HGM6110/6120 AUTO START MODULE
HGM6110/6120 Auto Start Module ISSUE 2.0 2008-10-27 Page 12 of 24
6. CONNECTING TERMINAL
Pin
Function
Dim
Description
1
DC Plant Supply Input
(-ve)
2. 5mm
System DC negative input.
(Battery Negative).
2
DC Plant Supply Input
(+ve)
2. 5mm
System DC positive input.
(Battery
Positive).(Recommended
Maximum Fuse 20A)
3
Emergency Stop Input
2. 5mm
Plant ve. Also supplies fuel &
start outputs.
(Recommended Maximum Fuse 32A)
4
Fuel relay Output
2. 5mm
Plant ve from pin 3.
7 Amp rated.
5
Start relay Output
2. 5mm
Plant ve from pin 3.
7 Amp rated.
6
Auxiliary Output relay 1
1.5mm
Plant ve from
pin 2.
7 Amp rated.
7
8
9
Auxiliary Output relay 2
1.5mm
Free voltage contacts.
7 Amp rated
10
11
Auxiliary Output relay 3
2.5mm
12
13
Auxiliary Output relay 4
2.5mm
Free voltage contacts.
16 Amp rated
Reference
table 2
14
Charge fail / excite
1.0mm
Do not connect to ground (battery –ve)
15
Magnetic ve
16
Magnetic pickup -ve
Connect to Magnetic Pickup device