HGM7100N GENSET CONTROLLER USER MANUAL 

HGM7100N Genset Controller                        2017-08-26                      Version1.0                Page 24 of 48 

No. 

Items 

Range 

Default 

Description 

14  Charge Alt Fail 

(0-60.0)V 

8.0 

If the voltage of charger D+(WL) is lower than 
the  setting  value  during  gen-set  normal 
running,  controller  will  initiate  fail  to  charge 
warning alarms. 

15  Start Attempts 

(1-10)times 

Maximum crank times when engine starts fail. 
If reach this number, controller will send start 
failure signals. 

16 

Crank 

Disconnect 

Condition 

(0-6) 

Details please to see table 14

 

There  are  3  cranking  disconnect  conditions, 
which  can  be  used  separately  or  together, 
aiming  to  disconnect  starter  motor  with 
engine as soon as possible.   

17 

Frequency of Crank 
Disconnect 

(0-200)% 

24 

The  setting  value  is  the  percentage  of  rated 
frequency,  when  generator  frequency  is 
higher  than  the  set  value,  starter  will  be 
disconnected.  Details  to  see  the  following 
installation description. 

18 

Speed 

of 

Crank 

Disconnect 

(0-200)% 

24 

The  setting  value  is  the  percentage  of  the 
rated  speed,  when  speed  is  higher  than  the 
setting  value,  starter  will  disconnect.  Details 
to see the following installation description.   

19 

Oil 

Pressure 

of 

Crank Disconnect 

(0-1000)kPa 

200 

When  engine  oil  pressure  is  higher  than  the 
setting  value,  starter  will  disconnect.  Details 
to see the following installation description. 

20 

Battery Low Voltage 
Start Enabled 

(0-1) 

0: Disabled; 1:Enabled 

21 

Battery Low Voltage 
Start Value 

(1.0-60.0)V 

10.0 

It is the low-battery-start value. Active when in 
auto mode. 

22 

Battery Low Voltage 
Stop Value 

(1.0-60.0)V 

24.0 

The  shutdown  value  after  low-battery-start 
and charged. Active when in auto mode. 

23 

Battery Low Voltage 
Start/Stop Delay 

(0-3600)s 

60 

When battery voltage reached to engine start 
threshold,  engine  will  start  up  after  delay 
expired;  when  battery  voltage  reached  to 
engine  stop  threshold,  engine  will  stop  after 
delay expired. 

Generator 

Power 

Supply 

System 

(0-3) 

0: 3P4W; 
1: 3P3W 

2: 2P3W 

3: 1P2W 

Engine Poles 

(2-64) 

It  is  the  number  of  engine  poles,  which  can 
help engine without installing speed sensor to 
calculate engine speed.   

Rated Voltage 

(30-30000)V 

230 

Provide  standard  for  judging  gen  over/under 
voltage,  and  on-load  voltage.  If  voltage 
transformer is used, this value is transformer 
primary voltage.   

Содержание HGM7100N Series

Страница 1: ...HGM7100N SERIES HGM7110N 7120N GENSET CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Страница 2: ...13 5 2 1 MANUAL SWITCHING PROCESS 13 5 2 2 AUTO SWITCHING PROCESS 13 6 PROTECTION 14 6 1 WARNINGS 14 6 2 SHUTDOWN ALARM 16 6 3 TRIP AND STOP ALARM 18 6 4 TRIP ALARM 18 7 WIRINGS CONNECTION 19 8 SCOPES...

Страница 3: ...SER MANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 4 of 48 11 SENSOR SETTING 42 12 COMMISSIONING 43 13 TYPICAL APPLICATION 44 14 INSTALLATION 46 14 1 FIXING CLIPS 46 14 2 OVERALL DIMENSI...

Страница 4: ...r close or open in C O interface under manual mode only suit for HGM7120N Close Pressing this key to control breaker close under user manual mode only suit for HGM7110N Open Pressing this key to contr...

Страница 5: ...t Panel Indication Figure 2 HGM7120N Front Panel Indication NOTE Part of indicator lights illustration Table 4 Alarm Indicator Description Alarm Type Alarm Indicators Warning alarm slowly flash once p...

Страница 6: ...ted with negative of starter battery 2 B 2 5mm2 Connected with positive of starter battery If wire length is over 30m better to double wires in parallel Max 20A fuse is recommended 3 Emergency Stop 2...

Страница 7: ...to see table 12 23 Aux Input 2 1 0mm2 Ground connected is active B 24 Aux Input 3 1 0mm2 Ground connected is active B 25 Aux Input 4 1 0mm2 Ground connected is active B 26 Aux Input 5 1 0mm2 Ground c...

Страница 8: ...t 1 0mm2 Connected to S phase of mains 2A fuse recommended HGM7110N without 42 Mains T phase voltage monitoring input 1 0mm2 Connected to T phase of mains 2A fuse recommended HGM7110N without 43 Mains...

Страница 9: ...The setting value is mains rated voltage percentage return value and delay value also can be set 8 Mains Under Voltage 0 200 80 9 Mains Over Frequency 0 200 Disabled The setting value is mains rated...

Страница 10: ...conditions and inspecting engine speed Details to see the following installation description 3 Engine Rated Speed 0 6000 RPM 1500 Provide standard for judging over under speed and on load speed 4 Spe...

Страница 11: ...higher than the setting value starter will disconnect Details to see the following installation description 19 Oil Pressure of Crank Disconnect 0 1000 kPa 200 When engine oil pressure is higher than t...

Страница 12: ...ge Shutdown 0 200 80 10 Gen Over Frequency Shutdown 0 200 114 The setting values are rated frequency percentage of generator and delay value can be set 11 Gen Under Frequency Shutdown 0 200 80 12 Gen...

Страница 13: ...de 0 2 0 0 Stop Mode 1 Manual Mode 2 Auto Mode 2 Communication Address 1 254 1 Controller address while in remote monitoring status 3 Communication Stop bit Setting 0 1 1 0 2 bit stop bit 1 1 bit stop...

Страница 14: ...nected oil pressure sensor is lower than the setting point controller will initiate low oil pressure warning alarm judgment only starts after safety on delay expired Return value and delay value can b...

Страница 15: ...panel are inactive except for and displays on the right side of the first line of LCD status page 7 Reserved 8 Idle Control Mode Under speed under frequency and under voltage are not protected in thi...

Страница 16: ...HGM7100N GENSET CONTROLLER USER MANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 44 of 48 13 TYPICAL APPLICATION Figure 5 HGM7100N Typical Application Figure 6 HGM7120N Typical Application...

Страница 17: ...ANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 45 of 48 Figure 7 Single Phase 2 Wire Connection Diagram Figure 8 2Phase 3Wire Connection Diagram NOTE Expand relay with high capacity in st...

Страница 18: ...and negative input ports in order to prevent charge disturbing the controller s normal working a SPEED SENSOR INPUT Speed sensor is the magnetic equipment which be installed in starter and for detecti...

Отзывы: