HGM7220N/HGM7220S GENSET CONTROLLER USER MANUAL
HGM7220N/HGM7220S Genset Controller 2019-02-28 Version 1.0 Page 33 of 60
No.
Items
Range
Default
Description
SGE02-4G Setting
1
SGE02-4G Enable
(0-1)
1
0: Disabled; 1: Enabled
2
SMS Enable
(0-1)
0
0: Disabled; 1: Enabled
3
Mobile Number
Max. 20 bits
All numbers are needed to add district or country
number, e.g. China 13666666666.
4
GPRS Enable
(0-1)
1
0: Disabled; 1: Enabled
5
GPS Enable
(0-1)
1
0: Disabled; 1: Enabled
6
Longitude
(-180-180)
°
113.33
When GPS is disabled, monitor module
GPS position and altitude information can be
inputted.
7
Latitude
(-90-90)
°
34.48
8
Altitude
(-9999.9-9999.9)m 100
Cloud Server Setting
1
Site Name
20 characters/40 letters/40 numbers
2
URL Server
3
Server Port
(0-65535)
91
4
Module Password
123456
16 characters
8.2 DEFINITION CONTENT OF PROGRAMMABLE OUTPUT PORTS 1~6
Table 11 - Programmable Output Ports 1~6
No.
Type
Description
0
Not Used
1
Custom Period 1
For details about function description please see the following
content.
2
Custom Period 2
3
Custom Period 3
4
Custom Period 4
5
Custom Period 5
6
Custom Period 6
7
Custom Combined 1
8
Custom Combined 2
9
Custom Combined 3
10
Custom Combined 4
11
Custom Combined 5
12
Custom Combined 6
13
Reserved
14
Reserved
15
Reserved
16
Reserved
17
Air Flap Control
It is activated when over speed shutdown and emergency
shutdown alarms occur, which can turn off the engine intake.
18
Audible Alarm
It is activated when warning, shutdown and electrical trip
alarms appear. Announciator can be connected externally; if
aux. input port is configured as
“Mute Alarms” and if it is