HGM7100N GENSET CONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 26 of 48
No.
Items
Range
Default
Description
5
Over Power Setting
(0-1)
0
0: Disabled; 1: Enabled
6
Reverse
Power
Setting
(0-1)
0
0: Disabled; 1: Enabled
Switch
1
Switching Time
(0-7200)s
5
Time from open mains to close generator or
from open generator to close mains.
2
Close Delay
(0-20.0)s
5.0
Pulse width of mains closed and generator
closed; 0s stands for constant output.
3
Open Delay
(0-20.0)s
3.0
Pulse width of open mains and open
generator.
4
Switching Detection
Time
(0-20.0)s
5.0
It is the time to detect auxiliary contactor after
ATS switching.
5
Switch
Failure
Warning Enabled
(0-1)
0
0: Disabled; 1: Enabled
6
Open
Detection
Enabled
(0-1)
0
7
Immediately
Trip
when
Mains
Dropout
(0-1)
1
0: Disabled; 1: Enabled
Module
1
Power On Mode
(0-2)
0
0: Stop Mode; 1: Manual Mode; 2: Auto Mode
2
Communication
Address
(1-254)
1
Controller address while in remote monitoring
status.
3
Communication
Stop-bit Setting
(0-1)
1
0: 2-bit stop bit; 1: 1-bit stop bit
4
Language Selection (0-2)
0
0: Simplified Chinese; 1: English; 2: Other
5
Password Setting
(0-65535)
00318
This password used to enter into advanced
parameter setting.
6
Backlight Time
(0-3600) s
300
When it is 0s, LCD always light.
Schedule & Maintenance
1
Scheduled
Start
Setting
(0-1)
0
0: Disabled; 1: Enabled
2
Scheduled Not Run
Setting
(0-1)
0
0: Disabled; 1: Enabled
3
Maintenance
Setting
(0-1)
0
0: Disabled; 1: Enabled
Analog Sensors
Temperature Sensor
1
Curve Type
(0-15)
7
SGX. Detail to see Table 13
2
Open Circuit Action
(0-2)
0
0: Warning; 1: Shutdown; 2: None
3
High
Temp
Shutdown Setting
(0-300)ºC
98
When
temperature
value
of
external
connected temperature sensor is higher than
the setting point, controller will initiate high
temperature shutdown alarm (judgment only
starts after safety on delay expired). Delay
value can be set.