Fire damper can be cleaned with a dry or damp cloth. Dirt and other pollution can be cleaned with generally available
cleaners. Do not use aggressive, caustic cleaners and sharp tools.
Replacing the thermal fuse element in KWP-LS
Exchange must be performer on the closed position.
To replace the thermal fuse element:
a.
Release the spring
7
from the spring mechanism plate
1
.
b.
Unscrew the bolt
14
and pull out the entire thermal fuse element. The assembly of these elements consists of a
thermal fuse element
16
, hook
6
, console
5
, washer
7
, release spring
9
, nut M8
12
, round nut
8
, thermal fuse
plate
13
. To replace the thermal fuse, press the hook
6
towards to the nut and put into console. When you put
the thermal fuse, release the hook and push the lever of hand mechanism.
c.
Install the assembly of thermal fuse with the bolt
14.
d.
Pull the spring onto spring mechanism plate
1.
e.
Open the fire damper and check that it opens and closes correctly after push the hand release lever
11
.
Figure 21. Spring mechanism
–
replacement of the thermal fuse element