4.7
TERMINAL
No.
Function
Cable Size
Note
1
B-
1.0mm
2
Connected with negative of starter battery.
2
B+
1.0mm
2
Connected with positive of starter battery. 3A fuse
is recommended.
3
Aux. Input 1
1.0mm
2
Active when connect to B-.
4
Aux. Input 2
1.0mm
2
Active when connect to B-.
5
Aux. Output
Normally
Open
1.0mm
2
Normally open outputs, rated 1A DC30V
6
Common
1.0mm
2
7
Normally
Close
1.0mm
2
8
RS485 B(-)
MASTER
0.5mm
2
Impedance-
120Ω shielding wire is
recommended, its single-end earthed.
9
RS485 A(+)
0.5mm
2
10
SCR
0.5mm
2
11
RS485 B(-)
SLAVE
0.5mm
2
Impedance-
120Ω shielding wire is
recommended, its single-end earthed.
12
RS485 A(+)
0.5mm
2
13
SCR
0.5mm
2