HGM7220N/HGM7220S GENSET CONTROLLER USER MANUAL 

HGM7220N/HGM7220S Genset Controller              2019-02-28            Version 1.0              Page 33 of 60 

No. 

Items 

Range 

Default 

Description 

SGE02-4G Setting 

SGE02-4G Enable 

(0-1) 

0: Disabled; 1: Enabled 

SMS Enable 

(0-1) 

0: Disabled; 1: Enabled 

Mobile Number   

Max. 20 bits 

All  numbers  are  needed  to  add  district  or  country 

number, e.g. China 13666666666.   

GPRS Enable   

(0-1) 

0: Disabled; 1: Enabled 

GPS Enable   

(0-1) 

0: Disabled; 1: Enabled 

Longitude 

(-180-180)

°

 

113.33 

When  GPS  is  disabled,    monitor  module 

GPS position and altitude information can be 

inputted.   

Latitude 

(-90-90)

°

 

34.48 

Altitude 

(-9999.9-9999.9)m  100 

Cloud Server Setting 

Site Name 

20 characters/40 letters/40 numbers 

URL Server 

www.monitoryun.com

   

Server Port 

(0-65535) 

91 

 

Module Password 

123456 

16 characters 

8.2  DEFINITION CONTENT OF PROGRAMMABLE OUTPUT PORTS 1~6 

Table 11 - Programmable Output Ports 1~6 

No. 

Type 

Description 

Not Used 

 

Custom Period 1 

For details about function description please see the following 

content. 

Custom Period 2 

Custom Period 3 

Custom Period 4 

Custom Period 5 

Custom Period 6 

Custom Combined 1 

Custom Combined 2 

Custom Combined 3 

10 

Custom Combined 4 

11 

Custom Combined 5 

12 

Custom Combined 6 

13 

Reserved 

 

14 

Reserved 

 

15 

Reserved 

 

16 

Reserved 

 

17 

Air Flap Control 

It  is  activated  when  over  speed  shutdown  and  emergency 

shutdown alarms occur, which can turn off the engine intake. 

18 

Audible Alarm 

It  is  activated  when  warning,  shutdown  and  electrical  trip 

alarms appear. Announciator can be connected externally; if 

aux.  input  port  is  configured  as 

“Mute  Alarms”  and  if  it  is 

Содержание HGM7220N Series

Страница 1: ...HGM7220N HGM7220S SERIES GENSET CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Страница 2: ...tart genset in manual mode Manual Set the module to manual mode Auto Set the module to auto mode C O Control breaker close and open in manual mode Set Confirm Enter menu list page Move cursor in param...

Страница 3: ...alarm fast flashing 5 times per second Trip and stop alarm fast flashing 5 times per second NOTES a Status Indicators illuminate always after crank disconnection and before ETS extinguished during ot...

Страница 4: ...start idle delay is initiated if configured g During start idle delay period under speed under frequency under voltage alarms are inhibited When this delay is over warming up delay starts if configure...

Страница 5: ...ter after stop delay and failed to stop alarm will be eliminated automatically g When after stop delay is over genset shall enter standby status 4 4 MANUAL START STOP OPERATION a HGM7220N 7220S Press...

Страница 6: ...generator close occurs In the process of generator close transfer failure is detected When the detection time is due if close fails then generator close is waited for If transfer failure warning is e...

Страница 7: ...of waiting for synchronization or if synchronization fails press generator C O button to cancel synchronization and generator breaker is open Then press mains C O button to force mains on load Mains D...

Страница 8: ...nd action is selected Trip it will send trip signals 3 Over Power When controller detects that the genset power value power is positive exceeds the pre set value and action is selected Trip it will se...

Страница 9: ...20N HGM7220S GENSET CONTROLLER USER MANUAL HGM7220N HGM7220S Genset Controller 2019 02 28 Version 1 0 Page 21 of 60 7 WIRINGS CONNECTION HGM7220N 7220S controller back panel is as below Figure 2 Back...

Страница 10: ...250VAC 2 5 mm2 13 14 Charger D 1 0mm2 Connected with charger starter s D WL terminal Please hang it up if there is not this terminal 15 Aux Output 5 8A 1 5 mm2 B is supplied by Terminal 2 rated 8A Fo...

Страница 11: ...0mm2 Connected to W phase output of genset 2A fuse recommended 39 Gen N2 line Input 1 0mm2 Connected to N line output of genset 40 Mains R phase Voltage Monitoring Input 1 0mm2 Connected to R phase of...

Страница 12: ...e percentage return value and delay value also can be set 9 Under Voltage 0 200 80 10 Over Frequency 0 200 Disabled The setting value is mains rated frequency percentage return value and delay value a...

Страница 13: ...Server www monitoryun com 3 Server Port 0 65535 91 4 Module Password 123456 16 characters 8 2 DEFINITION CONTENT OF PROGRAMMABLE OUTPUT PORTS 1 6 Table 11 Programmable Output Ports 1 6 No Type Descri...

Страница 14: ...button and genset will start After the cranking times set before controller will send signal of Start Failure then press stop to reset controller Recover the action to prevent engine from cranking suc...

Страница 15: ...GM7220S GENSET CONTROLLER USER MANUAL HGM7220N HGM7220S Genset Controller 2019 02 28 Version 1 0 Page 46 of 60 13 TYPICAL APPLICATION Figure 4 HGM7220S Typical Application Figure 5 HGM7220N Typical Ap...

Страница 16: ...h capacity in start and fuel output is recommend 14 INSTALLATION 14 1 SGE02 EXPANSION MODULE 14 1 1 4G ANTENNA PORT Connect 4G antenna and 4G port of SGE02 Antenna port 50 SMA USB 14 1 2 GPS ANTENNA P...

Страница 17: ...ys on the controller and this means SIM is not inserted or SIM contact is not good Please refer to the following installation steps Figure 9 SIM Installation Steps 14 2 FIXING CLIPS Controller is pane...

Страница 18: ...ithin 1 24 VAC effective value during the full speed 12VAC is recommended in rated speed When the speed sensor is installed let the sensor spun to contacting flywheel first then make it back 1 3 lap a...

Отзывы: