HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
HGM8156 Genset Parallel (With Mains) Controller 2019-09-10 Version 1.1 Page 30 of 44
8.2.1 DEFINED COMBINATION OUTPUT
Defined combination output is composed by 3 parts: OR condition output S1 or S2 and AND condition
output S3.
S1 or S2 is
TRUE
, and S3 is
TRUE
, defined combination output is outputting;
S1 and S2 are
FALSE
, or S3 is
FALSE
, defined combination output is not outputting.
NOTE:
S1, S2, S3 can be set as any contents except for “defined combination output” in the output settings.
NOTE:
3 parts of defined combination output (S1, S2, S3) couldn’t include or recursively include themselves.
For example:
Contents of OR condition output S1: Input port 1 is active;
Close when OR condition output S1 is active /inactive: close when active (disconnect when inactive);
Contents of OR condition output S2, input port 2 is active;
Close when OR condition output S2 is active /inactive: close when active (disconnect when inactive);
Contents of AND condition output S3: Input port 3 is active;
Close when AND condition output S3 is active /inactive: close when active (disconnect when inactive);
When input port 1 active or input port 2 is active, if input port 3 is active, defined combination output is outputting; If input
port 3 is inactive, defined combination output is not outputting;
When input port 1 is inactive and input port 2 is inactive, whatever input port 3 is active or not, defined combination output
is not outputting.