BAC2405 BATTERY CHARGER USER MANUAL
BAC2405 Battery Charger Version 1.1 2017-11-09 Page 7 of 7
7.2 BAC2405 TROUBLESHOOTING
7.2.1 FAULT DIAGNOSIS
Output terminal of battery charger short circuit or battery reverse connection may blow the charger
output fuse. In that case, after connecting AC power supply, charger green LED lights up but output
terminal without voltage outputting, and then remove the output fuse tube to visually observe whether
fuse is blown or not, if condition permit, multimeter can be used to measure the fuse status.
a) If output terminal 10A fuse is blown, users only need to change the same capacity fuse.
b)
If output fuse isn‟t blown or battery without outputting after changing the fuse, battery needs to depot
repair.
c) Fuse burn emergency method: using conductive metal wire short connected burnt fuse, and then
change the fuse later.
7.2.2 PROCEDURES OF CHANGING FUSE
a) Press hard on the slotted screwdriver, screw counter-clockwise and then take out the
fuse.( improper operation or over tightening may damage the block)
b) Put a new fuse into the block, press the slotted screwdriver and screw clockwise.
8 CASE DIMENSIONS