SMAY KWP-O-E Скачать руководство пользователя страница 3

 

 

Version 6.00 
Date of editing: 16.09.2022 r. 

Page 2 z 18 

Installation manual 

KWP-O-ES

 

INSTALLATION TECHNOLOGY 

Prior  to  the  installation,  fire dampers  should be  checked whether  there  has  been  no  damage  to  the dampers during 

transportation or storage..  

Check whether the damper baffle could be opened and closed (fully open and closed position). To open fire dampers 

KWP-O-E use the actuator key. 

The full opening and closing must proceed smoothly (not stepwise). 

You must not pull by baffle to open or close fire damper, it could cause lead to permanent damage, not covered by the 

warranty. 

While testing KWP-O-S open it by key, placed on the damper. 

The  damper  must  be  protected  with  covering  material  before  montage,  so  it  will  be  protected  from  soiling,  and 

consequently damaging the elements of the damper.  

 

ATTENTION:  Distance  between  fire  dampers  or  fire  damper  and  construction  elements  must  be  compatible  with 

standard 1366-2: 

Minimal 200 mm between fire damper, which are installed in different ventilating wires, 

Minimal 75 mm between fire damper and construction element (wall/ceiling). 

 

Before  installing  fire  dampers  please  read  assembly  technology  recommended  by  the  manufacturer.  The  way  of 

installing  recommended  by  one  manufacturer  may  not  be  the  same  for  other  dampers.  Recommended  material  and 
dimensions  of  the  openings  follow  from  experience  from  conducted  research.  In  rectangular  dampers,  most  of  all 

dampers with cross-sectional area more than 1 m2, it is recommended to use mounting wedge and spreader securing 

the housing against squeezing during assembly. 

Squeezing the housing can change the dimensions of slot between baffle and housing, correct dimensions of this slot is 

needed to keep correct way of opening and closing the damper. Correct preparation of the damper for the installation 

is presented on the figure 3 and 4.

 

 

Figure  1.  Correct  preparation  of  the  damper  for  the  installation  (using  spreader  securing 
the housing) 

Содержание KWP-O-E

Страница 1: ...a Installation manual KWP O E S Fire Damper rectangular v https www smay eu ...

Страница 2: ...ght to make changes to this document TABLE OF CONTENT INSTALLATION TECHNOLOGY 2 I INSTALLATION TECHNOLOGY RIGID WALL 3 II INSTALLATION TECHNOLOGY FLEXIBLE WALL 5 III INSTALLATION TECHNOLOGY CEILING 6 IV INSTALLATION TECHNOLOGY STRUCTURES THICKER THAN 135 MM 8 V INSTALLATION TECHNOLOGY FOR FIRE DAMPERS IN BATTERIES 8 ...

Страница 3: ...tion elements must be compatible with standard 1366 2 Minimal 200 mm between fire damper which are installed in different ventilating wires Minimal 75 mm between fire damper and construction element wall ceiling Before installing fire dampers please read assembly technology recommended by the manufacturer The way of installing recommended by one manufacturer may not be the same for other dampers R...

Страница 4: ...er body dimension 60 mm from one side fix it with suspension Z1 and from other side fix it to the ventilation duct suspended on Z2 suspension c After setting the fire damper as described fill the gap between the fire damper and the wall with cement cement lime mortar concrete or PROMASTOP MG III made by PROMAT d After 48 hours from the installation the suspensions and supports used during installa...

Страница 5: ...Version 6 00 Date of editing 16 09 2022 r Page 4 z 18 Installation manual KWP O ES Figure 3 Installation method of fire dampers KWP O in rigid wall ...

Страница 6: ...al Firesilicone B1 FR c Put the closed fire damper into the installation opening and support or suspend in this way that the minimum installation depth mark is on the plane of the flange surface d After setting the fire damper as described fill the gap between the fire damper and the wall with non flammable mineral wool of high density 80 kg m3 or more e Seal the place of filling with mineral wool...

Страница 7: ...een the fire damper and the wall with cement cement lime mortar concrete Under difficult working conditions producer recommend PROMASTOP MG III mortar of production of the PROMAT company d Mount the mounting brackets on each side Number of mounting brackets Side length up to 500 mm 1 pcs Side length from 500 to 800 mm 2 pcs e Housing install with actuator similarly as in the picture Only the lengt...

Страница 8: ...Version 6 00 Date of editing 16 09 2022 r Page 7 z 18 Installation manual KWP O ES Figure 6 Installation method of fire dampers KWP O in ceiling ...

Страница 9: ...y There are two possibilities of realizing the order of fire damper batteries basic and complete First one covers the set of fire dampers assembly strips and complete set of self tapping screws The purchase of other materials needed such as intumescent gasket PROMASEAL PL PVC SK mineral wool for thermal insulation with minimum density of 60 kg m3 and aluminum tape remains with the Customer The sec...

Страница 10: ...ree space between the fire dampers as shown in w1 NOTE The alternative way of wool mounting is to use two layers of wool with thickness of 30 mm In this case apply the fire resistant PROMASTOP Coating with width of 50 mm The mass is placed between the strips of wool and between wool and damper housings c Place the fire damper A on the fire damper B and assemble them together on the front and back ...

Страница 11: ...e way of wool mounting is to use two layers of wool with thickness of 30 mm In this case apply the fire resistant PROMASTOP Coating with width of 50 mm The mass is placed between the strips of wool and between wool and damper housings c Place the fire damper B on the fire damper C and assemble them together on the front and back with use of perforated assembly strips 2 and self tapping screws M6x1...

Страница 12: ...he openings in fire damper body In order to carry out the correct assembly 4 self tapping screws should be used per each assembly strip with length of 1200 mm c Fill the whole free space between the joint of fire dampers with non combustible mineral wool as shown in w1 NOTE The alternative way of wool mounting is to use two layers of wool with thickness of 30 mm In this case apply the fire resista...

Страница 13: ...EP 1 a Fix the gasket on insulating spacer of one of adjoining fire dampers position 1 in the Figure 14 b Set together the sides of fire damper A and the fire damper B where the gasket was fixed and assemble them together on the front and back with use of perforated assembly strips 2 and self tapping screws M6x16 3 which should be tightened into the openings in fire damper body In order to carry o...

Страница 14: ...ery size and its arrangement For vertical battery consisting of two KWP fire dampers B1 120 x H1 H2 180 Figure 15 For vertical battery consisting of three KWP fire dampers B1 120 x H1 H2 H3 240 Figure 16 For horizontal battery consisting of two KWP fire dampers B1 B2 180 x H1 120 Figure 17 For battery consisting of four KWP fire B1 B2 180 x H1 H2 180 Figure 18 b Put the battery of fire dampers int...

Страница 15: ...Version 6 00 Date of editing 16 09 2022 r Page 14 z 18 Installation manual KWP O ES Figure 13 Installation of a battery consisting of two fire dampers KWP in vertical arrangement in ceiling ...

Страница 16: ...Version 6 00 Date of editing 16 09 2022 r Page 15 z 18 Installation manual KWP O ES Figure 14 Installation of a battery consisting of three fire dampers KWP in vertical arrangement in ceiling ...

Страница 17: ...Version 6 00 Date of editing 16 09 2022 r Page 16 z 18 Installation manual KWP O ES Figure 15 Installation of battery consisting of two fire dampers KWP in horizontal arrangement in ceiling ...

Страница 18: ...Version 6 00 Date of editing 16 09 2022 r Page 17 z 18 Installation manual KWP O ES Figure 16 Installation of a battery consisting of four fire dampers KWP in ceiling ...

Страница 19: ...75 0 400 53 9 63 8 73 7 83 0 92 6 98 0 112 7 122 6 131 9 141 8 152 0 177 7 188 5 199 1 500 72 2 83 5 94 1 105 5 116 2 127 5 138 5 149 9 160 2 171 2 199 8 211 5 223 2 600 80 2 92 6 104 7 117 1 129 2 142 0 154 1 166 5 178 9 191 3 222 0 235 5 248 7 700 88 4 102 0 115 2 14 9 142 9 156 8 163 1 176 0 197 3 211 1 247 6 264 9 282 5 800 96 6 111 8 125 8 141 3 155 9 170 9 186 1 200 7 215 7 230 6 266 0 281 6...

Отзывы: