HGM7100N GENSET CONTROLLER USER MANUAL 

HGM7100N Genset Controller                        2017-08-26                      Version1.0                Page 26 of 48 

No. 

Items 

Range 

Default 

Description 

Over Power Setting 

(0-1) 

0: Disabled; 1: Enabled 

Reverse 

Power 

Setting 

(0-1) 

0: Disabled; 1: Enabled 

Switch 

Switching Time 

(0-7200)s   

Time  from  open  mains  to  close  generator  or 
from open generator to close mains. 

Close Delay 

(0-20.0)s 

5.0 

Pulse  width  of  mains  closed  and  generator 
closed; 0s stands for constant output. 

Open Delay 

(0-20.0)s 

3.0 

Pulse  width  of  open  mains  and  open 
generator. 

Switching Detection 
Time 

(0-20.0)s 

5.0 

It is the time to detect auxiliary contactor after 
ATS switching.   

Switch 

Failure 

Warning Enabled 

(0-1) 

0: Disabled; 1: Enabled 

Open 

Detection 

Enabled 

(0-1) 

Immediately 

Trip 

when 

Mains 

Dropout   

(0-1) 

0: Disabled; 1: Enabled 

Module 

Power On Mode 

(0-2) 

0: Stop Mode; 1: Manual Mode; 2: Auto Mode 

Communication 
Address 

(1-254) 

Controller address while in remote monitoring 
status. 

Communication 
Stop-bit Setting 

(0-1) 

0: 2-bit stop bit; 1: 1-bit stop bit 

Language Selection  (0-2) 

0: Simplified Chinese; 1: English; 2: Other 

Password Setting 

(0-65535) 

00318 

This  password  used  to  enter  into  advanced 
parameter setting.   

Backlight Time 

(0-3600) s 

300 

When it is 0s, LCD always light. 

Schedule & Maintenance   

Scheduled 

Start 

Setting 

(0-1) 

0: Disabled; 1: Enabled 

Scheduled Not Run 
Setting 

(0-1) 

0: Disabled; 1: Enabled 

Maintenance 
Setting 

(0-1) 

0: Disabled; 1: Enabled 

Analog Sensors 
Temperature Sensor 

Curve Type 

(0-15) 

SGX. Detail to see Table 13 

Open Circuit Action 

(0-2) 

0: Warning; 1: Shutdown; 2: None 

High 

Temp 

Shutdown Setting 

(0-300)ºC 

98 

When 

temperature 

value 

of 

external 

connected temperature sensor is higher than 
the  setting  point,  controller  will  initiate  high 
temperature  shutdown  alarm  (judgment  only 
starts  after  safety  on  delay  expired).  Delay 
value can be set. 

Содержание HGM7100N Series

Страница 1: ...HGM7100N SERIES HGM7110N 7120N GENSET CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Страница 2: ...13 5 2 1 MANUAL SWITCHING PROCESS 13 5 2 2 AUTO SWITCHING PROCESS 13 6 PROTECTION 14 6 1 WARNINGS 14 6 2 SHUTDOWN ALARM 16 6 3 TRIP AND STOP ALARM 18 6 4 TRIP ALARM 18 7 WIRINGS CONNECTION 19 8 SCOPES...

Страница 3: ...SER MANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 4 of 48 11 SENSOR SETTING 42 12 COMMISSIONING 43 13 TYPICAL APPLICATION 44 14 INSTALLATION 46 14 1 FIXING CLIPS 46 14 2 OVERALL DIMENSI...

Страница 4: ...r close or open in C O interface under manual mode only suit for HGM7120N Close Pressing this key to control breaker close under user manual mode only suit for HGM7110N Open Pressing this key to contr...

Страница 5: ...t Panel Indication Figure 2 HGM7120N Front Panel Indication NOTE Part of indicator lights illustration Table 4 Alarm Indicator Description Alarm Type Alarm Indicators Warning alarm slowly flash once p...

Страница 6: ...ted with negative of starter battery 2 B 2 5mm2 Connected with positive of starter battery If wire length is over 30m better to double wires in parallel Max 20A fuse is recommended 3 Emergency Stop 2...

Страница 7: ...to see table 12 23 Aux Input 2 1 0mm2 Ground connected is active B 24 Aux Input 3 1 0mm2 Ground connected is active B 25 Aux Input 4 1 0mm2 Ground connected is active B 26 Aux Input 5 1 0mm2 Ground c...

Страница 8: ...t 1 0mm2 Connected to S phase of mains 2A fuse recommended HGM7110N without 42 Mains T phase voltage monitoring input 1 0mm2 Connected to T phase of mains 2A fuse recommended HGM7110N without 43 Mains...

Страница 9: ...The setting value is mains rated voltage percentage return value and delay value also can be set 8 Mains Under Voltage 0 200 80 9 Mains Over Frequency 0 200 Disabled The setting value is mains rated...

Страница 10: ...conditions and inspecting engine speed Details to see the following installation description 3 Engine Rated Speed 0 6000 RPM 1500 Provide standard for judging over under speed and on load speed 4 Spe...

Страница 11: ...higher than the setting value starter will disconnect Details to see the following installation description 19 Oil Pressure of Crank Disconnect 0 1000 kPa 200 When engine oil pressure is higher than t...

Страница 12: ...ge Shutdown 0 200 80 10 Gen Over Frequency Shutdown 0 200 114 The setting values are rated frequency percentage of generator and delay value can be set 11 Gen Under Frequency Shutdown 0 200 80 12 Gen...

Страница 13: ...de 0 2 0 0 Stop Mode 1 Manual Mode 2 Auto Mode 2 Communication Address 1 254 1 Controller address while in remote monitoring status 3 Communication Stop bit Setting 0 1 1 0 2 bit stop bit 1 1 bit stop...

Страница 14: ...nected oil pressure sensor is lower than the setting point controller will initiate low oil pressure warning alarm judgment only starts after safety on delay expired Return value and delay value can b...

Страница 15: ...panel are inactive except for and displays on the right side of the first line of LCD status page 7 Reserved 8 Idle Control Mode Under speed under frequency and under voltage are not protected in thi...

Страница 16: ...HGM7100N GENSET CONTROLLER USER MANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 44 of 48 13 TYPICAL APPLICATION Figure 5 HGM7100N Typical Application Figure 6 HGM7120N Typical Application...

Страница 17: ...ANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 45 of 48 Figure 7 Single Phase 2 Wire Connection Diagram Figure 8 2Phase 3Wire Connection Diagram NOTE Expand relay with high capacity in st...

Страница 18: ...and negative input ports in order to prevent charge disturbing the controller s normal working a SPEED SENSOR INPUT Speed sensor is the magnetic equipment which be installed in starter and for detecti...

Отзывы: