pins...

Страница 15: ...biasing jumpers are OFF The OFF position is when the 2 RED biasing jumpers straddle the 4 pins closest to the outside of the board of the ProtoNode Figure 11 Only turn biasing ON o IF the BMS cannot...

Страница 16: ...the pins closest to the inside of the board of the ProtoNode o On short cabling runs the EOL switch does not to need to be turned ON If the ProtoNode is placed at one of the ends of the trunk set the...

Страница 17: ...Termination Switch needs to be enabled Figure 14 o The default setting from the factory is OFF switch position right side o To enable the EOL Termination turn the EOL switch ON switch position left s...

Страница 18: ...TE These values are nominal and a safety margin should be added to the power supply of the host system A safety margin of 25 is recommended Figure 16 Required current draw for the ProtoNode Apply powe...

Страница 19: ...ProtoNode The Default IP Address of ProtoNode is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and ProtoNode are on different IP Networks assign a static IP Address to the PC on the 192 168 1 xx...

Страница 20: ...rator the Active Profiles section is shown on the lower left side of the screen The Active Profiles section lists the currently active device profiles including previous Web Configurator additions and...

Страница 21: ...the device s Modbus Node ID which was assigned in Section 3 3 2 Then press the Submit button to add the Profile to the list of devices to be configured Repeat this process until all the devices have b...

Страница 22: ...net as the ProtoNode Section 5 1 open a web browser on the PC and enter the IP Address of the ProtoNode the default address is 192 168 1 24 The Web Configurator is displayed as the landing page Figure...

Страница 23: ...he IP Gateway Default Gateway field Type in a new IP Gateway NOTE If the ProtoNode is connected to a router the IP Gateway of the ProtoNode should be set to the IP Address of that router Reset ProtoNo...

Страница 24: ...ange from 1 to 4 194 303 To assign a specific Device Instance or range change the Node_Offset value as needed using the calculation below Device Instance desired Node_Offset Modbus Node_ID For example...

Страница 25: ...e the default address is 192 168 1 24 If the IP Address of the ProtoNode has been changed by previous configuration the assigned IP Address must be gathered from the network administrator The Web Conf...

Страница 26: ...ks Network Management Tool If an XIF file is required see steps in Section 8 1 1 to generate XIF 8 1 1 Instructions to Download XIF File from ProtoNode FPC N35 Using Browser Connect a CAT5 Ethernet ca...

Страница 27: ...browser and go to the following address IP Address of ProtoNode fserver xif o Example 192 168 1 24 fserver xif If the web browser prompts to save the file save the file onto the PC If the web browser...

Страница 28: ...nload the BACnet Explorer Start up Guide For purchasing information look up the BACnet Explorer page on the Sierra Monitor website www sierramonitor com connect all protocol gateway products bacnet ex...

Страница 29: ...Downloads http www sierramonitor com customer care resource center filters software downloads Extract the executable file and complete the installation Disable firewall and virus protection software i...

Страница 30: ...ProtoNode into the web browser or use the FieldServer Toolbox to connect to the ProtoNode Click on Diagnostics and Debugging Button then click on view and then on connections If there are any errors...

Страница 31: ...op bits o Check device address o Verify wiring o Verify device is connected to the same subnet as the ProtoNode o Verify the Modbus device was discovered in Web Configurator Section 5 2 Field COM prob...

Страница 32: ...LED will go on solid 15 seconds after power up It will turn off after 5 seconds A steady red light will indicate there is a system error on the unit If this occurs immediately report the related syste...

Страница 33: ...d or download FieldServer Toolbox zip on the Sierra Monitor webpage under Customer Care Resource Center Software Downloads http www sierramonitor com customer care resource center filters software dow...

Страница 34: ...art up Guide Page 34 of 46 o Select Full Diagnostic NOTE If desired the default capture period can be changed o Click on Start Diagnostic o When the capture period is finished the Diagnostic Test Comp...

Страница 35: ...5 of 46 Step 2 Send Log o Once the diagnostic test is complete a zip file is saved on the PC o Choose Open to launch explorer and have it point directly at the correct folder o Send the Diagnostic zip...

Страница 36: ...wing a Click on Setup b Click on File Transfer c Click on the Firmware tab 5 In the Firmware tab click on Choose Files and select the firmware file extracted in step 1 6 Click on the orange Submit but...

Страница 37: ...ted access to the ProtoNode The User account can view any ProtoNode information but cannot make any changes or restart the ProtoNode The password needs to be a minimum of eight characters and is case...

Страница 38: ...VT_count_f 30012 Circuit 1 Filter Drier Entering Temp 10 x C F AI 11 do do do do Temp FilterDriveA2 AI 13 AI 13 nvoTpFlDrA2_XXX SNVT_count_f 30013 Circuit 1 Filter Drier Leaving Temp 10 x C F AI 12 do...

Страница 39: ...RelaxBand1 AV 27 AO 27 nvi nvoTpRlxBnd1_XXX SNVT_count_f 40027 Temperature Dead Band 10 x F AV 28 x x x x x TempDeadBand2 AV 28 AO 28 nvi nvoTmpDdBnd2_XXX SNVT_count_f 40028 Temperatue Relax Band 10 x...

Страница 40: ...AO02_XXX SNVT_count_f 40083 Cooling Demand Valve Position AV 84 x x x Main AO03 AV 84 AO 84 nvi nvoMain_AO03_XXX SNVT_count_f 40084 Water Reg Valve 1 Position AV 85 o o o EX AO01 AV 85 AO 85 nvi nvoEx...

Страница 41: ...SHum_XXX SNVT_switch 10023 Low Supply Air Humidity BI 24 o o o o o Low S Humidity BI 24 DI 24 nvoLoSHum_XXX SNVT_switch 10024 Lose of Supply Air Sensor BI 25 o o o o o Lose of S Sensor BI 25 DI 25 nvo...

Страница 42: ...f Off On Off On Off Off 42 Off On Off On Off On Off Off 43 On On Off On Off On Off Off 44 Off Off On On Off On Off Off 45 On Off On On Off On Off Off 46 Off On On On Off On Off Off Address A0 A1 A2 A3...

Страница 43: ...8 Off On Off On Off Off Off On 139 On On Off On Off Off Off On 140 Off Off On On Off Off Off On 141 On Off On On Off Off Off On Address A0 A1 A2 A3 A4 A5 A6 A7 142 Off On On On Off Off Off On 143 On O...

Страница 44: ...On On 219 On On Off On On Off On On 220 Off Off On On On Off On On 221 On Off On On On Off On On 222 Off On On On On Off On On 223 On On On On On Off On On 224 Off Off Off Off Off On On On 225 On Off...

Страница 45: ...40 C to 75 C 40 F to167 F Surge Suppression EN61000 4 2 ESD EN61000 4 3 EMC EN61000 4 4 EFT Humidity 5 90 RH non condensing Specifications subject to change without notice Figure 31 Specifications App...

Страница 46: ...ation or on which original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from ba...

Отзывы: