HGM501Genset Controller 

HGM501 Genset Controller              Version V1.0              2012-07-10                  Page 12 of 15 
 

them (each pressing will increase/decrease the value for one step). When the 

screen  shows  the  needed  value,  press 

  to  confirm  and  enter  the  next 

menu item; 

Rated power settings: power LED window first digit will start flashing; use 

 

and 

  to choose a value from 0 to 9, then press 

  to confirm and enter 

next settings; power window second digit will start flashing, use 

  and 

 

to choose a value from 0 to 9 and 

  to confirm; power window third digit will 

start  flashing,  use 

  and 

  to  choose  a  value  from  0  to  9  and 

  to 

confirm and enter the next menu item; 

Rated  frequency  setting:  frequency  LED  indicator  illuminates,  multifunctional 

window starts flashing; press 

  and 

  to choose frequency value (there 

are  2  choices:  50  and  60Hz),  every  time  you  press  the  button  the  value  will 

change;  when  the  needed  value  is  displayed,  press 

  to  confirm  and 

automatically enter the next setting; 

Auto protection setting: when auto protection light indicator is on, press 

  to 

confirm  and  auto  protection  will  continue  to  be  enabled;  use 

  or 

  to 

make  indicator  off  and  press 

  to  disable  auto  protection.  When  the  light 

indicator is off, it means that auto protection is disabled. Enabling this function 
is recommended; 

C.T  setting:  multifunctional  window  first  digit  will  start  flashing;  use 

  and 

  to choose a value from 0 to 9, then press 

  to confirm and enter next 

settings;  power  window  second  digit  will  start  flashing,  use 

  and 

  to 

choose a value from 0 to 9 and 

  to confirm; power window third digit will 

start  flashing,  use 

  and 

  to  choose  a  value  from  0  to  9  and 

  to 

confirm and enter the next menu item; 

Engine temperature sensor type setting: when engine temperature indicator is 

on,  multifunctional  window  will  start  flashing:  use 

  and 

  to  select 

temperature sensor type (there are five choices: L-0

L-1

L-2

L-3

L-4. L-0 

stands for 'no temperature sensor used'). Every time you press the button, the 
temperature  sensor  type  will  change;  when  the  needed  type  is  displayed, 

press 

  button to confirm and automatically enter the next setting; 

Generator temperature sensor type setting: the same as 7. 

Turn the start key from ON to OFF position to finish configuration. 

NOTE: during configuration use 

  button to enter the next  menu item and 

Содержание HGM501

Страница 1: ...HGM501 Gen set Controller USER MANUAL Smartgen Technology...

Страница 2: ...ronic means or other without the written permission of the copyright holder Smartgen Technology reserves the right to change the contents of this document without prior notice Version History Date Ver...

Страница 3: ...NICAL DATA 5 4 OPERATION 6 4 1 BUTTON DESCRIPTION 6 4 2 START STOP OPERATION 7 4 2 1 STARTING PROCEDURE 7 4 2 2 STOPPING PROCEDURE 7 5 AUTO PROTECTION 8 6 TERMINAL 9 7 CONFIGURABLE PARAMETERS 10 7 1 C...

Страница 4: ...RISTICS 1 Two specialized LED displays single phase voltage display and total active power voltage display calculated using single phase power taking load as balanced 2 Multifunction LED display that...

Страница 5: ...ase 4 wire L and N only AC 30V 360V ph N AC 30V 360V ph N AC 30V 360V ph N Alternator frequency 50 60Hz Start relay output 7A DC12V power supply output Fuel relay output 7A DC12V power supply output C...

Страница 6: ...alarm UP SCROLL 1 During parameter configuration pressing this button increases the set value 2 During normal operation press this button to switch to the upper LED DOWN SCROLL 1 During parameter conf...

Страница 7: ...6 Generator temp 7 Auto protection If on auto protection is enabled if not it is disabled 8 Run on indicator Fuel relay output indicator 9 Crank indicator Start output indicator 10 Engine oil warning...

Страница 8: ...g If the set value is exceeded by 5 7 5 and continuous for more than 3 hours then alarm shutdown will be initiated If the set value is exceeded by 7 5 10 and continues for more than 1 hours alarm shut...

Страница 9: ...after Safety On Delay when voltage frequency overload high temperature protection is initiated fuel output deactivates 6 TERMINAL HGM501 controller back panel is shown below Terminal connections desc...

Страница 10: ...lock START input 1 5mm2 Hand turn start start relay output Output activates when electric lock key is turned to START position 11 Start relay output 1 5mm2 Rated current 7A power supplied by terminal...

Страница 11: ...4 Select this according to the used sensor 7 2 PARAMETER CONFIGURATION Before using controller for the first time parameters must be configured rated voltage rated frequency rated power set values mus...

Страница 12: ...nd auto protection will continue to be enabled use or to make indicator off and press to disable auto protection When the light indicator is off it means that auto protection is disabled Enabling this...

Страница 13: ...sure all parameters are configured correctly and oil pressure light is on 3 Ensure the controller DC power supply is fused and correctly connected to the positive and negative of starter battery 4 Tak...

Страница 14: ...oller is designed for panel mounting it is held with the help of fixing clips Overall and cutout dimensions can be seen below unit mm 1 Battery Voltage Input NOTE HGM501 controller is suitable for 9 1...

Страница 15: ...n generator is on load C T secondary must not be open circuit 2 Withstanding voltage test CAUTION If withstanding voltage test is conducted after the controller has already been installed onto the con...