CMM365-2G Cloud Monitoring Communication Module User Manual 

CMM365-2G Cloud Monitoring Communication Module          2016-11-14        Version 1.0        Page 11 of 19

 

14 

History Data Rest 

(0-3600)s 

History data upload rest. 

Note:

 No upload when it is 0s 

15 

Time Zone 

(-12-12) 

Time Zone 

16 

Live 

Data 

Upload 

Interval 

(1-20)s 

Interval  time  of  uploading  real  time 

data. 

Module Configuration Info 

Type 

(0-5) 

0:AMF module 

1:Single-unit self-starting module 

2: Single-single parallel module 

3:Mains-genset parallel module 

4:Mains-bus parallel module 

5:Bus-bus parallel module 

Note: 

The parameter will auto change 

according to genset type. 

Rated Speed 

(0-6000)r/min 

1500 

Rated Speed 

AC Supply 

(0-3) 

0:3P4W;1:3P3W;2:2P3W;3:1P2W

 

Rated Volt 

(30-30000)V 

230 

Rated Volt 

Rated Freq 

(10-600)Hz 

50 

Rated Freq 

Rated Current 

(5-6000)A 

500 

Rated Current 

Rated Power 

(0-6000)kW 

276 

Rated Power 

Custom Description 1  (0-65535) 

Custom  Description  (20  Chinese  characters, 

letters or numbers) 

Custom Description 2  (0-65535) 

Custom  Description  (20  Chinese  characters, 

letters or numbers) 

10 

Custom Description 3  (0-65535) 

Custom  Description  (20  Chinese  characters, 

letters or numbers) 

11 

Custom Description 4  (0-65535) 

Custom  Description  (20  Chinese  characters, 

letters or numbers) 

12 

Custom Description 5  (0-65535) 

Custom  Description  (20  Chinese  characters, 

letters or numbers) 

Digital Input 

Digital Input 1 

Setting 

(0-9) 

Default: Not used 

Type 

(0-1) 

0:Active when close 

1:Active when open 

See: Form2 

Delay 

(0-20.0) 

0.0 

Action delay 

Digital Input 2 

Setting 

(0-9) 

Default: Lamp test 

Type 

(0-1) 

0:Active when close 

1:Active when open 

See: Form2 

Delay 

(0-20.0) 

0.0 

Action delay 

Digital Output 

Setting 

(0-14) 

Default: Not used 

See: Form3 

Содержание CMM365-2G

Страница 1: ...CMM365 2G CLOUD MONITORING COMMUNICATION MODULE USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ...

Страница 2: ...PTION 6 4 1 PANEL INDICATOR AND BUTTONS 6 4 2 GPRS 7 4 3 MASTER RS485 7 4 4 SLAVE RS485 7 4 5 LINK 8 4 6 USB DEVICE 8 4 7 TERMINAL 9 5 PROGRAMMABLE PARAMETERS 10 5 1 CONTENTS AND SCOPES OF PARAMETERS 10 5 2 PC CONFIGURATION INTERFACE 14 6 SMS FUNCTION AND REMOTE CONTROL 15 6 1 SMS SHORT MESSAGE ALARM 15 6 2 GSM SHORT MESSAGE REMOTE CONTROL 15 7 SYSTEM DIAGRAM 16 8 CASE DIMENSION AND INSTALLATION 1...

Страница 3: ...is publication may be reproduced in any material form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above Any reference to trademarked product names used w...

Страница 4: ...f international first class brands 3 Widely power supply DC 8 35 V can direct use genset build in battery 4 With ARM based 32 bit SCM high integration of hardware and strong programming ability 5 Include with GPS locate function to achieve gain location information and locate genset 6 Take JSON network data communication protocol upload real time data variation and take compression algorithm to va...

Страница 5: ...onsumption Standby 2W Working 5W Auxiliary Input Volt Free Digital Input Auxiliary Output 1A DC30V Volt free output Master RS485 Non seclusion type Slave RS485 Seclusion type LINK SmartGen exclusive port USB Device B type USB mother port GPRS Port Standard SMB port female SMB port male for antenna Case Dimensions 73mmx105mmx35mm Working Conditions Temperature 25 70 C Humidity 20 93 RH Storage Cond...

Страница 6: ...xtinguish RS485 disabled Normally Light Communication fail Blink Communication normal RS485 SLAVE Red Normally Extinguish Not communication Blink Communication normal GPRS Red Extinguish CMM365 2G login with server unsuccessfully Light Login with server successfully Blink Real time communication normal LINK Red Normally Extinguish Disabled Normally Light Communication fail Blink Communication norm...

Страница 7: ...set data information via RS485 port connects to Genset control module s RS485 port Add 120Ω terminal resistance is recommended if fail to communicate Shielding wire one end connects to SCR and the other one hang in the air RS485 Connection Diagram is as follows 4 4 SLAVE RS485 Connect to RS485 port of dynamic environment monitoring system via slave RS485 port then dynamic environment system will a...

Страница 8: ...n 1 0 Page 8 of 19 4 5 LINK Achieving genset data information via LINK port connects to Genset control module s LINK port RS485 Connection Diagram is as follows 4 6 USB DEVICE Set up all the parameters and view CMM365 2G ID Login password by CMM365 USB port connecting with PC USB port USB and PC connection diagram is follows ...

Страница 9: ...er battery 3A fuse is recommended 3 Aux Input 1 1 0mm2 Active when connect to B 4 Aux Input 2 1 0mm2 Active when connect to B 5 Aux Output Normally Open 1 0mm2 Normally open outputs rated 1A DC30V 6 Common 1 0mm2 7 Normally Close 1 0mm2 8 RS485 B MASTER 0 5mm2 Impedance 120Ω shielding wire is recommended its single end earthed 9 RS485 A 0 5mm2 10 SCR 0 5mm2 11 RS485 B SLAVE 0 5mm2 Impedance 120Ω s...

Страница 10: ...0 7 SMS Warning 0 1 0 8 Phone Number Set Max 20 bits Area code needed to be added before the phone number E g China 8613666666666 Cloud Server 1 Auto Gain Comm Port 0 1 1 0 Disabled 1 Enabled 2 ID 1 254 1 Module ID 3 Communication Port 0 4 2 0 Disabled 1 LINK 2 RS485 3 RS232 4 USB 4 Baud Rate 0 2 0 0 9600bit s 1 19200bit s 2 115200bit s 5 Location Info 0 1 0 0 Disabled 1 Manual input location info...

Страница 11: ...5 Rated Freq 10 600 Hz 50 Rated Freq 6 Rated Current 5 6000 A 500 Rated Current 7 Rated Power 0 6000 kW 276 Rated Power 8 Custom Description 1 0 65535 Custom Description 20 Chinese characters letters or numbers 9 Custom Description 2 0 65535 Custom Description 20 Chinese characters letters or numbers 10 Custom Description 3 0 65535 Custom Description 20 Chinese characters letters or numbers 11 Cus...

Страница 12: ...used Output port won t output when this item is selected 1 Digital Input 1 Active Output when auxiliary input 1 is active 2 Digital Input 2 Active Output when auxiliary input 2 is active 3 RS485 Comm Fail RS485 communication fails 4 Network Comm Fail Network communication fails 5 LINK Comm Fail LINK communication fails 6 RS232 Comm Fail RS232 communication fails 7 Common Alarm Output when there is...

Страница 13: ...a DSE7110MKII Single unit self starting module DSE7120MKII AMF module DSE7210 Single unit self starting module DSE7220 AMF module DSE7310 Single unit self starting module DSE7320 AMF module DSE7410 Single unit self starting module DSE7420 AMF module DSE7450 Single unit self starting module DSE8610 Single single parallel module DSE8620 Mains single parallel module ComAp MRS10 Ⅱ Single unit self sta...

Страница 14: ...loud Monitoring Communication Module 2016 11 14 Version 1 0 Page 14 of 19 5 2 PC CONFIGURATION INTERFACE The USB port of CMM366 3G communication module connects PC port to configure the parameters Gateway Configuration Cloud Server Configuration Module Monitoring Interface ...

Страница 15: ...Orders Pass Back Information Description 1 SMS GENSET GENSET ALARM When genset is stopping alarm status of genset SYSTEM IN STOP MODE GENSET AT REST At rest status in stop mode SYSTEM IN MANUAL MODE GENSET AT REST At rest status in manual mode SYSTEM IN TEST MODE GENSET AT REST At rest status in test mode SYSTEM IN AUTO MODE GENSET AT REST At rest status in auto mode SYSTEM IN STOP MODE GENSET IS ...

Страница 16: ...o follow SMS orders in above form and all the letters must be capital NOTE Pass back information from SMS DETAIL including working mode mains voltage generator voltage load current mains frequency generator frequency active power apparent power power factor battery voltage D voltage water temperature oil pressure oil level engine speed total running time genset status and alarm status 7 SYSTEM DIA...

Страница 17: ...ud Monitoring Communication Module 2016 11 14 Version 1 0 Page 17 of 19 8 CASE DIMENSION AND INSTALLATION 2 ways for installation 35mm guide rail in box or screw M4 installation as below CMM365 2G Case Dimension CMM365 2G Guide Rail Installation CMM365 2G Screw Installation ...

Страница 18: ...onnection wirings GPRS Indicator Not Light Check SIM card is inserted or not Check GPRS antenna is connected or not RS485 Communication Abnormal Check connections Check RS485 port is enabled or not Check settings of genset ID and baud rate are correct or not Check RS485 s connections of A and B is reverse connect or not LINK Communication Abnormal Check connections Check LINK port is enabled or no...

Страница 19: ...65 2G Cloud Monitoring Communication Module 2016 11 14 Version 1 0 Page 19 of 19 10 ENCLOSE PACKING LIST No Name Number Remark 1 CMM365 2G 1 2 Osculum Type GSM Antenna 1 3 120Ω Matched Resistance 4 4 Certification 1 5 User Manual 1 _________________________________ ...

Отзывы: