Smartgen HAT220A Скачать руководство пользователя страница 7

HAT220A/HAT240A    Automatic Transfer Switch Controller

 

HAT220A/HAT240A ATS Controller      ISSUE 2011-05-20      Version1.1          Page 8 of 11 

Voltage  upper  limit 
value 

(50~300)V

 

264V 

It  can  only  be  set  via 
PC

 

Voltage  lower  limit 
value 

(50~300)V

 

172V 

Transfer priority 

1# priority, 
2# priority, 
no priority 

1# priority 

It  can  be  set  via 
controller 

panel 

potentiometer or PC

 

10 

AC option 

3 phase 4 wire 
Single-phase 2 
wire 

3 phase 4 wire 

It  can  only  be  set  via 
PC 

Note:

  In  the  above  table  of  ten  items,  select 

“3-phase  4-wire”  is  used  to  HAT220A; 

select “single-phase 2-wire” when used HAT240A controller. 

7  OPERATION CONTROL 

Auto/Manual operation, 

When controller in running, press

key to transfer controller into Auto or Manual mode 

(Mode is indicated by lamps of Auto and Manual). In Manual mode, press 

  key, load 

transfer into #I power supply side and press 

  key, load transfer into #II power supply 

side. 

Procedures of 

setting “#I power supply priority”, “#II power supply priority” and 

“No priority” show as following:

 

a)  Press 

key, 

key and

key simultaneously, when #I power supply  indication 

lamp,  automatic  status  indication  lamp  and  #II  power  supply  indication  lamp 

illuminate  simultaneously,  loose 

  key, 

key  and 

  key,  then  automatic 

status  indications  lamp  and  #II  power  supply  indication  lamp  will  not  illuminate,  #I 

power  supply  indication  lamp  illuminate,  then  controller  enters  into  setting  priority 

status.

 

b)  Press 

  key can circularly set three priority status:

 

1)  When  #I  power  supply  indication  lamp  illuminate,  at  the  same  time  #II  power 

supply indication lamp isn

’t illuminate , for #I transfer priority;

 

2)  When  #II  power  supply  indication  lamp  illuminate,  at  the  same  time  #I  power 

supply indication lamp isn

’t illuminate , for #II transfer priority; 

3)  When #I power supply indication and #II power supply indication lamp illuminate 

Содержание HAT220A

Страница 1: ...HAT220A HAT240A ATS Automatic Transfer Switch CONTROLLER OPERATING MANUAL Smartgen Electronic ...

Страница 2: ...NCE AND CHARACTERISTICS 4 3 TECHNICAL SPECIFICATIONS 5 4 PANEL OPERATION INSTRUCTION 6 5 PANEL OPERATION AND DIAGRAM CONNECTION 6 5 1 DELAY ADJUSTMENT 6 5 2 RECOVER DEFAULT DELAYS VALUE 7 6 PROGRAMMED PARAMETER AND RANGE 7 7 OPERATION CONTROL 8 8 FUNCTION OF TERMINALS 9 9 TYPICAL WIRING DIAGRAM 10 10 OVERALL AND MOUNTING DIMENSIONS 11 11 FAULT FINDING 11 ...

Страница 3: ...SG72 interface module USB to LINK via the PC test software About PC software s operation please refer to software manual of HAT220A HAT240A The voltage normal delay of I or II can be set 0 60 seconds and the start Genset delay can be set 0 90 seconds The voltage abnormal delay of I or II can be set 0 60 seconds and the stop Genset delay can be set 0 90 seconds I power supply priority Auto Manual N...

Страница 4: ...edback time 5 seconds During break on procedure if switch break on status signal is detected break off immediately Power supply normal delay 0 60 seconds can be adjusted via controller front panel potentiometer Power supply abnormal delay 0 60 seconds can be adjusted via controller front panel potentiometer default setting 5 seconds Genset start delay after 1 abnormal delay 0 60 seconds can be adj...

Страница 5: ...t start delay can set genset start signal output delay after I power supply abnormal Procedures of setting I power supply abnormal delay II power supply abnormal delay and Genset stop delay show as following a Press key and key simultaneously when I power supply indication lamp automatic status indication lamp and II power supply indication lamp simultaneously illuminate loose key and key I power ...

Страница 6: ...uminate simultaneously loose key and key I power supply indication lamp automatic status indication lamp and II power supply indication lamp will not illuminate simultaneous controller enters into delay value setting status b Press key when I power supply indication lamp automatic status indication lamp and II power supply indication lamp illuminate simultaneously will restore factory setting valu...

Страница 7: ...ransfer into I power supply side and press key load transfer into II power supply side Procedures of setting I power supply priority II power supply priority and No priority show as following a Press key key and key simultaneously when I power supply indication lamp automatic status indication lamp and II power supply indication lamp illuminate simultaneously loose key key and key then automatic s...

Страница 8: ...idly 3 times for II power supply priority 3 If I and II power supply indication lamps are flashing rapidly 3 times simultaneously it is no priority 8 FUNCTION OF TERMINALS Terminal A1 B1 C1 N1 is separately connected to A B C N of I power supply For HAT240A A1 N1 is separately connected to A and N of I power supply Terminal A2 B2 C2 N2 is separately connected to A B C and N of II power supply For ...

Страница 9: ...HAT220A HAT240A Automatic Transfer Switch Controller HAT220A HAT240A ATS Controller ISSUE 2011 05 20 Version1 1 Page 10 of 11 9 TYPICAL WIRING DIAGRAM HAT220A HAT240A ...

Страница 10: ...om Possible Remedy Controller no operation Check connection wirings of controller ATS is not working Check ATS Check the connection wirings between the controller and the ATS Electric parameters detecting error Check connection wirings of controller and amend detecting values of electric parameters Communication error with PC Check setting of communication port and its wirings ...