background image

                     

 

MGC100 Petrol Genset Controller User Manual                                                                  Page 6 of 16 

3

 

SPECIFICATION 

Table 3 Technical Parameters

 

Item 

Contents 

Working Voltage 

DC9.0V  to  18.0V,  continuous  power  supply  (suitable  for  DC12V 
system) 

Overall Consumption 

Regular working:<1W (Standby mode:<0.4W) 

AC Volt Input: 
3-phase 4-wire 
3-phase 3-wire 
2-phase 3-wire 
Single phase 2-wire 

 
AC 30V – AC 360V (ph-N) 
AC 50V – AC 620V (ph-ph) 
AC 30V – AC 360V (ph-N) 
AC 30V – AC 360V (ph-N) 

AC Frequency 

50Hz/60Hz 

Speed Sensor Voltage 

1.0V to 24V(effective value) 

Speed Sensor Frequency 

10000Hz(Max) 

Start Relay 

7A    DC12V power supply 

Fuel Relay 

7A    DC12V power supply 

Flexible Transistor 

1A    DC12V connect to (B+) 

Overall Dimensions 

105.8mm x 61mm x 36.6mm 

Panel Cutout 

92mm x 44mm 

Working Temperature 

(-25~+70)°C

     

 

Working Humidity 

(20~93)%RH 

Storage Temperature 

(-25~+70)°C 

Protection Level 

IP55 Gasket 

Insulation 

Apply  AC2.2kV  voltage  between  high  voltage  terminal  and  low 
voltage  terminal;  The  leakage  current  is  not  more  than  3mA  within 
1min.   

Weight 

94g 

Содержание MGC100

Страница 1: ...MGC100 PETROL GENSET CONTROLLER USER MANUAL...

Страница 2: ...NEL 7 4 2 2 ALARM ICON INDICATION 8 4 2 3 PANEL INDICATOR 8 4 3 OPERATION 8 4 3 1 REMOTE START SEQUENCE 8 4 3 2 REMOTE STOP SEQUENCE 8 4 3 3 MANUAL START STOP 9 5 PROTECTION 9 6 CONNECTION 10 7 DEFINI...

Страница 3: ...n permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above Any reference to trademarked product names used within this publication is owned...

Страница 4: ...lights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not strictly observed could result in damage or destruction of equipment WARNING Ind...

Страница 5: ...atus Chose to control Petrol Genset or Diesel Genset via connection Suitable for 3 phase 4 wire 3 phase 3 wire 2 phase 3 wire single phase 2 wire 120V 240V systems with frequency 50 60 Hz Protection f...

Страница 6: ...AC 360V ph N AC 30V AC 360V ph N AC Frequency 50Hz 60Hz Speed Sensor Voltage 1 0V to 24V effective value Speed Sensor Frequency 10000Hz Max Start Relay 7A DC12V power supply Fuel Relay 7A DC12V power...

Страница 7: ...icator are normal In setting menu upturn or decrease parameter value it can be double clicked In setting menu press it for more than 3s to exit this menu Page Confirm Switch display contents of nixie...

Страница 8: ...y are disengaged for the pre set rest period Crank Rest Time begins and wait for the next crank attempt after the Crank Rest Time delay start for 3s preheat and ETS start to output after Crank Rest Ti...

Страница 9: ...2s 2 High Temperature detect when start Alarm Stop when High Temperature is active and lasts for 2s 3 Over Speed detect when start Alarm Stop after duration exceeds Over Speed Stop Delay 4 Gen Over V...

Страница 10: ...enset controller When this terminal connected with nothing it used as petrol genset controller 6 High Temperature 1 0mm2 Ground connected is active B 7 Low Oil Pressure 1 0mm2 Ground connected is acti...

Страница 11: ...start the genset P05 Stop Delay 0 3600 s 1 Time from remote stop signal is deactivated to stop the genset P06 Start Attempts 1 10 times 3 It is maximum of start attempts when starter failed to start...

Страница 12: ...0 r min 840 In starting process if genset rotate speed exceed this value it is regarded as genset start success starter will separate P23 Disc Freq 10 30 Hz 14 In starting process if genset frequency...

Страница 13: ...stop electromagnet Close before stoping idle ended Open when ETS Delay ended 5 Air Flap Choke Used for genset with choke valve electromagnet Close when gen start and open when safety running delay is...

Страница 14: ...or 3s to exit parameter setting status 8 2 RESTORE FACTORY SETTINGS In emergency stop input status press and for 5s at the same time it can restore to default and reset will be displayed on LED 8 3 EL...

Страница 15: ...start battery is strictly prohibit 2 Speed Sensor Input NOTE Speed sensor is magnetic equipment which is installed on engine body for testing flywheel teeth number 2 core shielding wire is used for t...

Страница 16: ...Table 10 Fault Finding Symptoms Possible Solutions Controller no response with power Check starting batteries Check controller connection wirings Check DC fuse Crank not disconnect Check fuel oil circ...