BAC150CAN Battery Charger User Manual
BAC150CAN Battery Charger Version 1.0 2019-03-05 Page 8 of 13
5 PARAMETERS CONFIGURATION
Table 3 Parameter Configuration
Items
Default
Adjustable Range
Description
12V
24V
12V
24V
Battery Selection
2
(0~2)
0: 12V
1: 24V
2: Self-adjusted
Charging Method
3
(2~3)
2: Two-stage;
3: Three-stage
Max. Rated Current 5.0A
/
Maximum charging current
Rated Current
100%
(0~100)%
Maximum rated charging current
percentage
Even
Charging
Voltage
14.1V
28.2V
(10~16)V (20~30)V
The charging voltage of “Constant
Voltage”
Even
Charging
Enable
1
(0~1)
0: Disable; 1: Enable
Even
Charging
Time Setting
1.0h
(0.1~100)h
The charging time of Constant
Voltage
Even
Charging
Completion Current
1
(0~1)
0: Disable; 1: Enable
Completion Current
Setting
0.50A
(0.20~3.00)A
The transition current from Even
Charging to Float Chargeing
Float
Charge
Voltage
13.5V
27.0V
(10~16)V (20~30)V
The voltage of “Float Charge”
AUTO
BOOST
Voltage
12V
24V
(10~16)V (20~30)V
When the charger is in Float Mode,
it enters Quick Charge if the battery
voltage has fallen below this value.
AUTO
BOOST
Voltage Delay
20s
(0~3600)s
When the battery voltage is below
this value for the delay time, it gets
into BOOST status.
Trickle Charge
0
(0~1)
0: Disable; 1: Enable
Trickle
Charge
Voltage
11.0V
22.0V
(10~16)V (20~30)V
The voltage of Trickle Charge
Trickle
Charge
Current
50%
(0~100)%
Maximum rated charging current
percentage
Battery
Under
Voltage Warn
1
(0~1)
0: Disable; 1: Enable
Under Voltage Set
Value
11.5V
23.0V
(8~15)V
(16~30)V
Under voltage alarm will be
initiated if the battery voltage has
fallen below the set value.
Under
Voltage
Delay
120s
(0~3600)s
Under voltage alarm will be
initiated if the battery voltage has
fallen below the set value and the
delay timer has expired.