HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL
HAT552/HAT553 ATS Controller 2020-05-14 Version 1.1 Page 17 of 35
No.
Item
Range
Default
Description
1: Fault
8
Auto Trans/Restore
(0-1)
1
0: Auto Trans/Non Restore
1: Auto Trans/Restore
9
Each Backup
(0-1)
1
0: Inactive
1: Active
10
Open Input Enable
(0~1)
0
0: Disable
1: Enable (HAT553)
If this is not connected, please set it to Disable.
11
No
Open
Transfer
Enable
(0~1)
0
0: Disable
1: Enable
When it is set to Enable, controller directly
transfers to the other circuit from one circuit;
and there is not open control output in the
transfer process. (HAT553)
Genset Setting
1
Genset Start Delay
(0~9999)s
1
Delay starts when genset prepares to start;
when delay is over, controller issues genset start
signal.
2
Genset Stop Delay
(0~9999)s
5
Delay starts when genset prepares to stop;
when delay is over, controller disconnects
genset start signal.
Scheduled Start/Stop Setting
1
Schedule Gen Enable
(0~1)
0
0: Disable
1: Enable
2
Schedule Load
(0~1)
0
0: Off Load
1: On Load
3
Schedule Period
(0~2)
0
0: Monthly
1: Weekly
2: Daily
4
Schedule Monthly
Month
January
February
March
April
May
June
July
August
September
October
November
December
5
Schedule Date
(1~31)
1
Date for genset start for each month.
6
Schedule Weekly
Week
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
7
Schedule Hours
(0~23)h
0
Time for scheduled start.
8
Schedule Minutes
(0~59)min
0
9
Schedule Work Time
(0~30000)min
30
Lasting time for scheduled start running.
Programmable Input Setting
1
Digital Input 1
(0~20)
0
Not Used
2
Active Type
(0~1)
0
0: Close to Activate
1: Open to Activate