Installation manual WKP type multi-blade fire damper

 

Version: 2.0.1 

 

1.

 

Installation manual 

Prior to the installation, fire dampers should be checked whether there has been no 

damage to the dampers during transportation or storage. Then carry out opening and 

closing in order to test the proper operation. Both opening and closing should proceed 

smoothly. During the testing of WKP-T fire damper, check the operation of the ratchet 

mechanism by cutting off the power and waiting approx. 1-4 seconds (lock response time) 

from the time of cutting of the power to the release of the release mechanism. 

 

1.1.

 

Lightweight partition walls

 

made of plasterboards 

 

The fire dampers, to maintain declared EI120 fire resistance class, should be installed in 

plasterboard walls which are verified and classified as EI120. The supporting structure of  

a partition wall are the steel studs made of cold rolled galvanized sheet steel. There are 

two layers of plasterboards 12,5  [mm]  thick mounted to each side of the steel sections. 
Plasterboards 

should be

 

mounted in such way, that their vertical and horizontal joints on 

one layer do not coincide with joints on adjacent layers. Boards are mounted with use of 

quick-mounting screws. Mineral wool is used as a filling of the wall.  

 

 

INSTALLATION TECHNOLOGY  

According to the Figure 1 

 

 

1.

 

Make a rectangular opening in the wall with dimensions: (A+315) x (B+240). 

2.

 

Place the mounting sections made of cold rolled sheet steel (fig. 1) on the inner side 

of the installation opening. 

3.

 

Screw previously prepared plasterboards to the fixed sections: 

a.

 

With thickness of 12,5 [mm] and width of 125 [mm] – 8 pcs. Two by wto on 
both sides of the installation opening; 

b.

 

With thickness of 12,5 [mm] and width of 40 [mm] – 3 pcs. Directly adjacent 

to the spacer insulating the body of the device. 

4.

 

Fill the steel flanges of the fire damper with mineral wool with minimum density  

of 150 [kg/m

3

]. 

5.

 

Put the fire damper into installation opening and screw the body with screws 

through the plasterboard slats to the steel sections of the partition wall. Arrange 2-4 
screws on each horizontal section of the body frame and 2-4 screws on vertical 

sections of the steel frame on the opposite side of the lever mechanism. 

6.

 

Secure the holes near the actuator casing, created as a result of installing the fire 

damper. In order to do it, cut 4 steel C-sections with length less than 140 [mm] and 

screw it to the lower and the upper surface of the casing and the horizontal steel 

bars of the partition wall (leading screws through the slats from point 3). Fill the 
surface of the holes with mineral wool with density recommended by the 

manufacturer of the wall, and then fix two plasterboards on both sides of the wall. 

7.

 

Fill the gaps between the outside dimension of the fire damper and the edges of the 

installation opening with mineral wool with density recommended by the 

manufacturer. 

8.

 

Cover the edges  of the fire damper with flange, made of plasterboards with 

thickness of 12,5 [mm] on both sides of the wall, screwing it to the sections of the 
partition wall and the edges of the fire damper. 

Содержание WKP

Страница 1: ......

Страница 2: ...eet steel fig 1 on the inner side of the installation opening 3 Screw previously prepared plasterboards to the fixed sections a With thickness of 12 5 mm and width of 125 mm 8 pcs Two by wto on both sides of the installation opening b With thickness of 12 5 mm and width of 40 mm 3 pcs Directly adjacent to the spacer insulating the body of the device 4 Fill the steel flanges of the fire damper with...

Страница 3: ...istance of no more than 25 mm from the clearance of the fire damper see Fig 1 It is prohibited to place the screws within 50 mm from the release of the locking mechanism In order to ensure the access to the electric drive mechanism make an additional opening in the flange made of plasterboards with dimensions of 140x320 mm from the appropriate side of the partition wall 9 Install the mounting fram...

Страница 4: ...page 4 z 6 Installation manual WKP type multi blade fire damper Version 2 0 1 Figure 1 Installation method of the WKP type multi blade fire dampers in lightweight partition walls ...

Страница 5: ...ed downwards respectively by dimension N x 100 where N the number of blade driven directly by the actuator 3 Put the fire damper into the installation opening in such way that the axis of the fire damper matches the axis of the wall 4 After setting the fire damper fill the gap between the fire damper and the wall with cement mortar lime mortar or concrete 5 Install the mounting frames on both side...

Страница 6: ...page 6 z 6 Installation manual WKP type multi blade fire damper Version 2 0 1 Figure 2 Installation method of the WKP type multi blade fire dampers in concrete or brickwork walls ...

Отзывы: