Longo programmable controller LPC-2.C06
11 Error in reception
→
Maximum receive timeout [Rx_Timeout_Max]:
Maximal timeout between received data
bytes in received telegram.
Type: UINT
Raw to engineering data:
0 .. 65535 0 .. 65535 us
→
Output
Protocol type [Protocol_Type]:
Selector of protocol type. Intended for future use.
Type: USINT
Raw to engineering data:
0 Universal
→
2 .. 255 Custom protocols. If custom protocol is
→
not implemented universal protocol is used.
Protocol option [Protocol_Option]:
Protocol options.
Type: USINT
Raw to engineering data:
xxxxxxx0 RS485
→
xxxxxxx1 RS232
→
Xxxxxx0x Normal TTL Tx signal
→
xxxxxx1x Inverted TTL Tx signal
→
xxxxx0xx Normal RS232 and inverted TTL Rx signal
→
xxxxx1xx Inverted RS232 and normal TTL Rx signal
→
UART speed [UART_Speed]:
Selector of baudrate.
Type: USINT
Raw to engineering data:
0 300
→
1 600
→
2 1200
→
3 2400
→
4 4800
→
5 9600
→
6 19200 (default)
→
7 38400
→
8 57600
→
9 115200
→
other 19200
→
UART parity [UART_Parity]:
Selector of parity.
Type: USINT
Raw to engineering data:
0 No parity bit
→
1 Odd
→
2 Even
→
other No parity bit
→
UART databits [UART_Databits]:
Number
of data bits.
5