HAT220A/HAT240A    Automatic Transfer Switch Controller

 

HAT220A/HAT240A ATS Controller      ISSUE 2011-05-20      Version1.1          Page 4 of 11 

1  SUMMARY 

HAT220A/HAT240A  ATS  controller  has  microprocessor  as  its  core,  can  accurately 

detect 2 ways-3 phase, 2 ways-1 phase or 2ways-2phase voltage and also can make 

accurate  judgment  to  conditions  of  abnormal  voltage  (loss  of  electricity,  over  or  under 

voltage),  control  ATS  to  transfer  after  delay.  Controller  also  has  a  function  of  sending 

start signal to genset when one power is abnormal.   

2  PERFORMANCE AND CHARACTERISTICS 

Controller  detect  multi-voltage  conditions,  such  as  2ways-3phase  voltage,  1phase 

voltage  (could  be  2  ways  mains,  2ways  gens,  or  1mains-1gens),  or  2ways-2phase 

voltage. Its performance and characteristics show as following, 

◘ 

Realizing  the  computer  programming  control,  can  use  computer  to  set  abnormal 

voltage  delay,  switch  priority,  genset  shutdown  delay,  the  voltage  correction  and 

other functions, fully graphical interface operation. When programming by computer, 

the controller front panel must be opened, then use SG72 interface module (USB to 

LINK)  via  the  PC  test  software.  About  PC  software

’s  operation,  please  refer  to 

“software manual of HAT220A/HAT240A”. 

◘ 

The voltage normal delay of #I or #II can be set (0~60) seconds and the start Genset 

delay can be set (0~90) seconds. 

◘ 

The  voltage  abnormal  delay  of  #I  or  #II  can  be  set  (0~60)  seconds  and  the  stop 

Genset delay can be set (0~90) seconds. 

◘ 

“#I  power  supply  priority”,  “Auto/Manual”,  “No  priority”  and  “#II  power  supply   

priority

” can be set via controller front panel and in order to ensure #I power supply 

priority power on or #II , or no priority power on for examine and repair. 

◘ 

Design of 2 ways N line isolate. 

◘ 

LEDs mounted on front panel can clearly show ATS running status. 

◘ 

The  #I  and  #II  power  supply  transfer  relay

’s  (CLOSE  1#,  CLOSE  2#)  output 

contactor capacity is 16A 250VAC/16A 28VDC, and they belong to passive contactor, 

can be directly used in driving switch to transfer. 

◘ 

The Genset start relay

’s (GENS START) output contactor capacity is 7A 250VAC/7A 

28VDC, and they belong to passive normally closed contacts. 

◘ 

Controller has strong ability for anti-electromagnetic interference, and very suitable 

for using in strong electromagnetic interference of complex environment. 

◘ 

Modular  configuration  design,  Flame  Retardant  ABS  plastic  shell,  inserted  type 

Содержание HAT220A

Страница 1: ...HAT220A HAT240A ATS Automatic Transfer Switch CONTROLLER OPERATING MANUAL Smartgen Electronic ...

Страница 2: ...NCE AND CHARACTERISTICS 4 3 TECHNICAL SPECIFICATIONS 5 4 PANEL OPERATION INSTRUCTION 6 5 PANEL OPERATION AND DIAGRAM CONNECTION 6 5 1 DELAY ADJUSTMENT 6 5 2 RECOVER DEFAULT DELAYS VALUE 7 6 PROGRAMMED PARAMETER AND RANGE 7 7 OPERATION CONTROL 8 8 FUNCTION OF TERMINALS 9 9 TYPICAL WIRING DIAGRAM 10 10 OVERALL AND MOUNTING DIMENSIONS 11 11 FAULT FINDING 11 ...

Страница 3: ...SG72 interface module USB to LINK via the PC test software About PC software s operation please refer to software manual of HAT220A HAT240A The voltage normal delay of I or II can be set 0 60 seconds and the start Genset delay can be set 0 90 seconds The voltage abnormal delay of I or II can be set 0 60 seconds and the stop Genset delay can be set 0 90 seconds I power supply priority Auto Manual N...

Страница 4: ...edback time 5 seconds During break on procedure if switch break on status signal is detected break off immediately Power supply normal delay 0 60 seconds can be adjusted via controller front panel potentiometer Power supply abnormal delay 0 60 seconds can be adjusted via controller front panel potentiometer default setting 5 seconds Genset start delay after 1 abnormal delay 0 60 seconds can be adj...

Страница 5: ...t start delay can set genset start signal output delay after I power supply abnormal Procedures of setting I power supply abnormal delay II power supply abnormal delay and Genset stop delay show as following a Press key and key simultaneously when I power supply indication lamp automatic status indication lamp and II power supply indication lamp simultaneously illuminate loose key and key I power ...

Страница 6: ...uminate simultaneously loose key and key I power supply indication lamp automatic status indication lamp and II power supply indication lamp will not illuminate simultaneous controller enters into delay value setting status b Press key when I power supply indication lamp automatic status indication lamp and II power supply indication lamp illuminate simultaneously will restore factory setting valu...

Страница 7: ...ransfer into I power supply side and press key load transfer into II power supply side Procedures of setting I power supply priority II power supply priority and No priority show as following a Press key key and key simultaneously when I power supply indication lamp automatic status indication lamp and II power supply indication lamp illuminate simultaneously loose key key and key then automatic s...

Страница 8: ...idly 3 times for II power supply priority 3 If I and II power supply indication lamps are flashing rapidly 3 times simultaneously it is no priority 8 FUNCTION OF TERMINALS Terminal A1 B1 C1 N1 is separately connected to A B C N of I power supply For HAT240A A1 N1 is separately connected to A and N of I power supply Terminal A2 B2 C2 N2 is separately connected to A B C and N of II power supply For ...

Страница 9: ...HAT220A HAT240A Automatic Transfer Switch Controller HAT220A HAT240A ATS Controller ISSUE 2011 05 20 Version1 1 Page 10 of 11 9 TYPICAL WIRING DIAGRAM HAT220A HAT240A ...

Страница 10: ...om Possible Remedy Controller no operation Check connection wirings of controller ATS is not working Check ATS Check the connection wirings between the controller and the ATS Electric parameters detecting error Check connection wirings of controller and amend detecting values of electric parameters Communication error with PC Check setting of communication port and its wirings ...