6  VOLTAGE/CURRENT REGULATION 

6.1 VOLTAGE REGULATION 

      If adjust voltage on-site, battery need to be disconnected with battery charger, and then adjust the 

voltage potentiometer (VOLT) to the appropriate value while measuring the charger output voltage.   

6.2 CURRENT REGULATION 

      After connecting output port to the storage battery, measuring charging current under 25.0V charging 

voltage, and then adjust the current potentiometer (AMP) to the appropriate value. Current also can be 

estimated according to the scale of the current potentiometer. 

7  OPERATION   

7.1 MASK DESCRIPTION   

 

─ 

Connect  terminals  L  and  N  to  alternating  voltage  (100~240)V,  using  BVR  1mm

2

 

multi-strand copper line. 

─ 

Connect B+ and B- to battery positive and negative using multi-strand BVR1.5mm

2

 copper 

wires. 

─ 

POWER: power supply indicator, illuminated when the charger is operating normally.   

─ 

CHARGING:  charging  indicator,  illuminated  when  charging  current  exceeds  0.5A  while 

extinguished when charging current has fallen below 0.5A. 

─ 

VOLT: charging voltage regulator-potentiometer 

─ 

AMP: charging current regulator-potentiometer   

─ 

FUSE:  output  fuse;  rated  current:  10A.  If  connected  in  the  wrong  way,  the  fuse  will  be 

burnt out and then voltage free. In this case connect cables correctly, replace the fuse and 

the system will continue to operate normally. 

  NOTE: 

1)  Because  there  is  diode  and  current-limiting  circuit  inner  the  charger,  it  can  be  used  together  with  charging 

generator, and there is no need to disconnect the charger when cranking 

2)  During  genset  is  running,  high  current  will  cause  voltage  drop  in  charging  line,  so  recommend  separately 

connecting to battery terminal to avoid disturbance on sampling precision. 

   

 
 
 
 

Содержание BAC2405

Страница 1: ...BAC2405 BATTERY CHARGER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ...

Страница 2: ...nt can be adjusted via potentiometer on the spot Suitable for 24V storage battery and the rated current is 5A LED display Power indication and charging indication 3 CHARGING PRINCIPLE Charging is performed according to the battery charging characteristics using two stage method Charging type is constant current type which means that when the battery terminal voltage falls below the pre set value c...

Страница 3: ...put Characteristics No load Output Voltage 27 6V Error 1 Rated Charging Current 5A Error 2 Max Output Power 135W Insulating Property Insulation Resistance Between input and output input and shell both are DC500V 1min RL 500MΩ Insulation Voltage Between input and output input and shell both are AC1500V 50Hz 1min leakage current IL 3 5mA Working Condition Working Temperature 30 55 C Storage Temperat...

Страница 4: ...d B to battery positive and negative using multi strand BVR1 5mm2 copper wires POWER power supply indicator illuminated when the charger is operating normally CHARGING charging indicator illuminated when charging current exceeds 0 5A while extinguished when charging current has fallen below 0 5A VOLT charging voltage regulator potentiometer AMP charging current regulator potentiometer FUSE output ...

Страница 5: ... multimeter can be used to measure the fuse status a If output terminal 10A fuse is blown users only need to change the same capacity fuse b If output fuse isn t blown or battery without outputting after changing the fuse battery needs to depot repair c Fuse burn emergency method using conductive metal wire short connected burnt fuse and then change the fuse later 7 2 2 PROCEDURES OF CHANGING FUSE...

Отзывы: