HGM6110/6120 AUTO START MODULE
HGM6110/6120 Auto Start Module ISSUE 2.0 2008-10-27 Page 11 of 24
LOW OIL PRESSURE
, if the module detects that the engine oil pressure has
fallen below the low oil pressure setting level after the
Safety On
timer has
expired, a shutdown will occur.
OVERSPEED
, if the engine speed exceeds the setting value a shutdown is
initiated.
UNDERSPEED
, if the engine speed falls below the setting value after the Safety
On timer has expired, a shutdown is initiated.
LOSS OF SPEED SIGNAL,
if the speed sensing signal is lost, a shutdown is
initiated.
GENERATOR OVER FREQUENCY
if the module detects a generator output
frequency in excess of the setting value a shutdown is initiated.
GENERATOR UNDER FREQUENCY
, if the module detects a generator output
frequency below the setting value after the Safety On timer has expired, a
shutdown is initiated.
GENERATOR OVER VOLTAGE
if the module detects a generator output voltage
in excess of the setting value a shutdown is initiated.
GENERATOR UNDER VOLTAGE
if the module detects a generator output
voltage below the setting value after the Safety On timer has expired, a shutdown
is initiated.
GENERATOR OVER CURRENT,
if the module detects a generator output current
in excess of the setting value is initiated, a shutdown is initiated.
FAIL TO START
, if the engine does not fire after the pre-set number of attempts
has been made a shutdown will be initiated.
AUXILIARY INPUTS
, if an auxiliary input has been configured as a shutdown the
appropriate information will be displayed.