HGM9580 BUS TIE BUS PARALLEL UNIT
HGM9580 Bus Tie Bus Parallel Unit ISSUE 2014-02-16 Version 1.0 Page 24 of 33
7.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS
Form 2
No.
Type
Description
0
Not Used
1~6
Reserved
7
Custom Combined 1
Details of function description please see the following.
8
Custom Combined 2
9
Custom Combined 3
10
Custom Combined 4
11
Custom Combined 5
12
Custom Combined 6
13~17
Reserved
18
Audible Alarm
Action when warning, trips. Can be connected
annunciator externally. When
“alarm mute” configurable
input port is active, it can remove the alarm.
19~25
Reserved
26
Remote Control Output
This port is controlled by communication (PC).
27~28
Reserved
29
Close Bus Output
Control bus to take load.
30
Open Bus Output
Control bus to off load.
31~43
Reserved
44
Bus 1 OK
Action when bus 1 is normal.
45
Reserved
46
Bus 2 OK
Action when bus 2 is normal.
47
Synchronizing
Action when controller is synchronizing.
48
Common Alarm
Action when genset common warning or common trips
alarm.
49
Reserved
50
Reserved
51
Common Trip
Action when common trips alarm.
52
Common Warn
Action when common warning alarm.
53
Reserved
54
Battery Over Voltage
Action when battery’s over voltage warning alarm.
55
Battery Under Voltage
Action when battery’s low voltage warning alarm.
56~68
Reserved
69
Digital Input 1 Active
Action when input port 1 is active
70
Digital Input 2 Active
Action when input port 2 is active
71
Digital Input 3 Active
Action when input port 3 is active
72
Digital Input 4 Active
Action when input port 4 is active
73
Digital Input 5 Active
Action when input port 5 is active
74
Digital Input 6 Active
Action when input port 6 is active
75
Digital Input 7 Active
Action when input port 7 is active
76~230
Reserved
231
Manual Mode
Action in Manual mode.
232
Reserved