HGM501Genset Controller
HGM501 Genset Controller Version V1.0 2012-07-10 Page 11 of 15
No
Parameter
Range
Default
factory
value
Description
3
Rated
frequency
50Hz
60Hz
50
Generator rated frequency
selection
4
Rated power
(0.0-99.9)kw
5.0
Generator
rated
Active
power
5
Enable Auto
protection
Enable
Disable
Enable
Irrespective
of
whether
gen-set auto protection is
enabled
6
C. T. Ratio
(0-999)/5
20/5
Unit: A/5mA
(Must correspond to the
used current transformer)
7
Engine
temperature
sensor type
L-0
L-1
L-2
L-3
L-4
L-0
L-0
:
Not used
L-1
:
TE1
L-2
:
TE2
L-3
:
TE3
L-4
:
TE4
Select this according to the
used sensor.
8
Generator
temperature
sensor type
L-0
L-1
L-2
L-3
L-4
L-0
L-0
:
Not used
L-1
:
TG1
L-2
:
TG2
L-3
:
TG3
L-4
:
TG4
Select this according to the
used sensor.
7.2.
PARAMETER CONFIGURATION
Before using controller for the first time, parameters must be configured: rated
voltage, rated frequency, rated power set values must comply with the used
generator, set C.T. ratio value should comply to the used current transformer.
1
When the controller is disconnected, press
button, then change start key
position from OFF to ON; after the controller is powered on release
button and all the three windows (voltage window, frequency window and
multifunctional window will show set parameters; at the same time voltage
window will start flashing showing three choices (1P/2P/3P) which mean
1P2W,2P3W, and 3P4W respectively. Use
and
to choose AC wire
type and
to confirm and automatically enter the next menu item;
2
Rated voltage value settings: there are 7 possible variants of voltage
(110/115/120/130/220/230/240V), use
and
to switchover between