HGM9580 BUS TIE BUS PARALLEL UNIT
HGM9580 Bus Tie Bus Parallel Unit ISSUE 2014-02-16 Version 1.0 Page 23 of 33
No.
Items
Parameters
Defaults
Description
synchronized;
If the frequency difference is smaller
than 0.1Hz, then the phase will be
synchronized;
4
Voltage Difference
(0-30)V
3
The voltage difference between bus 1
and bus 2. It is considered voltage
synchronization when the voltage
difference between Bus 1 and Bus 2 is
lower than synchronization voltage
difference.
5
Positive
Freq
Difference
(0-2.0)Hz
0.2
The frequency difference between bus
1 and bus 2. It is considered frequency
synchronization when the frequency
difference between bus 1 and bus 2 is
less than Positive Freq Difference but
more than Negative Freq Difference.
6
Negative
Freq
Difference
(0-2.0)Hz
0.1
7
Phase
Angle
Difference
(0-20)°
10
Initial phase difference between bus 1
and bus 2. It is considered Check
Phase Angle when the initial phase
difference is lower than synchronization
phase difference.
8
Fail to Sync Delay
(5.0-300.0)s
60.0
When the controller detects no Sync
signal during the preset delay, it will
send
corresponding
alarm
signal
according to the action type.
Action Type:
0
:
Warn
;
1
:
Trip.
9
Fail to Sync Action (0-1)
0
10
Sync Freq Gain
(0~500)
20
Adjust and control before paralleling.
11
Sync Freq Stab.
(0~2000)
20
Adjust and control before paralleling.
12
Sync Volt Gain
(0~500)
20
Adjust and control before paralleling.
13
Sync Volt Stab.
(0~2000)
20
Adjust and control before paralleling.
14
MSC Number
(1-32)
2
15
Too Few Modules
Action
(0-2)
1
Action Type:
0
:
No Action
;
1
:
Warn
;
2
:
Trip.
16
Baud Rate
(0-3)
1
0
:
500Kbit/s
;
1
:
250Kbit/s
;
2
:
125Kbit/s
;
3
:
50Kbit/s.