Installation manual 

WKP-P

 

INSTALLATION TECHNOLOGY 

Before installing the fire dampers, make sure that there are no damage, during transport or storage, that could block 

the baffle.  

Check that the baffle can be opened and closed (full opening and closing position). To open fire dampers WKP-p use 

the actuator key. 

The opening and closing must proceed smoothly (not stepwise). 

Do not pull by baffle to open or close fire damper, it may cause permanent damage, not covered by the warranty. 

Before  installation  verify  dimensions  of  a  gap  between  bottom  blade  and  inner  part  of  housing  under  blade,  and 

between top blade and inner part of housing above blade. The dimension of the gap can not be lower than 4 mm. 

Before  installing,  secure  the  fire  damper,  by  dust  and  dirt,  using  a  foil  or  other  screening  material.  It  can  prevent 
components of fire damper by damage.  
Dampers to preserve of the declared resistance, insulation and smoke leakage EIS120, EIS90, should be installed on 
wall, which was classified as EIS120, EIS90. 
It is allowed to install WKP-P dampers in wall with other fire-resistance, should be remembered that fire-resistance in 
this situation is resistance of lowest classified (in this regard) element in this system. 
Ducts  made  of  flammable  and  non-flammable  materials  can  be  connected  to  the  damper.  Ducts  should  be  installed 
that they cannot load the damper during fire. Ducts lengthening during fire can be compensated by support and knee. 
ATTENTION:  Distance  between  fire  dampers  or  fire  damper  and  construction  elements  must  be  compatible  with 
standard 1366-2: 

a.

 

Minimal 200 mm between fire damper, which are installed in different ventilating wires, 

b.

 

Minimal 75 mm between fire damper and construction element (wall/ceiling). 

 

 

Содержание WKP-P

Страница 1: ...a Installation manual v WKP P Rectangular fire damper https www smay eu ...

Страница 2: ...s the right to make changes to this document TABLE OF CONTENT INSTALLATION TECHNOLOGY 2 I INSTALATION TECHNOLOGY RIGID WALL 3 II INSTALLATION TECHNOLOGY STRUCTURES THICKER THAN 125 MM 7 III INSTALLATION TECHNOLOGY FLEXIBLE WALL WITH 125 MM THICKNESS 7 IV INSTALLATION TECHNOLOGY MKW HONEYCOMB MESH COVER 9 ...

Страница 3: ...amper by dust and dirt using a foil or other screening material It can prevent components of fire damper by damage Dampers to preserve of the declared resistance insulation and smoke leakage EIS120 EIS90 should be installed on wall which was classified as EIS120 EIS90 It is allowed to install WKP P dampers in wall with other fire resistance should be remembered that fire resistance in this situati...

Страница 4: ... the axis of the wall and ensure a concentricity of fire damper and installation opening d After setting the fire damper as described fill the gap between the fire damper and the wall with cement cement lime mortar or concrete e After drying of the mortar approx 48 hours remove used supports or suspensions check the fire damper correct operation and leave it in fully open position Figure 1 Dimensi...

Страница 5: ... 4 z 9 Installation manual WKP P Figure 2 Installing method of WKP P fire dampers in rigid wall baffle axis should be in line with wall axis Figure 3 Installing method of WKP P fire dampers in rigid wall baffle axis should be in line with wall axis ...

Страница 6: ...Version 6 00 Date of editing 16 09 2022 r Page 5 z 9 Installation manual WKP P Figure 4 Installing method of WKP P fire dampers in rigid wall ...

Страница 7: ... damper as described and build it in wall duct made of PROMATECT L500 boards with 50 mm thickness must be installed The band around the duct must be made by PROMATECT L500 with 50 mm thickness and 60 mm width Connection of damper and the wall and damper with the band must be made by K84 glue The sides of the duct and the band must be connected by using 4 2x90 4 8x120 screws ...

Страница 8: ... mm installation opening should have height H 160 mm acceptable 140 180 mm c Make a frame of two layers of GKF boards 15 mm thick and a width corresponding to the installation opening screwed tightly bearing in mind the exact sealing at their joints by using Hilti Firestop Coating CP 673 Promastop Coating Promaseal Mastic or Soudal Firesilicone B1 FR d Put the closed fire damper into the installat...

Страница 9: ...te of editing 16 09 2022 r Page 8 z 9 Installation manual WKP P Figure 7 Installation method of fire dampers WKP P in flexible wall with 125 mm thick Figure 8 Installation method of fire dampers WKP P in flexible wall ...

Страница 10: ... the deflection around the perimeter b Honeycomb mesh cover install to the wall with use metal pins for gas concrete 6x32 and with use 5x40 screws c Honeycomb mesh cover install in this way as shown in the figure below Outer edges of openings on left side of mesh cover as well on a top and on a bottom must be in line with inside edges of the damper Figure 9 Installation method of MKW B honeycomb m...

Отзывы: