HGM8151 Genset Parallel Controller User Manual Page 61 of 66
16.14
PERKINS
It is suitable for ADEM3/ADEM4 engine control module. Engine type is 2306, 2506, 1106, and 2806.
Table 39 Connector
Terminals of controller
Connector
Remark
Fuel relay output
1,10,15,33,34
Start relay output
-
Connect to starter coil directly
CAN GND
-
CAN
communication
shielding
line
(connect with controller’s terminal only)
CAN(H)
31
Using impedance 120Ω connecti
ng line
CAN(L)
32
Using impedan
ce 120Ω connecting line
Engine type: Perkins.
16.15
SCANIA
It is suitable for S6 engine control module. Engine type is DC9, DC12, and DC16.
Table 40 B1 Connector
Terminals of controller
B1 connector
Remark
Fuel relay output
3
Start relay output
-
Connect to starter coil directly
CAN GND
-
CAN
communication
shielding
line
(connect with controller’s
terminal only)
CAN(H)
9
Using impedance 120Ω connecting line
CAN(L)
10
Using impedance 120Ω connecting line
Engine type: Scania.
16.16
VOLVO EDC3
Suitable engine control mode is TAD1240, TAD1241, and TAD1242.
Table 41
“
Stand alone
”
Connector
Terminals of controller
“Stand alone” connector
Remark
Fuel relay output
H
Start relay output
E
Auxiliary output 1
P
ECU power
Configure output 1 as
“
ECU power
”
Table 42
“
Data bus
”
Connector
Terminals of controller
“Data bus” connector
Remark
CAN GND
-
CAN
communication
shielding
line
(connect with controller’s termin
al only)
CAN(H)
1
Using impedance 120Ω connecting line
CAN(L)
2
Using impedanc
e 120Ω connecting line
Engine type: Volvo.