HGM7100N GENSET CONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 24 of 48
No.
Items
Range
Default
Description
14 Charge Alt Fail
(0-60.0)V
8.0
If the voltage of charger D+(WL) is lower than
the setting value during gen-set normal
running, controller will initiate fail to charge
warning alarms.
15 Start Attempts
(1-10)times
3
Maximum crank times when engine starts fail.
If reach this number, controller will send start
failure signals.
16
Crank
Disconnect
Condition
(0-6)
2
Details please to see table 14
There are 3 cranking disconnect conditions,
which can be used separately or together,
aiming to disconnect starter motor with
engine as soon as possible.
17
Frequency of Crank
Disconnect
(0-200)%
24
The setting value is the percentage of rated
frequency, when generator frequency is
higher than the set value, starter will be
disconnected. Details to see the following
installation description.
18
Speed
of
Crank
Disconnect
(0-200)%
24
The setting value is the percentage of the
rated speed, when speed is higher than the
setting value, starter will disconnect. Details
to see the following installation description.
19
Oil
Pressure
of
Crank Disconnect
(0-1000)kPa
200
When engine oil pressure is higher than the
setting value, starter will disconnect. Details
to see the following installation description.
20
Battery Low Voltage
Start Enabled
(0-1)
0
0: Disabled; 1:Enabled
21
Battery Low Voltage
Start Value
(1.0-60.0)V
10.0
It is the low-battery-start value. Active when in
auto mode.
22
Battery Low Voltage
Stop Value
(1.0-60.0)V
24.0
The shutdown value after low-battery-start
and charged. Active when in auto mode.
23
Battery Low Voltage
Start/Stop Delay
(0-3600)s
60
When battery voltage reached to engine start
threshold, engine will start up after delay
expired; when battery voltage reached to
engine stop threshold, engine will stop after
delay expired.
Generator
1
Power
Supply
System
(0-3)
0
0: 3P4W;
1: 3P3W
2: 2P3W
3: 1P2W
2
Engine Poles
(2-64)
4
It is the number of engine poles, which can
help engine without installing speed sensor to
calculate engine speed.
3
Rated Voltage
(30-30000)V
230
Provide standard for judging gen over/under
voltage, and on-load voltage. If voltage
transformer is used, this value is transformer
primary voltage.