Page 3 of 4 

 

4 Settings - continued 

4.2 Change of Actuation 

50-VPE500-X60 and 50-VPE700-X60 

Body ported 

 

Figure 11 

  When changing the actuation from normally closed to normally open 

type, remove the end plate from the body and reset the 

 mark on the 

end plate to correspond with the ‘NO’ mark on the body as shown in 
Figure 11. 

  Refer to Table 4  for piping. 

 

                        Port 

Actuation

 

1(P) 

2(A) 

3(R)

 

N.C. 

Inlet side 

Outlet side 

Exhaust side 

N.O. 

Exhaust side 

Outlet side 

Inlet side 

Table 4 

5 How to Order 

Please contact SMC for details. 

 

6 Outline Dimensions 

Please contact SMC for details. 

 

7 Maintenance 

7.1 General Maintenance 

 Caution 

  Not following proper maintenance procedures could cause the product 

to malfunction and lead to equipment damage. 

  If handled improperly, compressed air can be dangerous. 

  Maintenance  of  pneumatic  systems  should  be  performed  only  by 

qualified personnel. 

  Before performing maintenance, turn off the power supply and be sure 

to  cut  off  the  supply  pressure.  Confirm  that  the  air  is  released  to 
atmosphere. 

  After  installation  and  maintenance,  apply  operating  pressure  and 

power  to  the  equipment  and  perform  appropriate  functional  and 
leakage tests to make sure the equipment is installed correctly. 

  If any electrical connections are disturbed during maintenance, ensure 

they  are  reconnected  correctly  and  safety  checks  are  carried  out  as 
required  to  ensure  continued  compliance  with  applicable  national 
regulations. 

  Do not make any modification to the product. 

  Do  not  disassemble  the  product,  unless  required  by  installation  or 

maintenance instructions. 

 

7.2 Mounting 

Danger 

  Never add or remove a valve from the manifold when energised. 

  Never  remove  terminal  box  cover  when  power  is  connected  to  the 

manifold. 

  Never  disconnect  or  reconnect  cables  or  connectors  when  power  is 

connected to the valves. 

Caution 

  Be sure to cut off power and the air supply and confirm that no air is 

left  in  actuators,  piping  and  manifolds  before  disassembling,  as 
remaining air may cause an accident. 

  Before  assembly  and  installations, confirm that  rubber  parts such  as 

gaskets and O rings are assembled to every block. If rubber parts are 
missing, air leakage may occur. 

 

Manifold 50-VFE-X60: 
Removal of valve 

  Remove screws and gently lift valve from manifold. 

  Ensure gasket and spacer are not misplaced or damaged. 

  Disconnect electrical connection. 

7 Maintenance - continued 

Assembly of valve 

  Reconnect the electrical connection. 

  Assemble  valve  to  the  manifold  in  the  correct  orientation,  ensuring 

spacer and all gaskets are present. 

  Torque tighten screws to torque shown in Table 5. 

 

Valve Series

 

Appropriate tightening torque 

N•m

 

50-VFE3000 

1.3 to 1.5 

50-VFE5000 

1.3 to 1.5 

Table 5 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

50-VFE-X60 Valve mounting: 

 

Figure 12 

 
 
 
 

7 Maintenance - continued 

 

Figure 13 

 
 
 
 
 
 
 

 

 

Figure 14 

 
 
 
 
 

7 Maintenance - continued 

 

Figure 15 

 
 
 
 
 
 

 

 

Figure 16 

 
 
 