HGM9580 Bus Tie Bus Parallel Unit
USER MANUAL
Smartgen Technology
Страница 1: ...HGM9580 Bus Tie Bus Parallel Unit USER MANUAL Smartgen Technology...
Страница 2: ...http www smartgen com cn http www smartgen cn Email sales smartgen cn All rights reserved No part of this publication may be reproduced in any material form including photocopying or storing in any m...
Страница 3: ...tion of notation used within this publication SIGN INSTRUCTION NOTE Highlights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not strictly...
Страница 4: ...SETTING MENU 10 4 4 AUTO OPERATION 13 4 5 MANUAL OPERATION 14 5 PROTECTIONS 15 5 1 WARNING ALARMS 15 5 2 TRIP ALARM 16 6 WIRING CONNECTION 17 7 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS 20 7...
Страница 5: ...GM9580 Bus Tie Bus Parallel Unit controls a bus breaker which can control the controller to synchronize the two ways buses via MSC CAN if the synchronization requirements have satisfied The powerful 3...
Страница 6: ...Uca Phase voltage Ua Ub and Uc Phase voltage Ua Ub and Uc Phase sequence Phase sequence Frequency Hz Frequency Hz Synchronization parameters Voltage Difference Between Bus 1 and Bus 2 Frequency Diffe...
Страница 7: ...DC28V power supply output Flexible Relay Output 3 7A DC28V power supply output Flexible Relay Output 4 7A AC250V volts free output Flexible Relay Output 5 7A AC250V volts free output Flexible Relay Ou...
Страница 8: ...and Alarm indicator Alarm Type Warning Indicator Alarm Indicator Warning Slow flashing Slow flashing Trip Alarm Off Fast flashing Running indicator It is light on when both of bus 1 and bus 2 are norm...
Страница 9: ...een scroll 2 Up cursor and increase value in setting menu Down Decrease 1 Screen scroll 2 Down cursor and decrease value in setting menu Left 1 Screen scroll 2 Left move cursor in setting menu Right 1...
Страница 10: ...ay all alarm information warning alarm trip alarm Event log Make records about all events trip alarm power on events and Bus switch events and the real time when events occur Others including Time and...
Страница 11: ...n setting Return Battery setting Bus setting Close Delay Form 2 Use to scroll settings to enter settings to return to previous menu form 1 Open Delay Breaker setting Input setting Output setting Modul...
Страница 12: ...on 1 0 Page 12 of 33 Close Delay 00003 Form 5 Press to change cursor position are used for changing cursor value to confirm setting form 4 to exit setting form 4 Open Delay Close Delay 00003 Form 6 Us...
Страница 13: ...the bus will be paralleled with the other bus b If both of Bus 1 and Bus 2 are active the controller will adjust frequency and voltage to synchronize bus with bus when synchronism requirements has be...
Страница 14: ...f either of the two buses is deactivate then bus close signal will be initiated and the bus will be paralleled with the other bus If both of Bus 1 and Bus 2 are active the controller will adjust frequ...
Страница 15: ...iate a warning alarm 3 Bus Breaker Fail When the controller detects that the bus close status is not configured in the input port it will initiate a warning alarm 4 Digital Input When the digit input...
Страница 16: ...it will initiate a trip alarm 4 MSC Too Few Sets When the controller detects fewer modules on the MSC link than the minimum number configured in the unit it will initiate a trip alarm There are 2 pos...
Страница 17: ...n parallel Max 20A fuse is recommended 3 COM Output 7 8 2 5mm2 Connected with B 4 Aux output 7 1 5mm2 B is supplied by 3 point rated 16A 5 Aux output 8 1 5mm2 B is supplied by 3 point rated 16A 6 Aux...
Страница 18: ...single end earthed 27 MSC2 CAN H 0 5mm2 28 MSC2 CAN L 0 5mm2 33 RS485 Impedance 120 shielding wire is recommended its single end earthed 34 RS485 0 5mm2 35 RS485 0 5mm2 36 Aux output 5 2 5mm2 Normall...
Страница 19: ...33 NO Functions Cable Size Remark 47 Bus 1 C phase voltage sensing input 1 0mm2 Connected to C phase of Bus 1 2A fuse is recommended 48 Bus 1 N wire input 1 0mm2 Connected to N wire of Bus 1 NOTE USB...
Страница 20: ...1 3P3W 2 2P3W 3 1P2W 2 Volt Trans PT 0 1 0 0 Disable 1 Enable Switch Setting 1 Close Time 0 20 0 s 5 0 Pulse width of switch on When it is 0 means output constantly 2 Open Time 0 20 0 s 3 0 Pulse wid...
Страница 21: ...Setting 0 50 0 User defined See form 3 2 Active Type 0 1 0 0 Closed to active 1 Open to active 3 Arming 0 2 2 0 From paralleling 1 Always 2 Never 4 Active Actions 0 2 2 0 Warn 1 Trip 2 Indication 5 A...
Страница 22: ...ntents Setting 0 239 30 Open Bus Output See form 2 2 Active Type 0 1 0 0 Normally open 1 Normally close Flexible Output Port 6 1 Contents Setting 0 239 29 Close Bus Output See form 2 2 Active Type 0 1...
Страница 23: ...egative Freq Difference 6 Negative Freq Difference 0 2 0 Hz 0 1 7 Phase Angle Difference 0 20 10 Initial phase difference between bus 1 and bus 2 It is considered Check Phase Angle when the initial ph...
Страница 24: ...hen bus 1 is normal 45 Reserved 46 Bus 2 OK Action when bus 2 is normal 47 Synchronizing Action when controller is synchronizing 48 Common Alarm Action when genset common warning or common trips alarm...
Страница 25: ...HGM9580 BUS TIE BUS PARALLEL UNIT HGM9580 Bus Tie Bus Parallel Unit ISSUE 2014 02 16 Version 1 0 Page 25 of 33 233 Auto Mode Action in Auto mode 234 Bus Load 235 239 Reserved...
Страница 26: ...ts of probably condition output S1 output port 1 is active Close when probably condition output S1 is active inactive close when active disconnect when inactive Contents of probably condition output S...
Страница 27: ...ng when input is active 6 Panel Lock All buttons in panel is inactive except and there is in the right of first row in LCD when input is active 7 12 Reserved 13 Aux Bus Closed Connect bus loading swit...
Страница 28: ...rsion 1 0 Page 28 of 33 36 Simulate Auto key An external button not self locking can be connected and pressed as simulate panel 37 Reserved 38 Simulate Close Button An external button not self locking...
Страница 29: ...HGM9580 BUS TIE BUS PARALLEL UNIT HGM9580 Bus Tie Bus Parallel Unit ISSUE 2014 02 16 Version 1 0 Page 29 of 33 8 TYPICAL DIAGRAM HGM9580 Typical Diagram...
Страница 30: ...HGM9580 BUS TIE BUS PARALLEL UNIT HGM9580 Bus Tie Bus Parallel Unit ISSUE 2014 02 16 Version 1 0 Page 30 of 33 9 TYPICAL APPLICATION...
Страница 31: ...battery s positive and negative directly then connect wires from battery s positive and negative to controller s positive and negative input ports in order to prevent charge disturbing the controller...
Страница 32: ...arallel Unit ISSUE 2014 02 16 Version 1 0 Page 32 of 33 11 USB Users can set the controller s parameters and monitor the controller s status via the test software which provided by Smartgen company Th...
Страница 33: ...Alarm in running Check related switch and its connections according to the information on LCD Check auxiliary input ports Genset running while ATS not transfer Check ATS Check the connections between...