background image

 

 

Version: 6.00 
Date of editing: 16.09.2022 r. 

Page 5 z 9 

Installation manual 

WKP-P

 

 

Figure 4. Installing method of WKP-P fire dampers in rigid wall

 

 

Содержание WKP-P

Страница 1: ...a Installation manual v WKP P Rectangular fire damper https www smay eu ...

Страница 2: ...s the right to make changes to this document TABLE OF CONTENT INSTALLATION TECHNOLOGY 2 I INSTALATION TECHNOLOGY RIGID WALL 3 II INSTALLATION TECHNOLOGY STRUCTURES THICKER THAN 125 MM 7 III INSTALLATION TECHNOLOGY FLEXIBLE WALL WITH 125 MM THICKNESS 7 IV INSTALLATION TECHNOLOGY MKW HONEYCOMB MESH COVER 9 ...

Страница 3: ...amper by dust and dirt using a foil or other screening material It can prevent components of fire damper by damage Dampers to preserve of the declared resistance insulation and smoke leakage EIS120 EIS90 should be installed on wall which was classified as EIS120 EIS90 It is allowed to install WKP P dampers in wall with other fire resistance should be remembered that fire resistance in this situati...

Страница 4: ... the axis of the wall and ensure a concentricity of fire damper and installation opening d After setting the fire damper as described fill the gap between the fire damper and the wall with cement cement lime mortar or concrete e After drying of the mortar approx 48 hours remove used supports or suspensions check the fire damper correct operation and leave it in fully open position Figure 1 Dimensi...

Страница 5: ... 4 z 9 Installation manual WKP P Figure 2 Installing method of WKP P fire dampers in rigid wall baffle axis should be in line with wall axis Figure 3 Installing method of WKP P fire dampers in rigid wall baffle axis should be in line with wall axis ...

Страница 6: ...Version 6 00 Date of editing 16 09 2022 r Page 5 z 9 Installation manual WKP P Figure 4 Installing method of WKP P fire dampers in rigid wall ...

Страница 7: ... damper as described and build it in wall duct made of PROMATECT L500 boards with 50 mm thickness must be installed The band around the duct must be made by PROMATECT L500 with 50 mm thickness and 60 mm width Connection of damper and the wall and damper with the band must be made by K84 glue The sides of the duct and the band must be connected by using 4 2x90 4 8x120 screws ...

Страница 8: ... mm installation opening should have height H 160 mm acceptable 140 180 mm c Make a frame of two layers of GKF boards 15 mm thick and a width corresponding to the installation opening screwed tightly bearing in mind the exact sealing at their joints by using Hilti Firestop Coating CP 673 Promastop Coating Promaseal Mastic or Soudal Firesilicone B1 FR d Put the closed fire damper into the installat...

Страница 9: ...te of editing 16 09 2022 r Page 8 z 9 Installation manual WKP P Figure 7 Installation method of fire dampers WKP P in flexible wall with 125 mm thick Figure 8 Installation method of fire dampers WKP P in flexible wall ...

Страница 10: ... the deflection around the perimeter b Honeycomb mesh cover install to the wall with use metal pins for gas concrete 6x32 and with use 5x40 screws c Honeycomb mesh cover install in this way as shown in the figure below Outer edges of openings on left side of mesh cover as well on a top and on a bottom must be in line with inside edges of the damper Figure 9 Installation method of MKW B honeycomb m...