MGC300 Genset Controller User Manual
MGC300 Genset Controller Version 1.1 2020-01-04 Page 13 of 27
5
PROTECTION
Table 5 Alarm Types
Icons
Alarm Contents
Type
Trigger
Over Frequency Stop
Shutdown Gen frequency is above over frequency limit for 2s, it
will issue alarm;
Under Frequency Stop
Shutdown Detected when genset is running normal; gen freq. is
less than under frequency limit for 10s, and it alarms.
Temp. High
Shutdown Detected after safety on delay; when temp. high is
above high temp. limit for 3s, it will issue alarm;
Temp. High Input
Shutdown Detected after safety on delay; when temp. high input is
active, it will issue alarm;
Oil Pressure Low Input Shutdown Detected after safety on delay; it alarms when oil
pressure low input is active;
Gen Over Current
Warning
Action is set to Warning; Gen current is over pre-set
value, and lasting time surpasses delay time, it alarms;
Gen Over Current
Shutdown Action is set to Shutdown; Gen current is over pre-set
value, and lasting time surpasses delay time, it alarms;
Gen
Over
Current
Cooling Shutdown
Shutdown Action is set to Cooling Shutdown; gen current is over
pre-set value and lasting time is over delay, it alarms;
Gen Voltage High
Shutdown Detected after safety on delay; gen voltage is over the
threshold, and this lasts for over delay, and it alarms;
Gen Voltage Low
Shutdown Detected after genset running; gen voltage is lower
than threshold for over the delay time, and it alarms;
Fail to Crank
Shutdown It alarms when starter doesn't start the engine in the
range of the pre-set start times;
Outside
Shutdown
Alarm Input
Shutdown When "outside shutdown alarm" is configured for the
input port, and when the input is active, it alarms;
Fuel Level Low
Warning
When fuel level is lower than the threshold for 10s, it
alarms;
Fuel Level Low Input
Warning
When fuel level low input is active, it alarms;
Fail to Stop
Warning
Complete stop time is over but genset still stops
completely and controller will alarm;
Battery Voltage Low
Warning
Battery voltage is lower than the threshold for 20s, it
alarms;
Battery Voltage High
Warning
Battery voltage is higher than the threshold for 20s, it
alarms;
NOTE 1
: Shutdown alarms are latched signals and alarms can be removed by using Stop key (in stop status); warning
alarms are not latched.